Caratteristiche del prodotto:
| Specifica | BRPV3-600 | |
| Classificazione SPD secondo EN61643-31 / IEC61643-31 | Tipo 2/Classe II | |
| Massimo. funzionamento continuo c.c. voltaggio | Ucpv | 600 V |
| Corrente di scarica nominale (8/20μs) | In | 20kA |
| Massimo. corrente di scarica (8/20μs) | Imax | 40kA |
| Livello di protezione della tensione [(DC+/DC-)→PE] | Su | ≤2,2kV |
| Tempo di risposta | tA | ≤25ns |
| Intervallo di temperatura operativa | Tu | -40℃-80℃ |
| Indicazione dello stato operativo/guasto | verde/rosso | |
| Area della sezione trasversale (Min.) | 4mm² | |
| Area della sezione trasversale (max.) | 35 mm² | |
| Per il montaggio | Guida DIN da 35 mm | |
| Materiale della custodia | Termoplastico UL94-V0 | |
| Grado di protezione | IP20 | |
| Codice ordine | B18009 | |
| Codice d'ordine (con segnale remoto) | B18011 |
Caratteristiche:
PV voltage up to 600Vdc.
According to type 2 / class II EN61643-31 and IEC61643-31.
Con contatto di segnalazione remota.
Optical status indicator.
Designed for 35 mm DIN rails.
High temperature and resistant flame retardant plastic shel.
BRPV3-600 are designed to protect against lightning surge voltages in photovoltaic power supply networks.
Lightning protection main device and the base can be separated, is pluggable type.
Applicazione:
Protect against lightning surge voltages in solar system (photovoltaic power supply system).
Suitable for the new energy wind power generation system.
Suitable for solar DC power distribution system of lightning protection, such as solar PV combiner box, PV DC power distribution cabinet, grid tie inverter, etc.
Widely used in the DC power lightning protection of solar power systems, mobile communication base stations, microwave communications bureau, telecommunications room, plant, civil aviation, finance, securities and other system.
Installation instruction:
Installed on the fount of the low-voltage distribution system.
Installed in the main power system at DC circuit, to protect against the indirect lighting current, direct lighting current or other instantaneous over voltage.