BR-80 3P Type 2 80kA Surge Protective Device For TN-C

Ottieni un preventivo
Descrizione

Caratteristiche del prodotto:

Specifica BR-80 150 3P BR-80 275 3P BR-80 320 3P BR-80 385 3P
SPD classification according to EN61643-11 Tipo 2 Tipo 2 Tipo 2 Tipo 2
SPD classification according to IEC61643-11 Class II Class II Class II Class II
Max. continuous operating a.c. voltage Uc 150V 275V 320V 385V
Corrente di scarica nominale (8/20μs) In 40kA 40kA 40kA 40kA
Massimo. corrente di scarica (8/20μs) Imax 80kA 80kA 80kA 80kA
Livello di protezione della tensione Su ≤1.0kV ≤1.7kV ≤2.0kV ≤2.3kV
Voltage protection level 5kA Su ≤0.6kV ≤1.0kV ≤1.1kV ≤1.2kV
Max. backup fuse 160A gG 160A gG 160A gG 160A gG
Short-circuit withstand capacity Isccr 25kA 25kA 25kA 25kA
Temporary overvoltage TOV-withstand UT 180V/5sec. 335V/5sec. 400V/5sec. 500V/5sec.
Temporary overvoltage TOV-safe failure UT 230V/120min. 440V/120min. 520V/120min. 650V/120min.
Tempo di risposta tA ≤25ns ≤25ns ≤25ns ≤25ns
Intervallo di temperatura operativa Tu -40℃-80℃ -40℃-80℃ -40℃-80℃ -40℃-80℃
Operating state/fault indication green/red green/red green/red green/red
Area della sezione trasversale (Min.) 4mm² 4mm² 4mm² 4mm²
Area della sezione trasversale (max.) 35 mm² 35 mm² 35 mm² 35 mm²
Per il montaggio Guida DIN da 35 mm
Materiale della custodia Thermoplastic   UL94-V0
Grado di protezione IP20 IP20 IP20 IP20
Order Code B18268 B18270 B18272 B18274
Order Code (With remote signaling) B18269 B18271 B18273 B18275

Caratteristiche:

Visual status display

Labeled connections

Type 2 (class II/C) for main boards, distribution boards and consumer units.

Available with and without remote signalling contacts.

1 pole up to 4 poles protected.

BR-80 consists of a high performance varistor block with thermal disconnection device. The plug-in module/base design facilitates replacement of a failed module in situ without the need to remove system wiring.

Solutions to meet IEC 61643-1 and EN 61643-11

Applicazione:

Distribution switch board located downstream from a Type 1 Lightning Current Arrester.

Protecting them from direct and indirect lightning impulse and other transient overvoltage.

Protects low-voltage systems against overvoltage triggered by lightning strikes or grid switching operations.

Ideal for industrial applications.

At the origin of the electrical installation in the main switchboard, in areas where electromagnetic fields caused by lightning currents are dominant (excluding a direct strike).

Suitable for TN-C systems.

Preventing the spread of medium overvoltage (Up) in the electrical installation and protecting equipment that is connected to it.

 

SIAMO QUI PER SUPPORTARTI!

Ulteriori informazioni o una consulenza personale? I nostri prodotti e il nostro know-how sono lì per fornire soluzioni.

PRODOTTI CORRELATI
NOTIZIE CORRELATE
POTRESTI ANCHE VEDERE
OTTIENI LA ​​PROTEZIONE DA SOVRATENSIONE
LA SOLUZIONE OGGI!
icona
icona
Seraphinite AcceleratorOptimized by Seraphinite Accelerator
Turns on site high speed to be attractive for people and search engines.