Caratteristiche del prodotto:
| Specifica | BR-80 150 2P | BR-80 275 2P | BR-80 320 2P | BR-80 385 2P | ||
| SPD classification according to EN61643-11 | Tipo 2 | Tipo 2 | Tipo 2 | Tipo 2 | ||
| SPD classification according to IEC61643-11 | Class II | Class II | Class II | Class II | ||
| Max. continuous operating a.c. voltage | Uc | 150V | 275V | 320V | 385V | |
| Corrente di scarica nominale (8/20μs) | In | 40kA | 40kA | 40kA | 40kA | |
| Massimo. corrente di scarica (8/20μs) | Imax | 80kA | 80kA | 80kA | 80kA | |
| Livello di protezione della tensione | Su | ≤1.0kV | ≤1.7kV | ≤2.0kV | ≤2.3kV | |
| Voltage protection level 5kA | Su | ≤0.6kV | ≤1.0kV | ≤1.1kV | ≤1.2kV | |
| Max. backup fuse | 160A gG | 160A gG | 160A gG | 160A gG | ||
| Short-circuit withstand capacity | Isccr | 25kA | 25kA | 25kA | 25kA | |
| Temporary overvoltage TOV-withstand | UT | 180V/5sec. | 335V/5sec. | 400V/5sec. | 500V/5sec. | |
| Temporary overvoltage TOV-safe failure | UT | 230V/120min. | 440V/120min. | 520V/120min. | 650V/120min. | |
| Tempo di risposta | tA | ≤25ns | ≤25ns | ≤25ns | ≤25ns | |
| Intervallo di temperatura operativa | Tu | -40℃-80℃ | -40℃-80℃ | -40℃-80℃ | -40℃-80℃ | |
| Operating state/fault indication | green/red | green/red | green/red | green/red | ||
| Area della sezione trasversale (Min.) | 4mm² | 4mm² | 4mm² | 4mm² | ||
| Area della sezione trasversale (max.) | 35 mm² | 35 mm² | 35 mm² | 35 mm² | ||
| Per il montaggio | Guida DIN da 35 mm | |||||
| Materiale della custodia | Thermoplastic UL94-V0 | |||||
| Grado di protezione | IP20 | IP20 | IP20 | IP20 | ||
| Order Code | B18276 | B18278 | B18280 | B18282 | ||
| Order Code (With remote signaling) | B18277 | B18279 | B18281 | B18283 | ||
Caratteristiche:
Class II, Type 2, 80kA 2P.
Discharge currents : In : 40 kA / Imax : 80 kA.
IEC 61643-11 and EN 61643-11 compliance.
BR-80 is DIN rail compatible and is built with a plug-in module and a fixed base.
The BR-80 protects against the direct and indirect lightning strikes and large switching transients.
They are particularly useful in areas where space is limited.
Version with a remote signaling for disconnection indication is also available.
Applicazione:
Widely appreciated for its high level of protection, efficiency, and reliable performance, these single phase surge protectors are vastly used for protecting electrical devices such as computers, TVs, and other devices.
Application in industrial plants, commercial buildings, institutional facilities, and corporate offices.
For use in the Lightning Protection Zones Concept at the boundaries of LPZ 1-2 (according to IEC 1312-1 and EN62305).
Ulteriori informazioni o una consulenza personale? I nostri prodotti e il nostro know-how sono lì per fornire soluzioni.