BR-7M Dispositivo di protezione contro le sovratensioni 2P 7kA Tipo 1+2 / B+C per TNS

Ottieni un preventivo
Descrizione

Caratteristiche del prodotto:

Specifica BR-7M 150 2P BR-7M 275 2P BR-7M 320 2P
SPD classification according to EN61643-11 Type 1 + Type 2 Type 1 + Type 2 Type 1 + Type 2
SPD classification according to IEC61643-11 Class I + Class II Class I + Class II Class I + Class II
Max. continuous operating a.c. voltage Uc 150V(50/60Hz) 275V(50/60Hz) 320V(50/60Hz)
Corrente impulsiva di fulmine (10/350μs) Iimp 7kA 7kA 7kA
Corrente di scarica nominale (8/20μs) In 20kA 20kA 20kA
Massimo. corrente di scarica (8/20μs) Imax 50kA 50kA 50kA
Specific energy W/R 12.25kJ/Ω 12.25kJ/Ω 12.25kJ/Ω
Livello di protezione della tensione Su ≤0.8kV ≤1.3kV ≤1.5kV
Short-circuit current rating a.c. Isccr 25kA rms 25kA rms 25kA rms
Max. backup fuse 125A gG 125A gG 125A gG
Temporary overvoltage TOV-withstand UT(L-N) 180V/5sec. 335V/5sec. 400V/5sec.
Temporary overvoltage TOV-safe failure UT(L-N) 230V/120min. 440V/120min. 520V/120min.
Tempo di risposta tA ≤25ns ≤25ns ≤25ns
Intervallo di temperatura operativa Tu -40℃-80℃ -40℃-80℃ -40℃-80℃
Operating state/fault indication green/red green/red green/red
Area della sezione trasversale (Min.) 4mm² 4mm² 4mm²
Area della sezione trasversale (max.) 35 mm² 35 mm² 35 mm²
Per il montaggio Guida DIN da 35 mm
Materiale della custodia Termoplastico UL94-V0
Grado di protezione IP20 IP20 IP20
Order Code B17312 B17314 B17316
Order Code (With remote signaling) B17313 B17315 B17317

Caratteristiche:

BR-7M high energy modular SPD is designed according to IEC standard.

This model designed in modular with excellent airtight property.

It is with 35mm din rail, which make it easy for installation.

Applicazione:

It could be installed in 275V/320V AC power system.

This product is especially suitable for application in the A grade Lightning Protection in high risk area of lightning strike.

Installazione:

The protector is installed with standard 35mm track.

The protector is connected by 4 ~ 35mm copper wire.

No need to adjust after the protector is installed as required.

During operation, regularly check whether the module is red; replace the failed component in time.

 

SIAMO QUI PER SUPPORTARTI!

Ulteriori informazioni o una consulenza personale? I nostri prodotti e il nostro know-how sono lì per fornire soluzioni.

PRODOTTI CORRELATI
NOTIZIE CORRELATE
POTRESTI ANCHE VEDERE
OTTIENI LA ​​PROTEZIONE DA SOVRATENSIONE
LA SOLUZIONE OGGI!
icona
icona
Seraphinite AcceleratorOptimized by Seraphinite Accelerator
Turns on site high speed to be attractive for people and search engines.