Caratteristiche del prodotto:
| Specifica | BR-7M 150 1P | BR-7M 275 1P | BR-7M 320 1P | |
| SPD classification according to EN61643-11 | Type 1 + Type 2 | Type 1 + Type 2 | Type 1 + Type 2 | |
| SPD classification according to IEC61643-11 | Class I + Class II | Class I + Class II | Class I + Class II | |
| Max. continuous operating a.c. voltage | Uc | 150V(50/60Hz) | 275V(50/60Hz) | 320V(50/60Hz) |
| Corrente impulsiva di fulmine (10/350μs) | Iimp | 7kA | 7kA | 7kA |
| Corrente di scarica nominale (8/20μs) | In | 20kA | 20kA | 20kA |
| Massimo. corrente di scarica (8/20μs) | Imax | 50kA | 50kA | 50kA |
| Specific energy | W/R | 12.25kJ/Ω | 12.25kJ/Ω | 12.25kJ/Ω |
| Livello di protezione della tensione | Su | ≤0.8kV | ≤1.3kV | ≤1.5kV |
| Short-circuit current rating a.c. | Isccr | 25kA rms | 25kA rms | 25kA rms |
| Max. backup fuse | 125A gG | 125A gG | 125A gG | |
| Temporary overvoltage TOV-withstand | UT(L-N) | 180V/5sec. | 335V/5sec. | 400V/5sec. |
| Temporary overvoltage TOV-safe failure | UT(L-N) | 230V/120min. | 440V/120min. | 520V/120min. |
| Tempo di risposta | tA | ≤25ns | ≤25ns | ≤25ns |
| Intervallo di temperatura operativa | Tu | -40℃-80℃ | -40℃-80℃ | -40℃-80℃ |
| Operating state/fault indication | green/red | green/red | green/red | |
| Area della sezione trasversale (Min.) | 4mm² | 4mm² | 4mm² | |
| Area della sezione trasversale (max.) | 35 mm² | 35 mm² | 35 mm² | |
| Per il montaggio | Guida DIN da 35 mm | |||
| Materiale della custodia | Termoplastico UL94-V0 | |||
| Grado di protezione | IP20 | IP20 | IP20 | |
| Order Code | B17318 | B17320 | B17322 | |
| Order Code (With remote signaling) | B17319 | B17321 | B17323 | |
Caratteristiche:
The technical performance of the products meets the standard technical equipment of GB18802.1 and IEC61643-11.
It adopts 35mm standard rail.
This model designed in modular with excellent airtight property.
It is with 35mm din rail, which make it easy for installation.
Applicazione:
Installation at LPZ 0 -1 or higher, protecting low voltage equipment.
Applied in PSD Class I+II (Class B+C).
Connected to AC low-voltage power systems for protection of equipment from transient over-voltage caused by the inducted lightning stroke or internal power systems.
Installazione:
The protector is installed with standard 35mm track.
The protector is connected by 4 ~ 35mm copper wire.
No need to adjust after the protector is installed as required.
During operation, regularly check whether the module is red; replace the failed component in time.
Ulteriori informazioni o una consulenza personale? I nostri prodotti e il nostro know-how sono lì per fornire soluzioni.