Caratteristiche del prodotto:
| Specifica | BR-60 150 1P | BR-60 275 1P | BR-60 320 1P | BR-60 385 1P | ||
| SPD classification according to EN61643-11 | Tipo 2 | Tipo 2 | Tipo 2 | Tipo 2 | ||
| SPD classification according to IEC61643-11 | Class II | Class II | Class II | Class II | ||
| Max. continuous operating a.c. voltage | Uc | 150V | 275V | 320V | 385V | |
| Corrente di scarica nominale (8/20μs) | In | 30kA | 30kA | 30kA | 30kA | |
| Massimo. corrente di scarica (8/20μs) | Imax | 60kA | 60kA | 60kA | 60kA | |
| Livello di protezione della tensione | Su | ≤1.0kV | ≤1.6kV | ≤1.8kV | ≤2,2kV | |
| Voltage protection level 5kA | Su | ≤0.5kV | ≤0.6kV | ≤1.0kV | ≤1.2kV | |
| Max. backup fuse | 160A gG | 160A gG | 160A gG | 160A gG | ||
| Short-circuit withstand capacity | Isccr | 25kA | 25kA | 25kA | 25kA | |
| Temporary overvoltage TOV-withstand | UT | 180V/5sec. | 335V/5sec. | 400V/5sec. | 500V/5sec. | |
| Temporary overvoltage TOV-safe failure | UT | 230V/120min. | 440V/120min. | 520V/120min. | 650V/120min. | |
| Tempo di risposta | tA | ≤25ns | ≤25ns | ≤25ns | ≤25ns | |
| Intervallo di temperatura operativa | Tu | -40℃-80℃ | -40℃-80℃ | -40℃-80℃ | -40℃-80℃ | |
| Operating state/fault indication | green/red | green/red | green/red | green/red | ||
| Area della sezione trasversale (Min.) | 4mm² | 4mm² | 4mm² | 4mm² | ||
| Area della sezione trasversale (max.) | 35 mm² | 35 mm² | 35 mm² | 35 mm² | ||
| Per il montaggio | Guida DIN da 35 mm | |||||
| Materiale della custodia | Thermoplastic UL94-V0 | |||||
| Grado di protezione | IP20 | IP20 | IP20 | IP20 | ||
| Order Code | B18791 | B18793 | B18795 | B18797 | ||
| Order Code (With remote signaling) | B18792 | B18794 | B18796 | B18798 | ||
Caratteristiche:
Modular SPD.
Type 2.
SPD BR-60 is for Imax 60kA.
The core parts are metal oxide vristor components with high discharge capacity.
Supplied with replaceable cartridges and operational indicator.
Remote signaling contact for control device: optional.
Working temperature: -40°C-80°C; Relative humidity: 5%-95%.
Housing protection level (IEC 60529): IP20.
Housing material fram-retarded level (Ul94): UL94-V0.
Applicazione:
Used for AC power line of house, bank, telecom tower and so on.
It’s to provide economical and reliable protection to primary distribution panel boards and power distribution systems.
It’s applied in low-voltage power supply and distribution systems such as computer room equipment, monitoring room equipment, fire control room equipment, telephone room, other low-voltage rooms, offices, and household electrical equipment forpreventing them from indirect lightning strike and surges.
Ulteriori informazioni o una consulenza personale? I nostri prodotti e il nostro know-how sono lì per fornire soluzioni.