BR-50GR Scaricatore di sovratensione 4P Tipo 1 50kA per TNS

Ottieni un preventivo
Descrizione

Caratteristiche del prodotto:

Specifica BR-50GR 150 4P BR-50GR 275 4P BR-50GR 350 4P
SPD classification according to EN61643-11 Type 1 + Type 2 Type 1 + Type 2 Type 1 + Type 2
SPD classification according to IEC61643-11 Class I + Class II Class I + Class II Class I + Class II
Nominal operating voltage Un 120V/240V(50/60Hz) 230V/400V(50/60Hz) 250V/440V(50/60Hz)
Max. continuous operating a.c. voltage Uc 150V(50/60Hz) 275V(50/60Hz) 350V(50/60Hz)
Corrente impulsiva di fulmine (10/350μs) Iimp 50kA 50kA 50kA
Corrente di scarica nominale (8/20μs) In 50kA 50kA 50kA
Massimo. corrente di scarica (8/20μs) Imax 160kA 160kA 160kA
Quantity of electric charge Q 25As 25As 25As
Specific energy W/R 625kJ/Ω 625kJ/Ω 625kJ/Ω
Livello di protezione della tensione Su ≤1.5kV ≤1.5kV ≤1.5kV
Short-circuit current rating a.c. Isccr 25kA rms 25kA rms 25kA rms
Max. backup fuse 350A gG 350A gG 350A gG
Temporary overvoltage TOV-withstand UT 230V/120min. 440V/120min. 580V/120min.
Tempo di risposta tA ≤100ns ≤100ns ≤100ns
Intervallo di temperatura operativa Tu -40℃-80℃ -40℃-80℃ -40℃-80℃
Operating state/fault indication green/red green/red green/red
Area della sezione trasversale (Min.) 4mm² 4mm² 4mm²
Area della sezione trasversale (max.) 35 mm² 35 mm² 35 mm²
Per il montaggio Guida DIN da 35 mm
Materiale della custodia Termoplastico UL94-V0
Grado di protezione IP20 IP20 IP20
Order Code B17158 B18147 B17184
Order Code (With remote signaling) B17159 B18148 B17185

Caratteristiche:

• Impact discharge current of per pole reaches 50kA(10/350).

• Fast response time less than <100ns.

• Max. backup Fuse: 315A gG.

• Status indicator.

• Fault signal contact.

• 35mm Din rail mountable.

• BR-50GR 4P is suitable for TN-S system.

• It has passed the class I lightning protection test conducted by national professional testing institutions.

• It is the first-level lightning protection product of ac power equipment.

Applicazione:

For electrical installations.

Suitable for lightning protection of power supply system in areas with high risk of lightning strike (LPZ0B or interface between LPZ0B and LPZ1).

Can handle lightning currents and protect sensitive electronic equipment.

Application-optimized and prewired combined lightning current.

Particularly useful in a high lightning density area where the risk of heavy surge current or even direct strike is high (e.g.: buildings equipped with lightning rods).

Installazione:

During installation, please connect according to the installation schematic diagram.

Power must be cut off during installation, live operation is strictly prohibited, and connecting wires must meet the requirements.

 

SIAMO QUI PER SUPPORTARTI!

Ulteriori informazioni o una consulenza personale? I nostri prodotti e il nostro know-how sono lì per fornire soluzioni.

PRODOTTI CORRELATI
NOTIZIE CORRELATE
POTRESTI ANCHE VEDERE
OTTIENI LA ​​PROTEZIONE DA SOVRATENSIONE
LA SOLUZIONE OGGI!
icona
icona
Seraphinite AcceleratorOptimized by Seraphinite Accelerator
Turns on site high speed to be attractive for people and search engines.