Caratteristiche del prodotto:
| Specifica | BR-50GR 150 3+1 | BR-50GR 275 3+1 | BR-50GR 350 3+1 | |
| SPD classification according to EN61643-11 | Type 1 + Type 2 | Type 1 + Type 2 | Type 1 + Type 2 | |
| SPD classification according to IEC61643-11 | Class I + Class II | Class I + Class II | Class I + Class II | |
| Nominal operating voltage | Un | 120V/240V(50/60Hz) | 230V/400V(50/60Hz) | 250V/440V(50/60Hz) |
| Max. continuous operating a.c. voltage | Uc (L-N/N-PE) | 150V/255V(50/60Hz) | 275V/255V(50/60Hz) | 350V/255V(50/60Hz) |
| Corrente impulsiva di fulmine (10/350μs) | Iimp (L-N/N-PE) | 50kA/100kA | 50kA/100kA | 50kA/100kA |
| Corrente di scarica nominale (8/20μs) | In (L-N/N-PE) | 50kA/100kA | 50kA/100kA | 50kA/100kA |
| Massimo. corrente di scarica (8/20μs) | Imax (L-N/N-PE) | 160kA/200kA | 160kA/200kA | 160kA/200kA |
| Quantity of electric charge (L-N, N-PE) | Q | 25As, 50As | 25As, 50As | 25As, 50As |
| Specific energy (L-N, N-PE) | W/R | 625kJ/Ω, 2500kJ/Ω | 625kJ/Ω, 2500kJ/Ω | 625kJ/Ω, 2500kJ/Ω |
| Livello di protezione della tensione | Up (L-N/N-PE) | ≤1.5kV/≤1.5kV | ≤1.5kV/≤1.5kV | ≤1.5kV/≤1.5kV |
| Short-circuit current rating a.c. | Isccr (L-N/N-PE) | 25kA rms/100A rms | 25kA rms/100A rms | 25kA rms/100A rms |
| Max. backup fuse | 350A gG | 350A gG | 350A gG | |
| Temporary overvoltage TOV-withstand | UT (L-N) | 230V/120min. | 440V/120min. | 580V/120min. |
| Temporary overvoltage TOV-withstand | UT (N-PE) | 1200V/200ms | 1200V/200ms | 1200V/200ms |
| Tempo di risposta | tA | ≤100ns | ≤100ns | ≤100ns |
| Intervallo di temperatura operativa | Tu | -40℃-80℃ | -40℃-80℃ | -40℃-80℃ |
| Operating state/fault indication | green/red | green/red | green/red | |
| Area della sezione trasversale (Min.) | 4mm² | 4mm² | 4mm² | |
| Area della sezione trasversale (max.) | 35 mm² | 35 mm² | 35 mm² | |
| Per il montaggio | Guida DIN da 35 mm | |||
| Materiale della custodia | Termoplastico UL94-V0 | |||
| Grado di protezione | IP20 | IP20 | IP20 | |
| Order Code | B17166 | B18167 | B17192 | |
| Order Code (With remote signaling) | B17167 | B18168 | B17193 | |
Caratteristiche:
Endurable, sustains multiple strikes.
LED status indication.
Protection class: Type 1+2, Class I +Class II.
BR-50GR 3P+N is suitable for TT and TN-S system.
Applicazione:
● Suitable for TT and TN-S system.
● Used in industrial systems and buildings with external lightning protection of Classes I to IV.
● For the protection of low voltage distribution systems against direct lightning strike into the overhead power supply line or external lightning protection system.
● Can be used in standard distributor housing.
● Used to protect all kinds of electrical equipment in the power system from lightning over-voltage, operation over-voltage, power frequency transient over-voltage impact damage to an electrical appliance.
Ulteriori informazioni o una consulenza personale? I nostri prodotti e il nostro know-how sono lì per fornire soluzioni.