BR-50GR 1+1 Type 1 50kA Surge Arrester for TT and TNS

Ottieni un preventivo
Descrizione

Caratteristiche del prodotto:

Specifica BR-50GR 150 1+1 BR-50GR 275 1+1 BR-50GR 350 1+1
SPD classification according to EN61643-11 Type 1 + Type 2 Type 1 + Type 2 Type 1 + Type 2
SPD classification according to IEC61643-11 Class I + Class II Class I + Class II Class I + Class II
Nominal operating voltage Un 120V(50/60Hz) 230V(50/60Hz) 250V(50/60Hz)
Max. continuous operating a.c. voltage Uc (L-N/N-PE) 150V/255V(50/60Hz) 275V/255V(50/60Hz) 350V/255V(50/60Hz)
Corrente impulsiva di fulmine (10/350μs) Iimp (L-N/N-PE) 50kA/100kA 50kA/100kA 50kA/100kA
Corrente di scarica nominale (8/20μs) In (L-N/N-PE) 50kA/100kA 50kA/100kA 50kA/100kA
Massimo. corrente di scarica (8/20μs) Imax (L-N/N-PE) 160kA/200kA 160kA/200kA 160kA/200kA
Quantity of electric charge (L-N, N-PE) Q 25As, 50As 25As, 50As 25As, 50As
Specific energy (L-N, N-PE) W/R 625kJ/Ω, 2500kJ/Ω 625kJ/Ω, 2500kJ/Ω 625kJ/Ω, 2500kJ/Ω
Livello di protezione della tensione Up (L-N/N-PE) ≤1.5kV/≤1.5kV ≤1.5kV/≤1.5kV ≤1.5kV/≤1.5kV
Short-circuit current rating a.c. Isccr (L-N/N-PE) 25kA rms/100A rms 25kA rms/100A rms 25kA rms/100A rms
Max. backup fuse 350A gG 350A gG 350A gG
Temporary overvoltage TOV-withstand UT (L-N) 230V/120min. 440V/120min. 580V/120min.
Temporary overvoltage TOV-withstand UT (N-PE) 1200V/200ms 1200V/200ms 1200V/200ms
Tempo di risposta tA ≤100ns ≤100ns ≤100ns
Intervallo di temperatura operativa Tu -40℃-80℃ -40℃-80℃ -40℃-80℃
Operating state/fault indication green/red green/red green/red
Area della sezione trasversale (Min.) 4mm² 4mm² 4mm²
Area della sezione trasversale (max.) 35 mm² 35 mm² 35 mm²
Per il montaggio Guida DIN da 35 mm
Materiale della custodia Termoplastico UL94-V0
Grado di protezione IP20 IP20 IP20
Order Code B17168 B18157 B17194
Order Code (With remote signaling) B17169 B18158 B17195

Caratteristiche:

Endurable, sustains multiple strikes.

LED status indication.

BR-50GR 1P+N is suitable for TT and TN-S system.

SPD indoor fixedly mounted, limiting voltage.

SPD has built-in disconnector, when SPD is invalid due to overheating or breakdown, the disconnector can automatically separate SPD from the network, meanwhile send an indication signal. If to be separated from network, the visible window will show red color.

Applicazione:

Being total current arresters between the neutral and protective conductor in TT systems, the single-pole N-PE lightning current arresters of type BR-50GR NPE help to ensure fulfilling the requirements for protection of personnel and equipment in “1+1” circuits.

The BR-50GR NPE coordinated NPE lightning current arresters hold a special position among total current arresters. Due to their low voltage protection level, they can be directly coordinated with N-PE surge arresters of the BR-50GR surge arresters without additional decoupling coil.

BR-50GR NPE devices are suitable for connecting conductors and busbars, allowing comfortable wiring with other DIN rail mounted terminals.

Widely used in mobile communication base stations, microwave communication bureaus/stations, telecommunication rooms, industrial mining, civil aviation, financial securities and other power systems.

Installation and note:

Usually installed in the low-voltage main distribution cabinet of the building incoming line.

Lightning protection grounding should meet the lightning protection specifications; the grounding wire should be as short as possible.

 

SIAMO QUI PER SUPPORTARTI!

Ulteriori informazioni o una consulenza personale? I nostri prodotti e il nostro know-how sono lì per fornire soluzioni.

PRODOTTI CORRELATI
NOTIZIE CORRELATE
POTRESTI ANCHE VEDERE
OTTIENI LA ​​PROTEZIONE DA SOVRATENSIONE
LA SOLUZIONE OGGI!
icona
icona
Seraphinite AcceleratorOptimized by Seraphinite Accelerator
Turns on site high speed to be attractive for people and search engines.