Caratteristiche del prodotto:
| Specifica | BR275-40DP 4P | BR320-40DP 4P | |||
| SPD classification according to EN61643-11 | Type 2 + Type 3 | Type 2 + Type 3 | |||
| SPD classification according to IEC61643-11 | Class II + Class III | Class II + Class III | |||
| Max. continuous operating a.c. voltage | Uc | 275V | 320V | ||
| Corrente di scarica nominale (8/20μs) | In | 20kA | 20kA | ||
| Massimo. corrente di scarica (8/20μs) | Imax | 40kA | 40kA | ||
| Combined impulse | Uoc | 10kV | 10kV | ||
| Livello di protezione della tensione | Su | ≤1.3kV | ≤1.5kV | ||
| Tempo di risposta | tA | ≤25ns | ≤25ns | ||
| Intervallo di temperatura operativa | Tu | -40℃-80℃ | -40℃-80℃ | ||
| Indicazione dello stato operativo/guasto | verde/rosso | verde/rosso | |||
| Area della sezione trasversale (Min.) | 2.5mm² | 2.5mm² | |||
| Area della sezione trasversale (max.) | 16mm² | 16mm² | |||
| Per il montaggio | Guida DIN da 35 mm | Guida DIN da 35 mm | |||
| Materiale della custodia | Termoplastico UL94-V0 | ||||
| Grado di protezione | IP20 | IP20 | |||
| Codice ordine | B18220 | B17250 | |||
| Codice d'ordine (con segnale remoto) | B18221 | B17251 | |||
Caratteristiche:
Type 2 + Type 3 Surge Protector.
Discharge currents : In : 20 kA / Imax : 40 kA.
DIN rail compatible.
Remote Signalling in option.
IEC 61643-11 and EN 61643-11 compliance.
Visible fault indication:Green on: Normal; Green off: Fault.
BR-40DP series is combined Type 2+3 / Class II+III devices for discharging voltage surges while providing a very fine voltage protection level.
Applicazione:
For protection of power supply systems.
For the protection of low voltage distribution systems against transient overvoltage caused by indirect lightning stroke and switching operations.
For using in the lightning protection zones concept at boundary 2-3.
Applied to power supply protection of equipment system in areas with high lightning risk.
Installazione:
Suitable as the final stage of protection in panels with Type 2 protection devices installed upstream.
These SPDs should be installed as close as possible to the equipment being protected.
Installed at a minimum conductor length of 10 meters (30 feet) from the electrical service panel to the point of utilization, for example cord connected, direct plug-in, receptacle type SPDs installed at the utilization equipment being protected. The distance (10 meters) is exclusive of the conductors provided with or used to attach SPDs.
Ulteriori informazioni o una consulenza personale? I nostri prodotti e il nostro know-how sono lì per fornire soluzioni.