BR-40 4P Type 2 40kA 690V 800V 1000V AC Surge Protector

Ottieni un preventivo
Descrizione

Caratteristiche del prodotto:

Specifica BR-40 690 4P BR-40 800 4P
BR-40 1000 4P
SPD classification according to EN61643-11 Tipo 2 Tipo 2 Tipo 2
SPD classification according to IEC61643-11 Class II Class II Class II
Max. continuous operating a.c. voltage Uc 690V 800V 1000V
Corrente di scarica nominale (8/20μs) In 20kA 20kA 20kA
Massimo. corrente di scarica (8/20μs) Imax 40kA 40kA 40kA
Livello di protezione della tensione Su ≤3.2kV ≤3.6kV ≤4.0kV
Voltage protection level 5kA Su ≤2.3kV ≤2.8kV ≤3.3kV
Max. backup fuse 100A gG 100A gG 100A gG
Short-circuit withstand capacity Isccr 25kA 25kA 25kA
Temporary overvoltage TOV-withstand UT 800V/5sec. 1000V/5sec. 1100V/5sec.
Temporary overvoltage TOV-safe failure UT 1000V/120min. 1200V/120min. 1400V/120min.
Tempo di risposta tA ≤25ns ≤25ns ≤25ns
Intervallo di temperatura operativa Tu -40℃-80℃ -40℃-80℃ -40℃-80℃
Operating state/fault indication green/red green/red green/red
Area della sezione trasversale (Min.) 4mm² 4mm² 4mm²
Area della sezione trasversale (max.) 35 mm² 35 mm² 35 mm²
Per il montaggio Guida DIN da 35 mm
Materiale della custodia Thermoplastic   UL94-V0
Grado di protezione IP20 IP20 IP20
Order Code B18036 B7957 B18052
Order Code (With remote signaling) B18037 B7958 B18053

Caratteristiche:

BRITEC BR-40 4P AC Protective Arrester SPD is suitably used in the TN-S power supply system of AC.

In: 20kA.

Suitable for system power protection, such as power distribution cabinet, switch cabinet, switch cabinet, AC distribution board, etc.

Protect from indirect lightning impulse and other transient over voltage.

Protection class: Type 2 , Class II.

Low residual voltage and quick response

The reaction time of less than 25 ns.

Uc 690V/800V/1000V

Color of visible window shows operating status, normal green, red fault.

With remote signaling contact for control device.

Patented fast tripping mechanism.

Standard: IEC/EN 6163-11

Consisting of a base part and plug-in protection modules.

Applicazione:

Designed for installations where direct lightning strike risk is reduced (without LPS or medium risk).

 

SIAMO QUI PER SUPPORTARTI!

Ulteriori informazioni o una consulenza personale? I nostri prodotti e il nostro know-how sono lì per fornire soluzioni.

PRODOTTI CORRELATI
NOTIZIE CORRELATE
POTRESTI ANCHE VEDERE
OTTIENI LA ​​PROTEZIONE DA SOVRATENSIONE
LA SOLUZIONE OGGI!
icona
icona
Seraphinite AcceleratorOptimized by Seraphinite Accelerator
Turns on site high speed to be attractive for people and search engines.