BR-20 1P Type 2 20kA Surge Protective Device

Ottieni un preventivo
Descrizione

Caratteristiche del prodotto:

Specifica BR-20 150 1P BR-20 275 1P BR-20 320 1P BR-20 385 1P BR-20 440 1P
SPD classification according to EN61643-11 Tipo 2 Tipo 2 Tipo 2 Tipo 2 Tipo 2
SPD classification according to IEC61643-11 Class II Class II Class II Class II Class II
Max. continuous operating a.c. voltage Uc 150V 275V 320V 385V 440V
Corrente di scarica nominale (8/20μs) In 10kA 10kA 10kA 10kA 10kA
Massimo. corrente di scarica (8/20μs) Imax 20kA 20kA 20kA 20kA 20kA
Livello di protezione della tensione Su ≤0.8kV ≤1.3kV ≤1.5kV ≤1.8kV ≤2.0kV
Voltage protection level 5kA Su ≤0.6kV ≤1kV ≤1.2kV ≤1.3kV ≤1.5kV
Max. backup fuse 63A gG 63A gG 63A gG 63A gG 63A gG
Short-circuit withstand capacity Isccr 25kA 25kA 25kA 25kA 25kA
Temporary overvoltage TOV-withstand UT 180V/5sec. 335V/5sec. 400V/5sec. 500V/5sec. 580V/5sec.
Temporary overvoltage TOV-safe failure UT 230V/120min. 440V/120min. 520V/120min. 650V/120min. 765V/120min.
Tempo di risposta tA ≤25ns ≤25ns ≤25ns ≤25ns ≤25ns
Intervallo di temperatura operativa Tu -40℃-80℃ -40℃-80℃ -40℃-80℃ -40℃-80℃ -40℃-80℃
Operating state/fault indication green/red green/red green/red green/red green/red
Area della sezione trasversale (Min.) 4mm² 4mm² 4mm² 4mm² 4mm²
Area della sezione trasversale (max.) 35 mm² 35 mm² 35 mm² 35 mm² 35 mm²
Per il montaggio Guida DIN da 35 mm
Materiale della custodia Thermoplastic   UL94-V0
Grado di protezione IP20 IP20 IP20 IP20 IP20
Order Code B18731 B18733 B18735 B18737 B18739
Order Code (With remote signaling) B18732 B18734 B18736 B18738 B18740

Caratteristiche:

• Low price surge protection device (SPD), Type 2 or Class II test level, selectable in nominal discharge current 10kA with max. discharge current of 20kA accordingly.

• Surge Protection Device for transient electrical over-voltages.

• DIN rail mounting, easy installation, compact size, and good performance.

• Class 2 SPD for typical waveforms of 8/20 μs.

• Best surge protector for your power supply system with rated voltage of 400V AC 50Hz/60Hz.

• The SPD is designed in accordance with IEC Class II.

Applicazione:

• They ensure protection against overvoltage conditions.

• For the protection of low voltage distribution systems against direct lightning strike into the overhead power supply line or external lightning protection system (IEC 62305).

• They are suitable for installation in secondary boards and in terminal equipment.

Installazione:

• The line of surge arresters includes a full range of compact protectors for installation on DIN rail

• When the fault indication window turns from green to red please replace the cartridge as soon as possible

• After the installation is complete, check that the protection unit is plug in place, close the automatic circuit breaker (fuse) switch, check the working status is normal.

 

SIAMO QUI PER SUPPORTARTI!

Ulteriori informazioni o una consulenza personale? I nostri prodotti e il nostro know-how sono lì per fornire soluzioni.

PRODOTTI CORRELATI
NOTIZIE CORRELATE
POTRESTI ANCHE VEDERE
OTTIENI LA ​​PROTEZIONE DA SOVRATENSIONE
LA SOLUZIONE OGGI!
icona
icona
Seraphinite AcceleratorOptimized by Seraphinite Accelerator
Turns on site high speed to be attractive for people and search engines.