BR-12.5M 3P 12.5kA Type 1+2 Surge Protective Device For TN-C

Ottieni un preventivo
Descrizione

Caratteristiche del prodotto:

Specifica BR-12.5M 150 3P BR-12.5M 275 3P BR-12.5M 320 3P
SPD classification according to EN61643-11 Type 1 + Type 2 Type 1 + Type 2 Type 1 + Type 2
SPD classification according to IEC61643-11 Class I + Class II Class I + Class II Class I + Class II
Max. continuous operating a.c. voltage Uc 150V(50/60Hz) 275V(50/60Hz) 320V(50/60Hz)
Corrente impulsiva di fulmine (10/350μs) Iimp 12.5kA 12.5kA 12.5kA
Corrente di scarica nominale (8/20μs) In 25kA 25kA 25kA
Massimo. corrente di scarica (8/20μs) Imax 60kA 60kA 60kA
Specific energy W/R 39kJ/Ω 39kJ/Ω 39kJ/Ω
Livello di protezione della tensione Su ≤0.8kV ≤1.3kV ≤1.5kV
Short-circuit current rating a.c. Isccr 25kA rms 25kA rms 25kA rms
Max. backup fuse 125A gG 125A gG 125A gG
Temporary overvoltage TOV-withstand UT(L-N) 180V/5sec. 335V/5sec. 400V/5sec.
Temporary overvoltage TOV-safe failure UT(L-N) 230V/120min. 440V/120min. 520V/120min.
Tempo di risposta tA ≤25ns ≤25ns ≤25ns
Intervallo di temperatura operativa Tu -40℃-80℃ -40℃-80℃ -40℃-80℃
Operating state/fault indication green/red green/red green/red
Area della sezione trasversale (Min.) 4mm² 4mm² 4mm²
Area della sezione trasversale (max.) 35 mm² 35 mm² 35 mm²
Per il montaggio Guida DIN da 35 mm
Materiale della custodia Termoplastico UL94-V0
Grado di protezione IP20 IP20 IP20
Order Code B18311 B18313 B18315
Order Code (With remote signaling) B18312 B18314 B18316

Caratteristiche:

Britec hold patent for the design.

It adopts 35mm standard rail.

Time of response 25ns.

The plug-in module / base design facilitate replacement of a failed module without the need to remove system wiring etc.

There is a failure release mounted on the module of surge protective device.

It consists of a high performance varistor with thermal disconnection tripping device.

When the SPD fails in breakdown for over-heat and over-current, the failure release will help electric device separate from the power system and give the indication signal, green means normal, red means abnormal.

Applicazione:

Used to guard sensitive equipment from voltage spike.

It is applied to low-voltage distribution system, which is connected in parallel between power supply and system equipment to protect the damage caused by instantaneous overvoltage caused by external (lightning

strike, electromagnetic radiation interference, etc.) or internal (system closing effect, induction and start and stop of capacitive load, etc.).

Installazione:

Installed in low-voltage distributions at the boundary of LPZ 0–LPZ 1 zones and higher to prevent overvoltage effects induced during a lightning strike and to prevent switching overvoltage.

Install in the main distribution cabinet/box of the low-voltage cabinet and the incoming line cabinet.

Recommended for main distribution boards.

During installation, please connect according to the installation schematic diagram, where L1, L2 and L3 are phase lines, N is the zero line and PE is the ground line.

Grounding should conform to the requirements of the specification of lightning protection.

 

SIAMO QUI PER SUPPORTARTI!

Ulteriori informazioni o una consulenza personale? I nostri prodotti e il nostro know-how sono lì per fornire soluzioni.

PRODOTTI CORRELATI
NOTIZIE CORRELATE
POTRESTI ANCHE VEDERE
OTTIENI LA ​​PROTEZIONE DA SOVRATENSIONE
LA SOLUZIONE OGGI!
icona
icona
Seraphinite AcceleratorOptimized by Seraphinite Accelerator
Turns on site high speed to be attractive for people and search engines.