Specification | BR-40 150 1+1 | BR-40 275 1+1 | BR-40 320 1+1 | BR-40 385 1+1 | BR-40 440 1+1 | |
SPD classification according to EN61643-11 | Type 2 | Type 2 | Type 2 | Type 2 | Type 2 | |
SPD classification according to IEC61643-11 | Class II | Class II | Class II | Class II | Class II | |
Max. continuous operating a.c. voltage(L-N) | Uc | 150V | 275V | 320V | 385V | 440V |
Max. continuous operating a.c. voltage(N-PE) | Uc | 255V | 255V | 255V | 255V | 255V |
Nominal discharge current (8/20μs) | In | 20kA | 20kA | 20kA | 20kA | 20kA |
Max. discharge current (8/20μs) | Imax | 40kA | 40kA | 40kA | 40kA | 40kA |
Voltage protection level (L-N) | Up | ≤0.8kV | ≤1.3kV | ≤1.5kV | ≤1.8kV | ≤2.0kV |
Voltage protection level 5kA (L-N) | Up | ≤0.6kV | ≤1kV | ≤1.2kV | ≤1.4kV | ≤1.6kV |
Voltage protection level (N-PE) | Up | ≤1.5kV | ≤1.5kV | ≤1.5kV | ≤1.5kV | ≤1.5kV |
Max. backup fuse | 125A gG | 125A gG | 125A gG | 125A gG | 125A gG | |
Short-circuit withstand capacity | Isccr | 25kA | 25kA | 25kA | 25kA | 25kA |
Temporary overvoltage TOV-withstand (L-N) | UT | 175V/5sec. | 335V/5sec. | 350V/5sec. | 550V/5sec. | 580V/5sec. |
Temporary overvoltage TOV-safe failure(L-N) | UT | 250V/120min. | 440V/120min. | 550V/120min. | 660V/120min. | 770V/120min. |
Temporary overvoltage TOV-withstand(N-PE) | UT | 1200V/200ms | 1200V/200ms | 1200V/200ms | 1200V/200ms | 1200V/200ms |
Response time (L-N) | tA | ≤25ns | ≤25ns | ≤25ns | ≤25ns | ≤25ns |
Response time (N-PE) | tA | ≤100ns | ≤100ns | ≤100ns | ≤100ns | ≤100ns |
Operating temperature range | Tu | -40℃-80℃ | -40℃-80℃ | -40℃-80℃ | -40℃-80℃ | -40℃-80℃ |
Operating state/fault indication | green/red | green/red | green/red | green/red | green/red | |
Cross-section area (Min.) | 4mm² | 4mm² | 4mm² | 4mm² | 4mm² | |
Cross-section area (Max.) | 35mm² | 35mm² | 35mm² | 35mm² | 35mm² | |
For mounting on | 35mm Din rail | |||||
Enclosure material | Thermoplastic UL94-V0 | |||||
Degree of protection | IP20 | IP20 | IP20 | IP20 | IP20 | |
Order Code | B18251 | B18253 | B18255 | B18257 | B18370 | |
Order Code (With remote signaling) | B18252 | B18254 | B18256 | B18258 | B18371 |
Features:
Lightning surge protector with compact construction design
35mm2 DIN-rail in accordance with EN 50022/DIN46277-3
Application systems: TT, IT, and TN power supply system.
Protection mode: L-N, N-PE.
40kA Type 2 Class C AC Surge Protection Device.
Our offered surge protector is designed by utilizing the top grade material and the most advanced techniques.
Reliable control thanks to Thermo Dynamic Control disconnector.
Application:
For protection of consumer equipment against transient voltage caused by indirect lightning strike and switching operations.
Use in domestic, commercial and light industrial installations.
Usually installed in household power distribution boards, telecom machinery center, computer equipment center, elevator control center, hospital’s surgery and ICU, information equipment, electronic equipment and in front of control equipment or nearest socket box of control equipment.
Installation:
Usually installed in the distribution box office, the power phase line (L), neutral (N), respectively, corresponding surge protectors access terminals to ensure secure and reliable, and the surge protector ground terminal and ground as well electrical connection.
It should regularly check the work, such as the window turns red indicating the deterioration of its front open space, when the fuse is tripped, timely maintenance or replacement module.