BR-80 3P Type 2 80kA Surge Protective Device For TN-C

Dapatkan Penawaran
Keterangan

Karakteristik produk:

Spesifikasi BR-80 150 3P BR-80 275 3P BR-80 320 3P BR-80 385 3P
Klasifikasi SPD menurut EN61643-11 Tipe 2 Tipe 2 Tipe 2 Tipe 2
Klasifikasi SPD menurut IEC61643-11 Class II Class II Class II Class II
Maks. operasi terus menerus a.c. voltase Uc 150V 275V 320V 385V
Arus pelepasan nominal (8/20μs) Di dalam 40kA 40kA 40kA 40kA
Maks. arus pelepasan (8/20μs) maksimal 80kA 80kA 80kA 80kA
Tingkat perlindungan tegangan Ke atas ≤1.0kV ≤1.7kV ≤2.0kV ≤2.3kV
Voltage protection level 5kA Ke atas ≤0.6kV ≤1.0kV ≤1.1kV ≤1.2kV
Maks. sekering cadangan 160A gG 160A gG 160A gG 160A gG
Short-circuit withstand capacity Isccr 25kA 25kA 25kA 25kA
Tahan TOV tegangan lebih sementara UT 180V/5sec. 335V/5sec. 400V/5sec. 500V/5sec.
Temporary overvoltage TOV-safe failure UT 230V/120 menit. 440V/120 menit. 520V/120min. 650V/120min.
Waktu respons ta ≤25ns ≤25ns ≤25ns ≤25ns
Kisaran suhu pengoperasian kamu -40℃-80℃ -40℃-80℃ -40℃-80℃ -40℃-80℃
Status pengoperasian/indikasi kesalahan hijau/merah hijau/merah hijau/merah hijau/merah
Luas penampang (Min.) 4mm² 4mm² 4mm² 4mm²
Luas penampang (Maks.) 35mm² 35mm² 35mm² 35mm²
Untuk pemasangan Rel Din 35mm
Bahan penutup Thermoplastic   UL94-V0
Tingkat perlindungan IP20 IP20 IP20 IP20
Kode Pesanan B18268 B18270 B18272 B18274
Kode Pesanan (Dengan sinyal jarak jauh) B18269 B18271 B18273 B18275

Fitur:

Visual status display

Labeled connections

Type 2 (class II/C) for main boards, distribution boards and consumer units.

Available with and without remote signalling contacts.

1 pole up to 4 poles protected.

BR-80 consists of a high performance varistor block with thermal disconnection device. The plug-in module/base design facilitates replacement of a failed module in situ without the need to remove system wiring.

Solutions to meet IEC 61643-1 and EN 61643-11

Aplikasi:

Distribution switch board located downstream from a Type 1 Lightning Current Arrester.

Protecting them from direct and indirect lightning impulse and other transient overvoltage.

Protects low-voltage systems against overvoltage triggered by lightning strikes or grid switching operations.

Ideal for industrial applications.

At the origin of the electrical installation in the main switchboard, in areas where electromagnetic fields caused by lightning currents are dominant (excluding a direct strike).

Suitable for TN-C systems.

Preventing the spread of medium overvoltage (Up) in the electrical installation and protecting equipment that is connected to it.

 

KAMI DI SINI UNTUK MENDUKUNG ANDA!

Informasi lebih lanjut atau konsultasi pribadi? Produk dan pengetahuan kami hadir untuk memberikan solusi.