Karakteristik produk:
| Spesifikasi | BR-60 150 2P | BR-60 275 2P | BR-60 320 2P | BR-60 385 2P | ||
| Klasifikasi SPD menurut EN61643-11 | Tipe 2 | Tipe 2 | Tipe 2 | Tipe 2 | ||
| Klasifikasi SPD menurut IEC61643-11 | Class II | Class II | Class II | Class II | ||
| Maks. operasi terus menerus a.c. voltase | Uc | 150V | 275V | 320V | 385V | |
| Arus pelepasan nominal (8/20μs) | Di dalam | 30kA | 30kA | 30kA | 30kA | |
| Maks. arus pelepasan (8/20μs) | maksimal | 60kA | 60kA | 60kA | 60kA | |
| Tingkat perlindungan tegangan | Ke atas | ≤1.0kV | ≤1.6kV | ≤1.8kV | ≤2.2kV | |
| Voltage protection level 5kA | Ke atas | ≤0.5kV | ≤0.6kV | ≤1.0kV | ≤1.2kV | |
| Maks. sekering cadangan | 160A gG | 160A gG | 160A gG | 160A gG | ||
| Short-circuit withstand capacity | Isccr | 25kA | 25kA | 25kA | 25kA | |
| Tahan TOV tegangan lebih sementara | UT | 180V/5sec. | 335V/5sec. | 400V/5sec. | 500V/5sec. | |
| Temporary overvoltage TOV-safe failure | UT | 230V/120 menit. | 440V/120 menit. | 520V/120min. | 650V/120min. | |
| Waktu respons | ta | ≤25ns | ≤25ns | ≤25ns | ≤25ns | |
| Kisaran suhu pengoperasian | kamu | -40℃-80℃ | -40℃-80℃ | -40℃-80℃ | -40℃-80℃ | |
| Status pengoperasian/indikasi kesalahan | hijau/merah | hijau/merah | hijau/merah | hijau/merah | ||
| Luas penampang (Min.) | 4mm² | 4mm² | 4mm² | 4mm² | ||
| Luas penampang (Maks.) | 35mm² | 35mm² | 35mm² | 35mm² | ||
| Untuk pemasangan | Rel Din 35mm | |||||
| Bahan penutup | Thermoplastic UL94-V0 | |||||
| Tingkat perlindungan | IP20 | IP20 | IP20 | IP20 | ||
| Kode Pesanan | B18781 | B18783 | B18785 | B18787 | ||
| Kode Pesanan (Dengan sinyal jarak jauh) | B18782 | B18784 | B18786 | B18788 | ||
Fitur:
High Surge Energy capacity protects downstream loads from voltage spikes and line transients.
Connected in parallel and use an MOV to clamp high-voltage surges.
Thermal protection circuit disconnects load under high energy absorption events.
This device is primarily used in the main electrical panel for the protection of 1-phase systems.
Fail safe/self-protection design.
Visual red-green indicator alerts when surge module needs replacement.
Certified: IEC61643-11:2013, Class II.
Remote alarm contact.
Touch Safe, IP20 Degree of Protection
Surge module plugs into DIN Rail mount base assembly for easy replacement in field.
Double thermal disconnection device, provide more reliable protection.
Two pole device provides full protection.
High discharge current — Imax 60kA per pole.
Narrow size, special design for saving installation space — width 18mm/pole, single phase.
Aplikasi:
Useful in case of high lightning density areas.
This surge arrestor is suitable for all installations where risk of surge and spike activity and, particularly due to nearby lightning activity, as in telecom installations, oil rigs, and open exposed areas with metal structures.
This unit should be installed in all building and sites at high risk (where a Lightning Protection System is in place and there is risk to human life such as schools, hospitals etc.).
Informasi lebih lanjut atau konsultasi pribadi? Produk dan pengetahuan kami hadir untuk memberikan solusi.