BR-40VG 4P Type 2 40kA Surge Protection

Dapatkan Penawaran
Keterangan

Karakteristik produk:

Spesifikasi BR-40VG 150 4P BR-40VG 275 4P BR-40VG 320 4P BR-40VG 385 4P BR-40VG 440 4P
Klasifikasi SPD menurut EN61643-11 Tipe 2 Tipe 2 Tipe 2 Tipe 2 Tipe 2
Klasifikasi SPD menurut IEC61643-11 Class II Class II Class II Class II Class II
Maks. operasi terus menerus a.c. voltase Uc 150V 275V 320V 385V 440V
Arus pelepasan nominal (8/20μs) Di dalam 20kA 20kA 20kA 20kA 20kA
Maks. arus pelepasan (8/20μs) maksimal 40kA 40kA 40kA 40kA 40kA
Tingkat perlindungan tegangan Ke atas ≤1.3kV ≤1.3kV ≤1.5kV ≤1.8kV ≤2.0kV
Maks. sekering cadangan 100A gG 100A gG 100A gG 100A gG 100A gG
Short-circuit withstand capacity Isccr 25kA 25kA 25kA 25kA 25kA
Tahan TOV tegangan lebih sementara UT 180V/5sec. 335V/5sec. 400V/5sec. 500V/5sec. 580V/5sec.
Temporary overvoltage TOV-safe failure UT 230V/120 menit. 440V/120 menit. 520V/120min. 650V/120min. 765V/120min.
Waktu respons ta ≤100ns ≤100ns ≤100ns ≤100ns ≤100ns
Kisaran suhu pengoperasian kamu -40℃-80℃ -40℃-80℃ -40℃-80℃ -40℃-80℃ -40℃-80℃
Status pengoperasian/indikasi kesalahan hijau/merah hijau/merah hijau/merah hijau/merah hijau/merah
Luas penampang (Min.) 4mm² 4mm² 4mm² 4mm² 4mm²
Luas penampang (Maks.) 35mm² 35mm² 35mm² 35mm² 35mm²
Untuk pemasangan Rel Din 35mm
Bahan penutup Thermoplastic   UL94-V0
Tingkat perlindungan IP20 IP20 IP20 IP20 IP20
Kode Pesanan B17506 B17518 B17530 B17542 B17554
Kode Pesanan (Dengan sinyal jarak jauh) B17507 B17519 B17531 B17543 B17555

Fitur:

Electric ratings: 230/400V, AC50/60Hz, 3-phase;

In: 20kA.

Surge protective device, plug.

Uc 150V / 275V / 320V / 385V / 440V can be achieved.

Standard: IEC/EN 61643-11

Hot melt flow double protection.

The visual window color said protector working state; green (normal), red (fault).

The reaction time of less than 100 ns.

Number of poles: 4;

Short circuit current: up to 40kA (8/20μs);

Remote signaling can select.

It is designed as module and 35mm din rail mounting.

Consisting of a base part and plug-in protection modules.

Aplikasi:

Protect electric system and on-loading electrical apparatus from thunder and instantaneous over-voltage.

In order to shunt and pressure to limit indirect lightning current or other instantaneous overvoltage.

 

KAMI DI SINI UNTUK MENDUKUNG ANDA!

Informasi lebih lanjut atau konsultasi pribadi? Produk dan pengetahuan kami hadir untuk memberikan solusi.