Karakteristik produk:

Spesifikasi BR275-40DP 3+1 BR320-40DP 3+1
Klasifikasi SPD menurut EN61643-11 Type 2 + Type 3 Type 2 + Type 3
Klasifikasi SPD menurut IEC61643-11 Class II + Class III Class II + Class III
Maks. operasi terus menerus a.c. voltase Uc(L-N/N-PE) 275V/255V 320V/255V
Arus pelepasan nominal (8/20μs) Di dalam 20kA 20kA
Maks. arus pelepasan (8/20μs) maksimal 40kA 40kA
Combined impulse Uoc 10kV 10kV
Tingkat perlindungan tegangan Up(L-N/N-PE) ≤1.3kV/≤1.5kV ≤1.5kV/≤1.5kV
Waktu respons ta ≤25ns ≤25ns
Kisaran suhu pengoperasian kamu -40℃-80℃ -40℃-80℃
Operating state / fault indication green / red green / red
Luas penampang (Min.) 2.5mm² 2.5mm²
Luas penampang (Maks.) 16mm² 16mm²
Untuk pemasangan Rel Din 35mm Rel Din 35mm
Bahan penutup Termoplastik UL94-V0
Tingkat perlindungan IP20 IP20
Order code B18243 B17254
Order code (with remote signal) B18244 B17255

Fitur:

Type 2 + Type 3 Surge Protector.

Uc 275V/320V.

This three phase SPD din-rail for lightning protection and other spikes in electrical power has a maximum amperage of 40 kA.

Response time: ≤25ns.

Pole number: 2P, 4P, 1P+N, 3P+N.

UL 94 V-0 Thermoplastic Housing.

DIN rail compatible.

Remote Signaling in option.

Degree of protection: IP20.

Conforming fully to international IEC 61643-11 and EN 61643-11 standards.

It can provide type 3 protection for equipment which installed within 5 meters from these devices.

Aplikasi:

For protection of power supply systems.

For the protection of low voltage distribution systems against transient overvoltage caused by indirect lightning stroke and switching operations.

For using in the lightning protection zones concept at boundary 2-3.

Applied to power supply protection of equipment system in areas with high lightning risk.

Instalasi:

Suitable as the final stage of protection in panels with Type 2 protection devices installed upstream.

These SPDs should be installed as close as possible to the equipment being protected.

Installed at a minimum conductor length of 10 meters (30 feet) from the electrical service panel to the point of utilization, for example cord connected, direct plug-in, receptacle type SPDs installed at the utilization equipment being protected. The distance (10 meters) is exclusive of the conductors provided with or used to attach SPDs.

 

KAMI DI SINI UNTUK MENDUKUNG ANDA!

Informasi lebih lanjut atau konsultasi pribadi? Produk dan pengetahuan kami hadir untuk memberikan solusi.

PRODUK TERKAIT
BERITA TERKAIT
ANDA MUNGKIN JUGA INGIN MELIHAT
DAPATKAN PERLINDUNGAN Lonjakan
SOLUSI HARI INI!
ikon
ikon
Seraphinite AcceleratorOptimized by Seraphinite Accelerator
Turns on site high speed to be attractive for people and search engines.