Karakteristik produk:
| Spesifikasi | BR-30FU 150 4P | BR-30FU 275 4P | BR-30FU 320 4P | BR-30FU 385 4P | BR-30FU 440 4P | |
| Klasifikasi SPD menurut EN61643-11 | Tipe 2 | Tipe 2 | Tipe 2 | Tipe 2 | Tipe 2 | |
| Klasifikasi SPD menurut IEC61643-11 | Class II | Class II | Class II | Class II | Class II | |
| Maks. operasi terus menerus a.c. voltase | Uc | 150V | 275V | 320V | 385V | 440V |
| Arus pelepasan nominal (8/20μs) | Di dalam | 15kA | 15kA | 15kA | 15kA | 15kA |
| Maks. arus pelepasan (8/20μs) | maksimal | 30kA | 30kA | 30kA | 30kA | 30kA |
| Tingkat perlindungan tegangan | Ke atas | ≤0.8kV | ≤1.3kV | ≤1.5kV | ≤1.8kV | ≤2.0kV |
| Voltage protection level 5kA | Ke atas | ≤0.6kV | ≤1kV | ≤1.2kV | ≤1.3kV | ≤1.5kV |
| Short-circuit withstand capacity | Isccr | 25kA | 25kA | 25kA | 25kA | 25kA |
| Tahan TOV tegangan lebih sementara | UT | 180V/5sec. | 335V/5sec. | 400V/5sec. | 500V/5sec. | 580V/5sec. |
| Temporary overvoltage TOV-safe failure | UT | 230V/120 menit. | 440V/120 menit. | 520V/120min. | 650V/120min. | 765V/120min. |
| Waktu respons | ta | ≤25ns | ≤25ns | ≤25ns | ≤25ns | ≤25ns |
| Kisaran suhu pengoperasian | kamu | -40℃-80℃ | -40℃-80℃ | -40℃-80℃ | -40℃-80℃ | -40℃-80℃ |
| Status pengoperasian/indikasi kesalahan | hijau/merah | hijau/merah | hijau/merah | hijau/merah | hijau/merah | |
| Luas penampang (Min.) | 4mm² | 4mm² | 4mm² | 4mm² | 4mm² | |
| Luas penampang (Maks.) | 35mm² | 35mm² | 35mm² | 35mm² | 35mm² | |
| Untuk pemasangan | Rel Din 35mm | |||||
| Bahan penutup | Thermoplastic UL94-V0 | |||||
| Tingkat perlindungan | IP20 | IP20 | IP20 | IP20 | IP20 | |
| Kode Pesanan | B16106 | B16118 | B16130 | B16142 | B16154 | |
| Kode Pesanan (Dengan sinyal jarak jauh) | B16107 | B16119 | B16131 | B16143 | B16155 | |
Fitur:
The surge arrestors BR-30FU meet the type 2 requirement class according to IEC 61643-11.
35mm electrical lead rail installation
Surge protective device, plug.
8/20us wave form, low residual voltage
Remote signaling port, remote alert
Hot melt flow double protection.
Connectable surge arrestor
The reaction time of less than 25 ns.
High arresting capacity
Visual status display
The maximum discharging currents (IMAX 8/20) of each line could be 30kA.
Labelled connections
Aplikasi:
Type 2 Surge Arresters provide protection against overvoltage originating from switching and the secondary effects of lightning strikes.
In order to shunt and pressure to limit indirect lightning current or other instantaneous overvoltage.
Floor distribution box of buildings
Instalasi:
• The type 2 arresters must install into sub-distribution boards after main distribution boards containing type 1 arresters.
• For proper operation between type 1 and type 2 arresters at least 10- 15 m cable or wire must be otherwise a decoupling coil have to install between the two devices.