Karakteristik produk:
| Spesifikasi | BR-25M 150 1P | BR-25M 275 1P | BR-25M 320 1P | |
| Klasifikasi SPD menurut EN61643-11 | Type 1 + Type 2 +Type 3 | Type 1 + Type 2 +Type 3 | Type 1 + Type 2 +Type 3 | |
| Klasifikasi SPD menurut IEC61643-11 | Class I + Class II + Class III | Class I + Class II + Class III | Class I + Class II + Class III | |
| Tegangan operasi nominal | Tidak | 120V(50/60Hz) | 230V(50/60Hz) | 250V(50/60Hz) |
| Maks. operasi terus menerus a.c. voltase | Uc | 150V(50/60Hz) | 275V(50/60Hz) | 320V(50/60Hz) |
| Arus impuls petir (10/350μs) | Imp | 25kA | 25kA | 25kA |
| Arus pelepasan nominal (8/20μs) | Di dalam | 25kA | 25kA | 25kA |
| Maks. arus pelepasan (8/20μs) | maksimal | 120kA | 120kA | 120kA |
| Jumlah muatan listrik | Q | 12.5A | 12.5A | 12.5A |
| Energi spesifik | W/R | 156kJ/Ω | 156kJ/Ω | 156kJ/Ω |
| Tingkat perlindungan tegangan | Ke atas | ≤0.8kV | ≤1.3kV | ≤1.3kV |
| Peringkat arus hubung singkat a.c. | Isccr | 25kA rms | 25kA rms | 25kA rms |
| Maks. sekering cadangan | 200A gG | 200A gG | 200A gG | |
| Tahan TOV tegangan lebih sementara | UT | 180V/5sec. | 335V/5sec. | 400V/5sec. |
| Temporary overvoltage TOV-safe failure | UT | 230V/120 menit. | 440V/120 menit. | 520V/120min. |
| Leakage current | Ipe | <2mA | <2mA | <2mA |
| Waktu respons | ta | ≤25ns | ≤25ns | ≤25ns |
| Kisaran suhu pengoperasian | kamu | -40℃-80℃ | -40℃-80℃ | -40℃-80℃ |
| Status pengoperasian/indikasi kesalahan | hijau/merah | hijau/merah | hijau/merah | |
| Luas penampang (Min.) | 4mm² | 4mm² | 4mm² | |
| Luas penampang (Maks.) | 35mm² | 35mm² | 35mm² | |
| Untuk pemasangan | Rel Din 35mm | |||
| Bahan penutup | Termoplastik UL94-V0 | |||
| Tingkat perlindungan | IP20 | IP20 | IP20 | |
| Kode Pesanan | B17206 | B18113 | B17219 | |
| Kode Pesanan (Dengan sinyal jarak jauh) | B17207 | B18114 | B17220 | |
Fitur:
The BR-25M 1P is an Type 1+2+3 AC surge protector device designed to protect at the entrance of the electrical installation.
There is a thermal cutoff member inside the protective device, when the device is over-current or over-voltage, the thermal cutoff member will automatically separate from the surge protective device from the electrical network, and the indication window will turn red from green.
This SPD is particularly useful in a high lightning density area where the risk of heavy surge current or even direct strike is high (e.g.: buildings equipped with lightning rods).
According to EN 61643-11 & IEC 61643-1
The BR-25M 1P is one-pole SPD.
Up: ≤1.3kV.
Standardized 35mm Din rail mounting, compact bistable rail fixed buckle, easy to disassemble.
Screw terminal connection, tightening force equivalent to twice the standard, make the connection more reliable and safer.
Aplikasi:
Used in AC power line of house, bank, telecom tower and so on.
Suitable as the first step of protection in incoming power supply panels and areas with greater exposure to the atmosphere, where installations are usually provided with an external lightning protection system.
Instalasi:
The 25kA first level surge protector shall be installed in a waterproof environment and free from violent vibration.
Ensure that the maximum continuous working voltage of the surge protector meets the actual requirements.
The wire connecting the surge protector should be as short and straight as possible, and the total length of the wire should be controlled within 0.5 meters.
Before powering on the power supply, check whether the cable is securely connected to the wiring terminal and whether the ground is reliable.
Informasi lebih lanjut atau konsultasi pribadi? Produk dan pengetahuan kami hadir untuk memberikan solusi.