Karakteristik produk:
| Spesifikasi | BR-12,5M 150 2P | BR-12,5M 275 2P | BR-12,5M 320 2P | |
| Klasifikasi SPD menurut EN61643-11 | Tipe 1 + Tipe 2 | Tipe 1 + Tipe 2 | Tipe 1 + Tipe 2 | |
| Klasifikasi SPD menurut IEC61643-11 | Kelas I + Kelas II | Kelas I + Kelas II | Kelas I + Kelas II | |
| Maks. operasi terus menerus a.c. voltase | Uc | 150V(50/60Hz) | 275V(50/60Hz) | 320V(50/60Hz) |
| Arus impuls petir (10/350μs) | Imp | 12,5kA | 12,5kA | 12,5kA |
| Arus pelepasan nominal (8/20μs) | Di dalam | 25kA | 25kA | 25kA |
| Maks. arus pelepasan (8/20μs) | maksimal | 60kA | 60kA | 60kA |
| Energi spesifik | W/R | 39kJ/Ω | 39kJ/Ω | 39kJ/Ω |
| Tingkat perlindungan tegangan | Ke atas | ≤0.8kV | ≤1.3kV | ≤1.5kV |
| Peringkat arus hubung singkat a.c. | Isccr | 25kA rms | 25kA rms | 25kA rms |
| Maks. sekering cadangan | 125A gG | 125A gG | 125A gG | |
| Tahan TOV tegangan lebih sementara | UT(L-N) | 180V/5sec. | 335V/5sec. | 400V/5sec. |
| Temporary overvoltage TOV-safe failure | UT(L-N) | 230V/120 menit. | 440V/120 menit. | 520V/120min. |
| Waktu respons | ta | ≤25ns | ≤25ns | ≤25ns |
| Kisaran suhu pengoperasian | kamu | -40℃-80℃ | -40℃-80℃ | -40℃-80℃ |
| Status pengoperasian/indikasi kesalahan | hijau/merah | hijau/merah | hijau/merah | |
| Luas penampang (Min.) | 4mm² | 4mm² | 4mm² | |
| Luas penampang (Maks.) | 35mm² | 35mm² | 35mm² | |
| Untuk pemasangan | Rel Din 35mm | |||
| Bahan penutup | Termoplastik UL94-V0 | |||
| Tingkat perlindungan | IP20 | IP20 | IP20 | |
| Kode Pesanan | B18211 | B18213 | B18215 | |
| Kode Pesanan (Dengan sinyal jarak jauh) | B18212 | B18214 | B18216 | |
Fitur:
Type 1+2.
High discharge capacity in a certain small size.
High follow current extinction and limitation due to no follow current technology.
Reliable safety due to double integrated disconnections with double protections.
Failure indication window, remote alarm terminal optional.
Plug design, easy maintenance.
High security performance.
Green light in notice window indicates normal; red indicates broken, replacement notice, which is clear and easy distinguished.
Indoor fixed installation, voltage limited type.
Small volume, pluggable.
Aplikasi:
To prevent power supply equipment from being damaged by surge and lightning.
Use on buildings in applications where there is an external lightning protection system installed, usually installed at the service entrance.
Widely used in the transformer low-voltage side as the first protection of the power supply.
Instalasi:
Installed in low-voltage distributions at the boundary of LPZ 0–LPZ 1 zones and higher to prevent overvoltage effects induced during a lightning strike and to prevent switching overvoltage.
Install in the main distribution cabinet/box of the low-voltage cabinet and the incoming line cabinet.
Recommended for main distribution boards.
During installation, please connect according to the installation schematic diagram, where L1, L2 and L3 are phase lines, N is the zero line and PE is the ground line.
Grounding should conform to the requirements of the specification of lightning protection.
Informasi lebih lanjut atau konsultasi pribadi? Produk dan pengetahuan kami hadir untuk memberikan solusi.