Quelle est la différence entre une forme d'onde 10/350 μs et 8/20 μs ?

19/12/2023

Selon la norme CEI61643-11, le dispositif de protection contre les surtensions de type 1 doit être testé par une forme d'onde de 10/350 μs et le SPD de type 2 doit être testé par une forme d'onde de 8/20 μs.

10/350μs waveform is a surge which reaches peak value at 10μs and it reduces to half of peak current at 350μs. Take BR-25GR type 1 SPD as an example, the product was tested at waveform which reach 25kA in 10μs which reduces to12.5kA at 350μs.

As comparison, 8/20μs waveform is a surge which reaches peak value at 8μs and reduces to half of peak current at 20μs. Take BR-40 type 2 SPD as an example, this product was tested at waveform which reach 40kA in 8μs which reduces to 20kA at 20μs.

As you can see from the above picture, 8/20μs waveform has much shorter time than the 10/350μs waveform. As energy equals to current square multiplied by resistor and time (E=I2Rt) and the time difference between the two wave is very big, therefore, a type 1 25kA SPD can discharge much more energy than a type 2 40kA SPD.

NOUVELLES CONNEXES
VOUS VOULEZ AUSSI VOIR
OBTENEZ UNE PROTECTION CONTRE LES SURTENSIONS
SOLUTIONS AUJOURD'HUI !
icône
icône
#!trpst#trp-gettext data-trpgettextoriginal=15#!trpen#Accélérateur de séraphinite#!trpst#/trp-gettext#!trpen##!trpst#trp-gettext data-trpgettextoriginal=16#!trpen#Optimized by #!trpst#trp-gettext data-trpgettextoriginal=15#!trpen#Accélérateur de séraphinite#!trpst#/trp-gettext#!trpen##!trpst#/trp-gettext#!trpen#