BRBD-4L SPDs For Dataline

Λάβετε μια προσφορά
Περιγραφή

Χαρακτηριστικά προϊόντος:

Προσδιορισμός BRBD-4L-6 BRBD-4L-12 BRBD-4L-24 BRBD-4L-48 BRBD-4L-60 BRBD-4L-180
SPD class TYPE2 P1 TYPE2 P1 TYPE2 P1 TYPE2 P1 TYPE2 P1 TYPE2 P1
Norminal voltage Ηνωμένα Έθνη 5V 12V 24V 48V 60V 180V
Μέγ. συνεχούς λειτουργίας d.c. δυναμικό Uc 6V 15V 33V 54V 70V 180V
Max. continuous operating a.c. voltage Uc 4.2V 10.6V 23.3V 38.1V 49.5V 127V
Nominal current at 45℃ IL 1A 1A 1A 1A 1A 0.75A
C2 Total Norminal discharge current (8/20μs) Σε 20 kA 20 kA 20 kA 20 kA 20 kA 20 kA
C2 Nominal discharge current (8/20μs) per line Σε 10kA 10kA 10kA 10kA 10kA 10kA
Voltage protection level line-line for In C2 Επάνω ≤15V ≤27V ≤55V ≤85V ≤110V ≤270V
Voltage protection level line-PG for In C2 Επάνω ≤600V ≤600V ≤600V ≤600V ≤600V ≤600V
Voltage protection level line-line at 1 kV/μs C3 Επάνω ≤9V ≤19V ≤45V ≤70V ≤90V ≤250V
Voltage protection level line-PG at 1 kV/μs C3 Επάνω ≤550V ≤550V ≤550V ≤550V ≤550V ≤550V
Series impedance per line 1 Ohm 1 Ohm 1 Ohm 1 Ohm 1 Ohm 1.8 Ohm
Cut-off frequency line-PG fG 1.0 MHz 2.8 MHz 7.8 MHz 8.7 MHz 11.0 MHz 25.0 MHz
Capacitance line-line C ≤5.4nF ≤2.0nF ≤1.0nF ≤0.7nF ≤500pF ≤240pF
capacitance line-PG C ≤16pF ≤16pF ≤16pF ≤16pF ≤16pF ≤16pF
Εύρος θερμοκρασίας λειτουργίας Tu -40℃…+80℃
Υλικό περιβλήματος Polyamide PA 6.6
Degree of protection (plugged-in) IP 20 IP 20 IP 20 IP 20 IP 20 IP 20
Order Code D9110 D9111 D9112 D9113 D9114 D9115

Χαρακτηριστικά:

Surge protection device.

Nominal voltage: 24V.

Nominal current at 45℃: 1A.

C2 Nominal discharge current (8/20us) per line: 10kA.

SPDs for Din rail mounting to enable easy installation.

According to IEC 61643-21.

Degree of protection: IP20.

Εφαρμογή:

Protection against indirect lightning effects.

Protect equipment with high-speed signal.

For the protection of network equipment.

Protect low frequency signaling application.

It protects AC power supply of sensitive data equipment against lightning induced surges.

Protects your AC power circuits against lightning induced surges.

Protect electronic equipment and power supply ports from power surge or lightning induced surges onto the signal cable, ground potential difference between equipment and electromagnetic coupling.

 

ΕΙΜΑΣΤΕ ΕΔΩ ΓΙΑ ΝΑ ΣΑΣ ΥΠΟΣΤΗΡΙΞΟΥΜΕ!

Περισσότερες πληροφορίες ή προσωπική διαβούλευση; Τα προϊόντα και η τεχνογνωσία μας υπάρχουν για να δώσουν λύσεις.

ΣΧΕΤΙΚΑ ΠΡΟΪΟΝΤΑ
ΣΧΕΤΙΚΑ ΝΕΑ
ΜΠΟΡΕΙ ΕΠΙΣΗΣ ΝΑ ΘΕΛΕΤΕ ΝΑ ΔΕΙΤΕ
ΑΠΟΚΤΗΣΤΕ ΤΗΝ ΠΡΟΣΤΑΣΙΑ ΑΠΟ ΤΥΠΟΥΣ
ΛΥΣΗ ΣΗΜΕΡΑ!
εικόνισμα
εικόνισμα
Seraphinite AcceleratorOptimized by Seraphinite Accelerator
Turns on site high speed to be attractive for people and search engines.