Produkteigenschaften:
| Spezifikation | BR-80 150 2P | BR-80 275 2P | BR-80 320 2P | BR-80 385 2P | ||
| SPD-Klassifizierung gemäß EN61643-11 | Typ 2 | Typ 2 | Typ 2 | Typ 2 | ||
| SPD-Klassifizierung gemäß IEC61643-11 | Class II | Class II | Class II | Class II | ||
| Max. Dauerbetrieb mit Wechselstrom Stromspannung | Uc | 150V | 275V | 320V | 385V | |
| Nominal discharge current (8/20μs) | In | 40kA | 40kA | 40kA | 40kA | |
| Max. discharge current (8/20μs) | Imax | 80kA | 80kA | 80kA | 80kA | |
| Spannungsschutzniveau | Hoch | ≤1.0kV | ≤1.7kV | ≤2.0kV | ≤2.3kV | |
| Voltage protection level 5kA | Hoch | ≤0.6kV | ≤1.0kV | ≤1.1kV | ≤1.2kV | |
| Max. backup fuse | 160A gG | 160A gG | 160A gG | 160A gG | ||
| Short-circuit withstand capacity | Isccr | 25kA | 25kA | 25kA | 25kA | |
| Temporary overvoltage TOV-withstand | UT | 180V/5sec. | 335V/5sec. | 400V/5sec. | 500V/5sec. | |
| Temporary overvoltage TOV-safe failure | UT | 230V/120min. | 440V/120min. | 520V/120min. | 650V/120min. | |
| Ansprechzeit | tA | ≤25ns | ≤25ns | ≤25ns | ≤25ns | |
| Betriebstemperaturbereich | Di | -40℃-80℃ | -40℃-80℃ | -40℃-80℃ | -40℃-80℃ | |
| Operating state/fault indication | green/red | green/red | green/red | green/red | ||
| Cross-section area (Min.) | 4mm² | 4mm² | 4mm² | 4mm² | ||
| Cross-section area (Max.) | 35mm² | 35mm² | 35mm² | 35mm² | ||
| Zur Montage | 35mm Din rail | |||||
| Gehäusematerial | Thermoplastic UL94-V0 | |||||
| Schutzart | IP20 | IP20 | IP20 | IP20 | ||
| Bestellcode | B18276 | B18278 | B18280 | B18282 | ||
| Order Code (With remote signaling) | B18277 | B18279 | B18281 | B18283 | ||
Merkmale:
Class II, Type 2, 80kA 2P.
Discharge currents : In : 40 kA / Imax : 80 kA.
IEC 61643-11 and EN 61643-11 compliance.
BR-80 is DIN rail compatible and is built with a plug-in module and a fixed base.
The BR-80 protects against the direct and indirect lightning strikes and large switching transients.
They are particularly useful in areas where space is limited.
Version with a remote signaling for disconnection indication is also available.
Anwendung:
Widely appreciated for its high level of protection, efficiency, and reliable performance, these single phase surge protectors are vastly used for protecting electrical devices such as computers, TVs, and other devices.
Application in industrial plants, commercial buildings, institutional facilities, and corporate offices.
For use in the Lightning Protection Zones Concept at the boundaries of LPZ 1-2 (according to IEC 1312-1 and EN62305).
Weitere Informationen oder eine persönliche Beratung? Unsere Produkte und unser Know-how sind da, um Lösungen anzubieten.