BR-60 2P Typ 2 60kA Überspannungsschutzgerät für TNS

Holen Sie sich ein Zitat
Beschreibung

Produkteigenschaften:

Spezifikation BR-60 150 2P BR-60 275 2P BR-60 320 2P BR-60 385 2P
SPD-Klassifizierung gemäß EN61643-11 Typ 2 Typ 2 Typ 2 Typ 2
SPD-Klassifizierung gemäß IEC61643-11 Class II Class II Class II Class II
Max. Dauerbetrieb mit Wechselstrom Stromspannung Uc 150V 275V 320V 385V
Nominal discharge current (8/20μs) In 30kA 30kA 30kA 30kA
Max. discharge current (8/20μs) Imax 60kA 60kA 60kA 60kA
Spannungsschutzniveau Hoch ≤1.0kV ≤1.6kV ≤1.8kV ≤2.2kV
Voltage protection level 5kA Hoch ≤0.5kV ≤0.6kV ≤1.0kV ≤1.2kV
Max. backup fuse 160A gG 160A gG 160A gG 160A gG
Short-circuit withstand capacity Isccr 25kA 25kA 25kA 25kA
Temporary overvoltage TOV-withstand UT 180V/5sec. 335V/5sec. 400V/5sec. 500V/5sec.
Temporary overvoltage TOV-safe failure UT 230V/120min. 440V/120min. 520V/120min. 650V/120min.
Ansprechzeit tA ≤25ns ≤25ns ≤25ns ≤25ns
Betriebstemperaturbereich Di -40℃-80℃ -40℃-80℃ -40℃-80℃ -40℃-80℃
Operating state/fault indication green/red green/red green/red green/red
Cross-section area (Min.) 4mm² 4mm² 4mm² 4mm²
Cross-section area (Max.) 35mm² 35mm² 35mm² 35mm²
Zur Montage 35mm Din rail
Gehäusematerial Thermoplastic   UL94-V0
Schutzart IP20 IP20 IP20 IP20
Bestellcode B18781 B18783 B18785 B18787
Order Code (With remote signaling) B18782 B18784 B18786 B18788

Merkmale:

High Surge Energy capacity protects downstream loads from voltage spikes and line transients.

Connected in parallel and use an MOV to clamp high-voltage surges.

Thermal protection circuit disconnects load under high energy absorption events.

This device is primarily used in the main electrical panel for the protection of 1-phase systems.

Fail safe/self-protection design.

Visual red-green indicator alerts when surge module needs replacement.

Certified: IEC61643-11:2013, Class II.

Remote alarm contact.

Touch Safe, IP20 Degree of Protection

Surge module plugs into DIN Rail mount base assembly for easy replacement in field.

Double thermal disconnection device, provide more reliable protection.

Two pole device provides full protection.

High discharge current — Imax 60kA per pole.

Narrow size, special design for saving installation space — width 18mm/pole, single phase.

Anwendung:

Useful in case of high lightning density areas.

This surge arrestor is suitable for all installations where risk of surge and spike activity and, particularly due to nearby lightning activity, as in telecom installations, oil rigs, and open exposed areas with metal structures.

This unit should be installed in all building and sites at high risk (where a Lightning Protection System is in place and there is risk to human life such as schools, hospitals etc.).

 

WIR SIND DA, UM SIE ZU UNTERSTÜTZEN!

Weitere Informationen oder eine persönliche Beratung? Unsere Produkte und unser Know-how sind da, um Lösungen anzubieten.

VERWANDTE PRODUKTE
VERWANDTE NACHRICHTEN
Vielleicht möchten Sie es auch sehen
ERHALTEN SIE ÜBERSPANNUNGSSCHUTZ
LÖSUNGEN HEUTE!
Symbol
Symbol
Seraphinite AcceleratorOptimized by Seraphinite Accelerator
Turns on site high speed to be attractive for people and search engines.