BR-50GR 1+1 Type 1 50kA Surge Arrester for TT and TNS

Holen Sie sich ein Zitat
Beschreibung

Produkteigenschaften:

Spezifikation BR-50GR 150 1+1 BR-50GR 275 1+1 BR-50GR 350 1+1
SPD-Klassifizierung gemäß EN61643-11 Type 1 + Type 2 Type 1 + Type 2 Type 1 + Type 2
SPD-Klassifizierung gemäß IEC61643-11 Class I + Class II Class I + Class II Class I + Class II
Nominal operating voltage Un 120V(50/60Hz) 230V(50/60Hz) 250V(50/60Hz)
Max. Dauerbetrieb mit Wechselstrom Stromspannung Uc (L-N/N-PE) 150V/255V(50/60Hz) 275V/255V(50/60Hz) 350V/255V(50/60Hz)
Lightning impulse current (10/350μs) Iimp (L-N/N-PE) 50kA/100kA 50kA/100kA 50kA/100kA
Nominal discharge current (8/20μs) In (L-N/N-PE) 50kA/100kA 50kA/100kA 50kA/100kA
Max. discharge current (8/20μs) Imax (L-N/N-PE) 160kA/200kA 160kA/200kA 160kA/200kA
Quantity of electric charge (L-N, N-PE) Q 25As, 50As 25As, 50As 25As, 50As
Specific energy (L-N, N-PE) W/R 625kJ/Ω, 2500kJ/Ω 625kJ/Ω, 2500kJ/Ω 625kJ/Ω, 2500kJ/Ω
Spannungsschutzniveau Up (L-N/N-PE) ≤1.5kV/≤1.5kV ≤1.5kV/≤1.5kV ≤1.5kV/≤1.5kV
Short-circuit current rating a.c. Isccr (L-N/N-PE) 25kA rms/100A rms 25kA rms/100A rms 25kA rms/100A rms
Max. backup fuse 350A gG 350A gG 350A gG
Temporary overvoltage TOV-withstand UT (L-N) 230V/120min. 440V/120min. 580V/120min.
Temporary overvoltage TOV-withstand UT (N-PE) 1200V/200ms 1200V/200ms 1200V/200ms
Ansprechzeit tA ≤100ns ≤100ns ≤100ns
Betriebstemperaturbereich Di -40℃-80℃ -40℃-80℃ -40℃-80℃
Operating state/fault indication green/red green/red green/red
Cross-section area (Min.) 4mm² 4mm² 4mm²
Cross-section area (Max.) 35mm² 35mm² 35mm²
Zur Montage 35mm Din rail
Gehäusematerial Thermoplast UL94-V0
Schutzart IP20 IP20 IP20
Bestellcode B17168 B18157 B17194
Order Code (With remote signaling) B17169 B18158 B17195

Merkmale:

Endurable, sustains multiple strikes.

LED status indication.

BR-50GR 1P+N is suitable for TT and TN-S system.

SPD indoor fixedly mounted, limiting voltage.

SPD has built-in disconnector, when SPD is invalid due to overheating or breakdown, the disconnector can automatically separate SPD from the network, meanwhile send an indication signal. If to be separated from network, the visible window will show red color.

Anwendung:

Being total current arresters between the neutral and protective conductor in TT systems, the single-pole N-PE lightning current arresters of type BR-50GR NPE help to ensure fulfilling the requirements for protection of personnel and equipment in “1+1” circuits.

The BR-50GR NPE coordinated NPE lightning current arresters hold a special position among total current arresters. Due to their low voltage protection level, they can be directly coordinated with N-PE surge arresters of the BR-50GR surge arresters without additional decoupling coil.

BR-50GR NPE devices are suitable for connecting conductors and busbars, allowing comfortable wiring with other DIN rail mounted terminals.

Widely used in mobile communication base stations, microwave communication bureaus/stations, telecommunication rooms, industrial mining, civil aviation, financial securities and other power systems.

Installation and note:

Usually installed in the low-voltage main distribution cabinet of the building incoming line.

Lightning protection grounding should meet the lightning protection specifications; the grounding wire should be as short as possible.

 

WIR SIND DA, UM SIE ZU UNTERSTÜTZEN!

Weitere Informationen oder eine persönliche Beratung? Unsere Produkte und unser Know-how sind da, um Lösungen anzubieten.

VERWANDTE PRODUKTE