BR-40VG 4P Type 2 40kA Surge Protection

Holen Sie sich ein Zitat
Beschreibung

Produkteigenschaften:

Spezifikation BR-40VG 150 4P BR-40VG 275 4P BR-40VG 320 4P BR-40VG 385 4P BR-40VG 440 4P
SPD-Klassifizierung gemäß EN61643-11 Typ 2 Typ 2 Typ 2 Typ 2 Typ 2
SPD-Klassifizierung gemäß IEC61643-11 Class II Class II Class II Class II Class II
Max. Dauerbetrieb mit Wechselstrom Stromspannung Uc 150V 275V 320V 385V 440V
Nominal discharge current (8/20μs) In 20kA 20kA 20kA 20kA 20kA
Max. discharge current (8/20μs) Imax 40kA 40kA 40kA 40kA 40kA
Spannungsschutzniveau Hoch ≤1,3 kV ≤1,3 kV ≤1.5kV ≤1.8kV ≤2.0kV
Max. backup fuse 100A gG 100A gG 100A gG 100A gG 100A gG
Short-circuit withstand capacity Isccr 25kA 25kA 25kA 25kA 25kA
Temporary overvoltage TOV-withstand UT 180V/5sec. 335V/5sec. 400V/5sec. 500V/5sec. 580V/5sec.
Temporary overvoltage TOV-safe failure UT 230V/120min. 440V/120min. 520V/120min. 650V/120min. 765V/120min.
Ansprechzeit tA ≤100ns ≤100ns ≤100ns ≤100ns ≤100ns
Betriebstemperaturbereich Di -40℃-80℃ -40℃-80℃ -40℃-80℃ -40℃-80℃ -40℃-80℃
Operating state/fault indication green/red green/red green/red green/red green/red
Cross-section area (Min.) 4mm² 4mm² 4mm² 4mm² 4mm²
Cross-section area (Max.) 35mm² 35mm² 35mm² 35mm² 35mm²
Zur Montage 35mm Din rail
Gehäusematerial Thermoplastic   UL94-V0
Schutzart IP20 IP20 IP20 IP20 IP20
Bestellcode B17506 B17518 B17530 B17542 B17554
Order Code (With remote signaling) B17507 B17519 B17531 B17543 B17555

Merkmale:

Electric ratings: 230/400V, AC50/60Hz, 3-phase;

In: 20kA.

Surge protective device, plug.

Uc 150V / 275V / 320V / 385V / 440V can be achieved.

Standard: IEC/EN 61643-11

Hot melt flow double protection.

The visual window color said protector working state; green (normal), red (fault).

The reaction time of less than 100 ns.

Number of poles: 4;

Short circuit current: up to 40kA (8/20μs);

Remote signaling can select.

It is designed as module and 35mm din rail mounting.

Consisting of a base part and plug-in protection modules.

Anwendung:

Protect electric system and on-loading electrical apparatus from thunder and instantaneous over-voltage.

In order to shunt and pressure to limit indirect lightning current or other instantaneous overvoltage.

 

WIR SIND DA, UM SIE ZU UNTERSTÜTZEN!

Weitere Informationen oder eine persönliche Beratung? Unsere Produkte und unser Know-how sind da, um Lösungen anzubieten.

VERWANDTE PRODUKTE
VERWANDTE NACHRICHTEN
Vielleicht möchten Sie es auch sehen
ERHALTEN SIE ÜBERSPANNUNGSSCHUTZ
LÖSUNGEN HEUTE!
Symbol
Symbol
Seraphinite AcceleratorOptimized by Seraphinite Accelerator
Turns on site high speed to be attractive for people and search engines.