Produkteigenschaften:
| Spezifikation | BR275-40DP 3+1 | BR320-40DP 3+1 | |||
| SPD-Klassifizierung gemäß EN61643-11 | Typ 2 + Typ 3 | Typ 2 + Typ 3 | |||
| SPD-Klassifizierung gemäß IEC61643-11 | Klasse II + Klasse III | Klasse II + Klasse III | |||
| Max. Dauerbetrieb mit Wechselstrom Stromspannung | Uc(L-N/N-PE) | 275V/255V | 320V/255V | ||
| Nominal discharge current (8/20μs) | In | 20kA | 20kA | ||
| Max. discharge current (8/20μs) | Imax | 40kA | 40kA | ||
| Kombinierter Impuls | Uoc | 10kV | 10kV | ||
| Spannungsschutzniveau | Up(L-N/N-PE) | ≤1.3kV/≤1.5kV | ≤1.5kV/≤1.5kV | ||
| Ansprechzeit | tA | ≤25ns | ≤25ns | ||
| Betriebstemperaturbereich | Di | -40℃-80℃ | -40℃-80℃ | ||
| Betriebszustands-/Fehleranzeige | green / red | green / red | |||
| Cross-section area (Min.) | 2.5mm² | 2.5mm² | |||
| Cross-section area (Max.) | 16mm² | 16mm² | |||
| Zur Montage | 35mm Din rail | 35mm Din rail | |||
| Gehäusematerial | Thermoplast UL94-V0 | ||||
| Schutzart | IP20 | IP20 | |||
| Bestellcode | B18243 | B17254 | |||
| Order code (with remote signal) | B18244 | B17255 | |||
Merkmale:
Type 2 + Type 3 Surge Protector.
Uc 275V/320V.
This three phase SPD din-rail for lightning protection and other spikes in electrical power has a maximum amperage of 40 kA.
Response time: ≤25ns.
Pole number: 2P, 4P, 1P+N, 3P+N.
UL 94 V-0 Thermoplastic Housing.
DIN rail compatible.
Remote Signaling in option.
Degree of protection: IP20.
Conforming fully to international IEC 61643-11 and EN 61643-11 standards.
It can provide type 3 protection for equipment which installed within 5 meters from these devices.
Anwendung:
For protection of power supply systems.
For the protection of low voltage distribution systems against transient overvoltage caused by indirect lightning stroke and switching operations.
For using in the lightning protection zones concept at boundary 2-3.
Applied to power supply protection of equipment system in areas with high lightning risk.
Installation:
Suitable as the final stage of protection in panels with Type 2 protection devices installed upstream.
These SPDs should be installed as close as possible to the equipment being protected.
Installed at a minimum conductor length of 10 meters (30 feet) from the electrical service panel to the point of utilization, for example cord connected, direct plug-in, receptacle type SPDs installed at the utilization equipment being protected. The distance (10 meters) is exclusive of the conductors provided with or used to attach SPDs.