Spezifikation BR-25VG 320 3+1 BR-25VG 440 3+1 BR-25VG 690 3+1
SPD-Klassifizierung gemäß EN61643-11 Type 1 + Type 2 +Type 3
SPD-Klassifizierung gemäß IEC61643-11 Class I + Class II + Class III
Nominal operating voltage Un 250V/440V(50/60Hz) 250V/440V(50/60Hz) 400V/690V(50/60Hz)
Max. Dauerbetrieb mit Wechselstrom Stromspannung Uc(L-N/N-PE) 320V/255V(50/60Hz) 440V/255V(50/60Hz) 690V/255V(50/60Hz)
Lightning impulse current (10/350μs) Iimp(L-N/N-PE) 25kA/100kA 25kA/100kA 25kA/100kA
Total discharge current (10/350μs) Itotal 100kA 100kA 100kA
Nominal discharge current (8/20μs) In(L-N/N-PE) 30kA/100kA 30kA/100kA 30kA/100kA
Max. discharge current (8/20μs) Imax(L-N/N-PE) 100kA/160kA 100kA/160kA 100kA/160kA
Quantity of electric charge Q 12.5As/50As 12.5As/50As 12.5As/50As
Specific energy W/R 156kJ/Ω, 2500kJ/Ω 156kJ/Ω, 2500kJ/Ω 156kJ/Ω, 2500kJ/Ω
Spannungsschutzniveau Up(L-N/N-PE) ≤1.5kV/≤1.5kV ≤1.8kV/≤1.5kV ≤2.5kV/≤1.5kV
Short-circuit current rating a.c. Isccr(L-N/N-PE) 25kA rms/100A rms 25kA rms/100A rms 25kA rms/100A rms
Max. backup fuse 200A gG 200A gG 200A gG
Temporary overvoltage TOV-withstand UT(L-N) 400V/5sec. 580V/5sec. 800V/5sec.
Temporary overvoltage TOV-safe failure UT(L-N) 520V/120min. 765V/120min. 1000V/120min.
Temporary overvoltage TOV-withstand UT(N-PE) 1200V/200ms 1200V/200ms 1200V/200ms
Leakage current Ipe None None None
Ansprechzeit tA(L-N/N-PE) ≤100ns/≤100ns ≤100ns/≤100ns ≤100ns/≤100ns
Betriebstemperaturbereich Di -40℃-80℃ -40℃-80℃ -40℃-80℃
Operating state/fault indication green/red green/red green/red
Cross-section area (Min.) 4mm² 4mm² 4mm²
Cross-section area (Max.) 35mm² 35mm² 35mm²
Zur Montage 35mm Din rail
Gehäusematerial Thermoplast UL94-V0
Schutzart IP20 IP20 IP20
Bestellcode B17269 B17281 B17293
Order Code (With remote signaling) B17270 B17282 B17294

Merkmale:

The surge arrestors BR-25VG meet the Class I and Class II requirement class according to IEC 61643-11.

Powerful components, suitable for all kinds of common power systems.

Visual status display.

The unit is designed to be used between Zone O and Zone 1 (according to IEC62305-4 definition of Lightning Protection Area).

Available with optional remote signaling.

Simple standard rail mounting.

The use of high-performance varistors permits a rapid response time and a low protection level.

Anwendung:

• These devices protect low-voltage consumer systems from overvoltage.

• It is applicable to lightning protection for the power system in areas with high lightning risk (LPZ0B or the interface between LPZ0B and LPZ1).

• Applied in modular SPD Class I + Class II (Class B + C) for TT and TN-S power supply system.

Installation:

• Power must be cut off before installation. Live operation is prohibited.

• It is recommended that a fuse or circuit breaker be connected in series at the front end of the surge protection.

• SPD is installed in parallel at the power supply inlet end of the building distribution box or the equipment room. The product is installed in the guide rail type. If conditions permit, the Kevin connection mode can be adopted.

• During installation, connect the device according to the installation diagram, where L is the phase line,N is the neutral line, and PE is the ground line. Do not misconnect the device. After the installation is complete, turn on the automatic circuit breaker and check whether the working status is normal.

• When the SPD is in use, check the status of the fault display window regularly. If the fault display window is red or the remote terminal outputs an alarm signal, it indicates that the SPD is faulty and should be repaired or replaced in time.

• Suitable for indoor operation, such as installed in the outdoor, must be equipped with waterproof shell.

 

WIR SIND DA, UM SIE ZU UNTERSTÜTZEN!

Weitere Informationen oder eine persönliche Beratung? Unsere Produkte und unser Know-how sind da, um Lösungen anzubieten.

VERWANDTE PRODUKTE
VERWANDTE NACHRICHTEN
Vielleicht möchten Sie es auch sehen
ERHALTEN SIE ÜBERSPANNUNGSSCHUTZ
LÖSUNGEN HEUTE!
Symbol
Symbol
Seraphinite AcceleratorOptimized by Seraphinite Accelerator
Turns on site high speed to be attractive for people and search engines.