BR-25GR 3P+N Type 1 25kA Surge Arrester for TT and TNS

Holen Sie sich ein Zitat
Beschreibung

Produkteigenschaften:

Spezifikation BR-25GR 150 3P+N BR-25GR 275 3P+N BR-25GR 350 3P+N
SPD-Klassifizierung gemäß EN61643-11 Type 1 + Type 2 Type 1 + Type 2 Type 1 + Type 2
SPD-Klassifizierung gemäß IEC61643-11 Class I + Class II Class I + Class II Class I + Class II
Nominal operating voltage Un 120V/240V(50/60Hz) 230V/400V(50/60Hz) 250V/440V(50/60Hz)
Max. Dauerbetrieb mit Wechselstrom Stromspannung Uc (L-N/N-PE) 150V/255V(50/60Hz) 275V/255V(50/60Hz) 350V/255V(50/60Hz)
Lightning impulse current (10/350μs) Iimp (L-N/N-PE) 25kA/100kA 25kA/100kA 25kA/100kA
Nominal discharge current (8/20μs) In (L-N/N-PE) 25kA/100kA 25kA/100kA 25kA/100kA
Max. discharge current (8/20μs) Imax (L-N/N-PE) 100kA/200kA 100kA/200kA 100kA/200kA
Quantity of electric charge (L-N, N-PE) Q 12.5As, 50As 12.5As, 50As 12.5As, 50As
Specific energy (L-N, N-PE) W/R 156kJ/Ω, 2500kJ/Ω 156kJ/Ω, 2500kJ/Ω 156kJ/Ω, 2500kJ/Ω
Spannungsschutzniveau Up (L-N/N-PE) ≤1.5kV/≤1.5kV ≤1.5kV/≤1.5kV ≤1.5kV/≤1.5kV
Short-circuit current rating a.c. Isccr (L-N/N-PE) 25kA rms/100A rms 25kA rms/100A rms 25kA rms/100A rms
Max. backup fuse 315A gG 315A gG 315A gG
Temporary overvoltage TOV-withstand UT (L-N) 230V/120min. 440V/120min. 580V/120min.
Temporary overvoltage TOV-withstand UT (N-PE) 1200V/200ms 1200V/200ms 1200V/200ms
Ansprechzeit tA ≤100ns ≤100ns ≤100ns
Betriebstemperaturbereich Di -40℃-80℃ -40℃-80℃ -40℃-80℃
Operating state/fault indication green/red green/red green/red
Cross-section area (Min.) 4mm² 4mm² 4mm²
Cross-section area (Max.) 35mm² 35mm² 35mm²
Zur Montage 35mm Din rail
Gehäusematerial Thermoplast UL94-V0
Schutzart IP20 IP20 IP20
Bestellcode B17128 B17141 B17154
Order Code (With remote signaling) B17129 B17142 B17155

Merkmale:

Core components are strictly screened, stable performance and reliable operation.

Using the latest arc extinguishing technology to avoid fire completely

Module is designed and installed conveniently.

Status indication.

Model: BR-25GR 3P+N.

Protection class: Type 1,Class I

Thermal disconnect device.

SPD Iimp 25kA AC Power Surge Arrester.

Widely suitable for TT system,for protecting the buildings to avoid national defense.

Anwendung:

• Protects electrical installations against direct lightning strokes, and discharge the back-current from lightning spreading from the earth conductor to the network conductors.

• Used to AC power system, power distribution system, terminal devices, electronic equipment, buildings, industrial enterprises and Medical institutes etc.

 

WIR SIND DA, UM SIE ZU UNTERSTÜTZEN!

Weitere Informationen oder eine persönliche Beratung? Unsere Produkte und unser Know-how sind da, um Lösungen anzubieten.

VERWANDTE PRODUKTE
VERWANDTE NACHRICHTEN
Vielleicht möchten Sie es auch sehen
ERHALTEN SIE ÜBERSPANNUNGSSCHUTZ
LÖSUNGEN HEUTE!
Symbol
Symbol
Seraphinite AcceleratorOptimized by Seraphinite Accelerator
Turns on site high speed to be attractive for people and search engines.