Product characteristics:
| Specification | BR-7M 150 1P | BR-7M 275 1P | BR-7M 320 1P | |
| SPD classification according to EN61643-11 | Type 1 + Type 2 | Type 1 + Type 2 | Type 1 + Type 2 | |
| SPD classification according to IEC61643-11 | Class I + Class II | Class I + Class II | Class I + Class II | |
| Max. continuous operating a.c. voltage | Uc | 150V(50/60Hz) | 275V(50/60Hz) | 320V(50/60Hz) | 
| Lightning impulse current (10/350μs) | Iimp | 7kA | 7kA | 7kA | 
| Nominal discharge current (8/20μs) | In | 20kA | 20kA | 20kA | 
| Max. discharge current (8/20μs) | Imax | 50kA | 50kA | 50kA | 
| Specific energy | W/R | 12.25kJ/Ω | 12.25kJ/Ω | 12.25kJ/Ω | 
| Voltage protection level | Up | ≤0.8kV | ≤1.3kV | ≤1.5kV | 
| Short-circuit current rating a.c. | Isccr | 25kA rms | 25kA rms | 25kA rms | 
| Max. backup fuse | 125A gG | 125A gG | 125A gG | |
| Temporary overvoltage TOV-withstand | UT(L-N) | 180V/5sec. | 335V/5sec. | 400V/5sec. | 
| Temporary overvoltage TOV-safe failure | UT(L-N) | 230V/120min. | 440V/120min. | 520V/120min. | 
| Response time | tA | ≤25ns | ≤25ns | ≤25ns | 
| Operating temperature range | Tu | -40℃-80℃ | -40℃-80℃ | -40℃-80℃ | 
| Operating state/fault indication | green/red | green/red | green/red | |
| Cross-section area (Min.) | 4mm² | 4mm² | 4mm² | |
| Cross-section area (Max.) | 35mm² | 35mm² | 35mm² | |
| For mounting on | 35mm Din rail | |||
| Enclosure material | Thermoplastic UL94-V0 | |||
| Degree of protection | IP20 | IP20 | IP20 | |
| Order Code | B17318 | B17320 | B17322 | |
| Order Code (With remote signaling) | B17319 | B17321 | B17323 | |
Features:
The technical performance of the products meets the standard technical equipment of GB18802.1 and IEC61643-11.
It adopts 35mm standard rail.
This model designed in modular with excellent airtight property.
It is with 35mm din rail, which make it easy for installation.
Application:
Installation at LPZ 0 -1 or higher, protecting low voltage equipment.
Applied in PSD Class I+II (Class B+C).
Connected to AC low-voltage power systems for protection of equipment from transient over-voltage caused by the inducted lightning stroke or internal power systems.
Installation:
The protector is installed with standard 35mm track.
The protector is connected by 4 ~ 35mm copper wire.
No need to adjust after the protector is installed as required.
During operation, regularly check whether the module is red; replace the failed component in time.