{"id":2700,"date":"2026-10-07T16:51:16","date_gmt":"2026-10-07T08:51:16","guid":{"rendered":"https:\/\/www.britecelectric.com\/?post_type=blog&#038;p=2700"},"modified":"2026-10-13T14:54:50","modified_gmt":"2026-10-13T06:54:50","slug":"where-to-install-solar-spd-in-pv-combiner-box","status":"publish","type":"blog","link":"https:\/\/www.britecelectric.com\/tr\/blog\/where-to-install-solar-spd-in-pv-combiner-box\/","title":{"rendered":"Where to Install a Solar SPD in a PV Combiner Box"},"content":{"rendered":"<p style=\"margin: 0 0 18px 0; font-family: Arial,Helvetica,sans-serif; font-size: 16px; line-height: 1.8; color: #333333;\">By the Britec Electric engineering team \u2014 Britec Electric (Wenzhou, Zhejiang, China) has manufactured IEC\/EN 61643 surge protective devices since 2003, with products certified by T\u00dcV, CE and Intertek SEMKO and an ISO 9001 quality system. This guide explains, from a PV system designer\u2019s perspective, exactly where a solar SPD should be mounted inside a PV combiner box and why that position determines how much lightning and switching-surge energy actually gets diverted before it reaches the inverter.<\/p>\r\n\r\n<h2 style=\"font-family: Arial,Helvetica,sans-serif; font-size: 24px; color: #1a1a1a; margin: 28px 0 12px 0; border-bottom: 2px solid #009292; padding-bottom: 6px;\">Why the PV Combiner Box Is the Correct Location for a Solar SPD<\/h2>\r\n<p style=\"margin: 0 0 18px 0; font-family: Arial,Helvetica,sans-serif; font-size: 16px; line-height: 1.8; color: #333333;\">A PV combiner box sits between the PV string cabling and the inverter. It aggregates the output of several DC strings through fuses or circuit breakers onto a common DC busbar, then feeds the inverter. The array cabling is the longest, most exposed part of the system \u2014 metres of conductor run across rooftops and open ground, acting as an antenna for induced lightning overvoltage. If you only protect the inverter input, the surge has already travelled the full string length unchecked.<\/p>\r\n<p style=\"margin: 0 0 18px 0; font-family: Arial,Helvetica,sans-serif; font-size: 16px; line-height: 1.8; color: #333333;\">Placing a dedicated DC SPD at the combiner box gives the first and best clamping point: it intercepts the overvoltage right where the exposed array wiring enters the protected zone. For a deeper look at whether a PV system needs surge protection at all, see our guide on <a style=\"color: #009292; text-decoration: underline;\" href=\"https:\/\/www.britecelectric.com\/tr\/blog\/electrical-spd-for-solar-pv-systems-do-you-really-need-it\/\" target=\"_blank\" rel=\"noopener noreferrer\">whether you really need an SPD for solar PV systems<\/a>.<\/p>\r\n<p style=\"margin: 0 0 18px 0; font-family: Arial,Helvetica,sans-serif; font-size: 16px; line-height: 1.8; color: #333333;\">The goal is simple: divert the surge to earth as close as possible to the point where the string conductors enter the box, with the shortest possible SPD lead length.<\/p>\r\n\r\n<h2 style=\"font-family: Arial,Helvetica,sans-serif; font-size: 24px; color: #1a1a1a; margin: 28px 0 12px 0; border-bottom: 2px solid #009292; padding-bottom: 6px;\">Where Exactly to Mount the SPD Inside the Combiner Box<\/h2>\r\n<p style=\"margin: 0 0 18px 0; font-family: Arial,Helvetica,sans-serif; font-size: 16px; line-height: 1.8; color: #333333;\">The SPD must be connected in parallel across the DC bus, on the incoming (array) side of the combiner \u2014 not on the outgoing inverter side. Follow this physical order from the cable entry inward:<\/p>\r\n<p style=\"margin: 0 0 6px 0; font-family: Arial,Helvetica,sans-serif; font-size: 16px; line-height: 1.8; color: #333333;\">\u25cf Mount the SPD directly on the positive and negative DC busbar, between the string fuses\/breakers and the combiner output terminal.<\/p>\r\n<p style=\"margin: 0 0 6px 0; font-family: Arial,Helvetica,sans-serif; font-size: 16px; line-height: 1.8; color: #333333;\">\u25cf Position it as close as physically possible to the incoming string terminals \u2014 ideally within 0.5 m of lead length from the busbar to the SPD.<\/p>\r\n<p style=\"margin: 0 0 6px 0; font-family: Arial,Helvetica,sans-serif; font-size: 16px; line-height: 1.8; color: #333333;\">\u25cf Install it on the array side so every string is protected before its current reaches the common bus and the inverter feed.<\/p>\r\n<p style=\"margin: 0 0 6px 0; font-family: Arial,Helvetica,sans-serif; font-size: 16px; line-height: 1.8; color: #333333;\">\u25cf Keep the SPD away from the enclosure door and any moving parts; DIN-rail mount it on the same rail as the string breakers for a short, clean connection.<\/p>\r\n<p style=\"margin: 0 0 18px 0; font-family: Arial,Helvetica,sans-serif; font-size: 16px; line-height: 1.8; color: #333333;\">\u25cf For a multi-string box, one Type 1+2 SPD across the main + \/ \u2212 bus is normally sufficient; do not fit a separate SPD per string unless the design calls for it.<\/p>\r\n<p style=\"margin: 0 0 18px 0; font-family: Arial,Helvetica,sans-serif; font-size: 16px; line-height: 1.8; color: #333333;\">In practice the SPD is the last device the incoming surge meets before the busbar. That placement is what limits the let-through voltage (Up) seen by the inverter and the DC isolator downstream.<\/p>\r\n<p style=\"margin: 22px 0; font-family: Arial,Helvetica,sans-serif; font-size: 16px; line-height: 1.8; color: #ffffff; background: #009292; border-radius: 8px; padding: 20px 24px; text-align: center;\"><strong style=\"font-size: 18px; color: #ffffff;\">Specifying SPDs for your PV combiner boxes?<\/strong>\r\nBritec supplies IEC 61643-31 Type 1+2 DC SPDs in 1000 V and 1500 V classes, with DIN-rail modules and remote-signal options for panel builders.\r\n<a style=\"display: inline-block; margin-top: 12px; background: #ffffff; color: #009292; text-decoration: none; font-weight: bold; padding: 10px 22px; border-radius: 6px;\" href=\"https:\/\/www.britecelectric.com\/tr\/contact-us\/\" target=\"_blank\" rel=\"noopener noreferrer\">Request a combiner-box SPD quote<\/a><\/p>\r\n\r\n<h2 style=\"font-family: Arial,Helvetica,sans-serif; font-size: 24px; color: #1a1a1a; margin: 28px 0 12px 0; border-bottom: 2px solid #009292; padding-bottom: 6px;\">Wiring and Equipotential Bonding Rules<\/h2>\r\n<p style=\"margin: 0 0 18px 0; font-family: Arial,Helvetica,sans-serif; font-size: 16px; line-height: 1.8; color: #333333;\">Correct position is only half the story \u2014 the wiring determines whether the SPD actually performs. Inductance in the leads is the enemy: every extra centimetre of conductor lets the surge overshoot the rated protection level.<\/p>\r\n<p style=\"margin: 0 0 6px 0; font-family: Arial,Helvetica,sans-serif; font-size: 16px; line-height: 1.8; color: #333333;\">\u25cf Use the shortest possible connection from the SPD terminals to the DC busbar; keep both the live and the protective-earth leads short and equal in length.<\/p>\r\n<p style=\"margin: 0 0 6px 0; font-family: Arial,Helvetica,sans-serif; font-size: 16px; line-height: 1.8; color: #333333;\">\u25cf Bond the SPD\u2019s earthing terminal to the combiner box chassis and the site earth bar with a low-impedance, direct conductor \u2014 never share a long daisy-chained earth path.<\/p>\r\n<p style=\"margin: 0 0 6px 0; font-family: Arial,Helvetica,sans-serif; font-size: 16px; line-height: 1.8; color: #333333;\">\u25cf Keep the SPD earth lead separate from the DC power leads and route it straight to the enclosure earth point.<\/p>\r\n<p style=\"margin: 0 0 18px 0; font-family: Arial,Helvetica,sans-serif; font-size: 16px; line-height: 1.8; color: #333333;\">\u25cf Verify the enclosure itself is bonded to the PV system earthing electrode conductor so the diverted current has a low-resistance path to earth.<\/p>\r\n<p style=\"text-align: center; margin: 18px 0;\"><a href=\"https:\/\/www.britecelectric.com\/tr\/product\/brpv3-1500-12-5-t1t2-1500v-12-5ka-pv-surge-protection-device\/\" target=\"_blank\" rel=\"noopener noreferrer\"><img style=\"max-width: 320px; height: auto; border: 1px solid #e3e8ef; border-radius: 6px; padding: 6px; background: #ffffff;\" src=\"https:\/\/www.britecelectric.com\/wp-content\/uploads\/2026\/09\/BRPV3-1500-12.5.webp\" alt=\"BRPV3-1500-12.5 1500V T1+T2 PV surge arrester for solar SPD\" \/><\/a><\/p>\r\n\r\n<h2 style=\"font-family: Arial,Helvetica,sans-serif; font-size: 24px; color: #1a1a1a; margin: 28px 0 12px 0; border-bottom: 2px solid #009292; padding-bottom: 6px;\">Selecting the Right DC SPD Type and Voltage Rating<\/h2>\r\n<p style=\"margin: 0 0 18px 0; font-family: Arial,Helvetica,sans-serif; font-size: 16px; line-height: 1.8; color: #333333;\">A solar SPD inside a combiner box must comply with IEC\/EN 61643-31 (PV applications) and match the system\u2019s open-circuit voltage. Two decisions matter most: the Type and the voltage class.<\/p>\r\n<p style=\"margin: 0 0 18px 0; font-family: Arial,Helvetica,sans-serif; font-size: 16px; line-height: 1.8; color: #333333;\"><strong style=\"color: #1a1a1a;\">Type:<\/strong> For a combiner box exposed to both direct and indirect lightning, a Type 1+2 (T1+T2) device is the safest choice because it handles the partial lightning current (10\/350 \u00b5s) and the induced surge. A pure Type 2 is acceptable only where an upstream T1 already exists. If you are unsure which Type your site needs, our comparison of <a style=\"color: #009292; text-decoration: underline;\" href=\"https:\/\/www.britecelectric.com\/tr\/blog\/type-1-vs-1-2-vs-2-vs-3-dc-spd-which-to-choose\/\" target=\"_blank\" rel=\"noopener noreferrer\">Type 1, Type 1+2, Type 2 and Type 3 DC SPDs<\/a> breaks it down by application.<\/p>\r\n<p style=\"margin: 0 0 18px 0; font-family: Arial,Helvetica,sans-serif; font-size: 16px; line-height: 1.8; color: #333333;\"><strong style=\"color: #1a1a1a;\">Voltage rating:<\/strong> Match Ucpv to the array\u2019s maximum open-circuit voltage. For a 1000 V system the <a style=\"color: #009292; text-decoration: underline;\" href=\"https:\/\/www.britecelectric.com\/tr\/product\/brpv3-1000-type-2-surge-protection-device-for-pv-upto-1000v\/\" target=\"_blank\" rel=\"noopener noreferrer\">BRPV3-1000 Type 2 PV surge arrester<\/a> is the standard fit, while 1500 V arrays need a 1500 V-class device such as the <a style=\"color: #009292; text-decoration: underline;\" href=\"https:\/\/www.britecelectric.com\/tr\/product\/brpv3-1500-12-5-t1t2-1500v-12-5ka-pv-surge-protection-device\/\" target=\"_blank\" rel=\"noopener noreferrer\">BRPV3-1500-12.5 T1+T2 PV surge arrester<\/a>. The choice between the two voltage classes affects let-through and cost \u2014 see our post on <a style=\"color: #009292; text-decoration: underline;\" href=\"https:\/\/www.britecelectric.com\/tr\/blog\/1500v-vs-1000v-dc-spd-should-you-upgrade\/\" target=\"_blank\" rel=\"noopener noreferrer\">1000V vs 1500V DC SPD<\/a>. For sites in high lightning-density regions, a higher nominal current device like the <a style=\"color: #009292; text-decoration: underline;\" href=\"https:\/\/www.britecelectric.com\/tr\/product\/brpv3-1000-20-1000v-20ka-t12-pv-surge-arrester\/\" target=\"_blank\" rel=\"noopener noreferrer\">BRPV3-1000-20 Type 1+2 PV surge arrester (20 kA)<\/a> gives extra margin.<\/p>\r\n<p style=\"text-align: center; margin: 18px 0;\"><a href=\"https:\/\/www.britecelectric.com\/tr\/product\/brpv3-1000-20-1000v-20ka-t12-pv-surge-arrester\/\" target=\"_blank\" rel=\"noopener noreferrer\"><img style=\"max-width: 320px; height: auto; border: 1px solid #e3e8ef; border-radius: 6px; padding: 6px; background: #ffffff;\" src=\"https:\/\/www.britecelectric.com\/wp-content\/uploads\/2026\/09\/BRPV3-1000-20.webp\" alt=\"BRPV3-1000-20 1000V Type 1+2 PV surge arrester for solar SPD\" \/><\/a><\/p>\r\n<p style=\"margin: 22px 0; font-family: Arial,Helvetica,sans-serif; font-size: 16px; line-height: 1.8; color: #ffffff; background: #009292; border-radius: 8px; padding: 20px 24px; text-align: center;\"><strong style=\"font-size: 18px; color: #ffffff;\">Not sure which voltage class or Type fits your array?<\/strong>\r\nSend us your string open-circuit voltage, lightning zone and box layout \u2014 our engineers will size the right T1+T2 device.\r\n<a style=\"display: inline-block; margin-top: 12px; background: #ffffff; color: #009292; text-decoration: none; font-weight: bold; padding: 10px 22px; border-radius: 6px;\" href=\"https:\/\/www.britecelectric.com\/tr\/contact-us\/\" target=\"_blank\" rel=\"noopener noreferrer\">Talk to a Britec engineer<\/a><\/p>\r\n\r\n<h2 style=\"font-family: Arial,Helvetica,sans-serif; font-size: 24px; color: #1a1a1a; margin: 28px 0 12px 0; border-bottom: 2px solid #009292; padding-bottom: 6px;\">Pairing the SPD With a Dedicated Backup Protector (SCB)<\/h2>\r\n<p style=\"margin: 0 0 18px 0; font-family: Arial,Helvetica,sans-serif; font-size: 16px; line-height: 1.8; color: #333333;\">An SPD can become a short circuit at end of life or after a heavy surge, so the combiner box needs a backup protective device (Surge Protective Device Circuit Breaker, SCB) in series with the SPD. The SCB must be coordinated so it does not trip on normal SPD leakage current yet clears a fault quickly. Position the SCB on the incoming feeder to the SPD, before the SPD connection to the bus. Proper coordination is covered in our guide to <a style=\"color: #009292; text-decoration: underline;\" href=\"https:\/\/www.britecelectric.com\/tr\/blog\/dc-type-2-spd-coordination-with-dc-circuit-breakers\/\" target=\"_blank\" rel=\"noopener noreferrer\">DC Type 2 SPD coordination with DC circuit breakers<\/a>.<\/p>\r\n\r\n<h2 style=\"font-family: Arial,Helvetica,sans-serif; font-size: 24px; color: #1a1a1a; margin: 28px 0 12px 0; border-bottom: 2px solid #009292; padding-bottom: 6px;\">Common Installation Mistakes to Avoid<\/h2>\r\n<p style=\"margin: 0 0 6px 0; font-family: Arial,Helvetica,sans-serif; font-size: 16px; line-height: 1.8; color: #333333;\">\u25cf Installing the SPD only at the inverter and leaving the long array string unprotected.<\/p>\r\n<p style=\"margin: 0 0 6px 0; font-family: Arial,Helvetica,sans-serif; font-size: 16px; line-height: 1.8; color: #333333;\">\u25cf Running long, looped SPD leads \u2014 inductance then defeats the protection level.<\/p>\r\n<p style=\"margin: 0 0 6px 0; font-family: Arial,Helvetica,sans-serif; font-size: 16px; line-height: 1.8; color: #333333;\">\u25cf Using an AC-rated SPD instead of an IEC 61643-31 DC\/PV device.<\/p>\r\n<p style=\"margin: 0 0 6px 0; font-family: Arial,Helvetica,sans-serif; font-size: 16px; line-height: 1.8; color: #333333;\">\u25cf Picking a voltage class below the array open-circuit voltage (e.g. a 1000 V SPD on a 1500 V string).<\/p>\r\n<p style=\"margin: 0 0 6px 0; font-family: Arial,Helvetica,sans-serif; font-size: 16px; line-height: 1.8; color: #333333;\">\u25cf Forgetting the SCB or sharing the string breaker as the SPD backup.<\/p>\r\n<p style=\"margin: 0 0 18px 0; font-family: Arial,Helvetica,sans-serif; font-size: 16px; line-height: 1.8; color: #333333;\">\u25cf Leaving the SPD earth lead long or bonding it to a painted, high-resistance enclosure surface.<\/p>\r\n\r\n<h2 style=\"font-family: Arial,Helvetica,sans-serif; font-size: 24px; color: #1a1a1a; margin: 28px 0 12px 0; border-bottom: 2px solid #009292; padding-bottom: 6px;\">Quick Installation Position Checklist<\/h2>\r\n<table style=\"border-collapse: collapse; width: 100%; font-family: Arial,Helvetica,sans-serif; font-size: 15px; margin: 10px 0 18px 0; color: #333333;\">\r\n<thead>\r\n<tr style=\"background: #009292; color: #ffffff;\">\r\n<th style=\"border: 1px solid #e3e8ef; padding: 10px 12px; text-align: left;\">Check item<\/th>\r\n<th style=\"border: 1px solid #e3e8ef; padding: 10px 12px; text-align: left;\">Pass criteria<\/th>\r\n<\/tr>\r\n<\/thead>\r\n<tbody>\r\n<tr style=\"background: #f4fbfb;\">\r\n<td style=\"border: 1px solid #e3e8ef; padding: 10px 12px;\">Mounting point<\/td>\r\n<td style=\"border: 1px solid #e3e8ef; padding: 10px 12px;\">On + \/ \u2212 DC busbar, array side of output<\/td>\r\n<\/tr>\r\n<tr>\r\n<td style=\"border: 1px solid #e3e8ef; padding: 10px 12px;\">Kur\u015fun uzunlu\u011fu<\/td>\r\n<td style=\"border: 1px solid #e3e8ef; padding: 10px 12px;\">\u2264 0.5 m from busbar to SPD<\/td>\r\n<\/tr>\r\n<tr style=\"background: #f4fbfb;\">\r\n<td style=\"border: 1px solid #e3e8ef; padding: 10px 12px;\">Earth bond<\/td>\r\n<td style=\"border: 1px solid #e3e8ef; padding: 10px 12px;\">Direct, low-impedance to enclosure earth bar<\/td>\r\n<\/tr>\r\n<tr>\r\n<td style=\"border: 1px solid #e3e8ef; padding: 10px 12px;\">Type &amp; voltage<\/td>\r\n<td style=\"border: 1px solid #e3e8ef; padding: 10px 12px;\">T1+T2, Ucpv \u2265 array Voc<\/td>\r\n<\/tr>\r\n<tr style=\"background: #f4fbfb;\">\r\n<td style=\"border: 1px solid #e3e8ef; padding: 10px 12px;\">Backup<\/td>\r\n<td style=\"border: 1px solid #e3e8ef; padding: 10px 12px;\">Coordinated SCB in series with SPD<\/td>\r\n<\/tr>\r\n<\/tbody>\r\n<\/table>\r\n<h2 style=\"font-family: Arial,Helvetica,sans-serif; font-size: 24px; color: #1a1a1a; margin: 28px 0 12px 0; border-bottom: 2px solid #009292; padding-bottom: 6px;\">S\u0131k sorulan sorular<\/h2>\r\n<p style=\"margin: 16px 0 4px 0; font-family: Arial,Helvetica,sans-serif; font-size: 17px; font-weight: bold; color: #1a1a1a;\">1. Can I install the solar SPD at the inverter instead of the combiner box?<\/p>\r\n<p style=\"margin: 0 0 18px 0; font-family: Arial,Helvetica,sans-serif; font-size: 16px; line-height: 1.8; color: #333333;\">You can, but it is not ideal. Mounting at the combiner box clamps the surge at the point where the long, exposed array wiring enters the system, giving the shortest protected run. An inverter-only SPD leaves the entire string length unprotected. Best practice is an SPD at the combiner box, with a second coordinated stage at the inverter if the design requires it.<\/p>\r\n<p style=\"margin: 16px 0 4px 0; font-family: Arial,Helvetica,sans-serif; font-size: 17px; font-weight: bold; color: #1a1a1a;\">2. Should the SPD go on the input or output side of the combiner box?<\/p>\r\n<p style=\"margin: 0 0 18px 0; font-family: Arial,Helvetica,sans-serif; font-size: 16px; line-height: 1.8; color: #333333;\">Always on the incoming (array \/ string) side, connected across the DC busbar before the output terminal that feeds the inverter. This way every string is protected before its energy reaches the common bus and the inverter feed.<\/p>\r\n<p style=\"margin: 16px 0 4px 0; font-family: Arial,Helvetica,sans-serif; font-size: 17px; font-weight: bold; color: #1a1a1a;\">3. How long can the SPD leads be?<\/p>\r\n<p style=\"margin: 0 0 18px 0; font-family: Arial,Helvetica,sans-serif; font-size: 16px; line-height: 1.8; color: #333333;\">Keep the total lead length from the DC busbar to the SPD at or below 0.5 m, with equal-length live and earth conductors. Longer leads add inductance that raises the let-through voltage and undermines the rated protection level.<\/p>\r\n<p style=\"margin: 16px 0 4px 0; font-family: Arial,Helvetica,sans-serif; font-size: 17px; font-weight: bold; color: #1a1a1a;\">4. What Type of SPD do I need in a PV combiner box?<\/p>\r\n<p style=\"margin: 0 0 18px 0; font-family: Arial,Helvetica,sans-serif; font-size: 16px; line-height: 1.8; color: #333333;\">For most combiner boxes a Type 1+2 (T1+T2) device per IEC\/EN 61643-31 is recommended because it handles both direct lightning partial current and induced surges. A Type 2 alone is acceptable only when a Type 1 device is already installed upstream.<\/p>\r\n<p style=\"margin: 16px 0 4px 0; font-family: Arial,Helvetica,sans-serif; font-size: 17px; font-weight: bold; color: #1a1a1a;\">5. Does the SPD voltage rating have to match the array voltage?<\/p>\r\n<p style=\"margin: 0 0 18px 0; font-family: Arial,Helvetica,sans-serif; font-size: 16px; line-height: 1.8; color: #333333;\">Yes. The SPD\u2019s maximum continuous operating voltage (Ucpv) must equal or exceed the array\u2019s maximum open-circuit voltage \u2014 1000 V systems use a 1000 V-class device, 1500 V strings need a 1500 V-class device. Underrating causes premature failure.<\/p>\r\n<p style=\"margin: 16px 0 4px 0; font-family: Arial,Helvetica,sans-serif; font-size: 17px; font-weight: bold; color: #1a1a1a;\">6. Is a backup breaker required for the combiner-box SPD?<\/p>\r\n<p style=\"margin: 0 0 18px 0; font-family: Arial,Helvetica,sans-serif; font-size: 16px; line-height: 1.8; color: #333333;\">Yes. A coordinated Surge Protective Device Circuit Breaker (SCB) in series with the SPD clears a fault if the SPD fails short, without tripping on normal leakage. Do not simply share the string breaker as the SPD backup.<\/p>\r\n<p style=\"margin: 22px 0; font-family: Arial,Helvetica,sans-serif; font-size: 16px; line-height: 1.8; color: #ffffff; background: #009292; border-radius: 8px; padding: 20px 24px; text-align: center;\"><strong style=\"font-size: 18px; color: #ffffff;\">Build a safer PV combiner box with Britec<\/strong>\r\nGet datasheets, wiring diagrams and sample units for your next solar project.\r\n<a style=\"display: inline-block; margin-top: 12px; background: #ffffff; color: #009292; text-decoration: none; font-weight: bold; padding: 10px 22px; border-radius: 6px;\" href=\"https:\/\/www.britecelectric.com\/tr\/contact-us\/\" target=\"_blank\" rel=\"noopener noreferrer\">Contact Britec Electric<\/a><\/p>\r\n\r\n<h2 style=\"font-family: Arial,Helvetica,sans-serif; font-size: 24px; color: #1a1a1a; margin: 28px 0 12px 0; border-bottom: 2px solid #009292; padding-bottom: 6px;\">Related Resources<\/h2>\r\n<p style=\"margin: 0 0 6px 0; font-family: Arial,Helvetica,sans-serif; font-size: 16px; line-height: 1.8; color: #333333;\">\u25cf <a style=\"color: #009292; text-decoration: underline;\" href=\"https:\/\/www.britecelectric.com\/tr\/blog\/electrical-spd-for-solar-pv-systems-do-you-really-need-it\/\" target=\"_blank\" rel=\"noopener noreferrer\">Do You Really Need an SPD for Solar PV Systems?<\/a><\/p>\r\n<p style=\"margin: 0 0 6px 0; font-family: Arial,Helvetica,sans-serif; font-size: 16px; line-height: 1.8; color: #333333;\">\u25cf <a style=\"color: #009292; text-decoration: underline;\" href=\"https:\/\/www.britecelectric.com\/tr\/blog\/type-1-vs-1-2-vs-2-vs-3-dc-spd-which-to-choose\/\" target=\"_blank\" rel=\"noopener noreferrer\">Type 1 vs 1+2 vs 2 vs 3 DC SPD \u2014 Which to Choose<\/a><\/p>\r\n<p style=\"margin: 0 0 6px 0; font-family: Arial,Helvetica,sans-serif; font-size: 16px; line-height: 1.8; color: #333333;\">\u25cf <a style=\"color: #009292; text-decoration: underline;\" href=\"https:\/\/www.britecelectric.com\/tr\/blog\/1500v-vs-1000v-dc-spd-should-you-upgrade\/\" target=\"_blank\" rel=\"noopener noreferrer\">1000V vs 1500V DC SPD \u2014 Should You Upgrade?<\/a><\/p>\r\n<p style=\"margin: 0 0 6px 0; font-family: Arial,Helvetica,sans-serif; font-size: 16px; line-height: 1.8; color: #333333;\">\u25cf <a style=\"color: #009292; text-decoration: underline;\" href=\"https:\/\/www.britecelectric.com\/tr\/blog\/dc-type-2-spd-coordination-with-dc-circuit-breakers\/\" target=\"_blank\" rel=\"noopener noreferrer\">DC Type 2 SPD Coordination With DC Circuit Breakers<\/a><\/p>\r\n<p style=\"margin: 0 0 6px 0; font-family: Arial,Helvetica,sans-serif; font-size: 16px; line-height: 1.8; color: #333333;\">\u25cf <a style=\"color: #009292; text-decoration: underline;\" href=\"https:\/\/www.britecelectric.com\/tr\/blog\/surge-protection-for-photovoltaic-systems\/\" target=\"_blank\" rel=\"noopener noreferrer\">Surge Protection for Photovoltaic Systems<\/a><\/p>","protected":false},"featured_media":2655,"parent":0,"menu_order":10,"template":"","meta":{"_acf_changed":false},"blog_category":[9],"class_list":["post-2700","blog","type-blog","status-publish","has-post-thumbnail","hentry","blog_category-industry-news"],"acf":{"des":"A practical, EEAT-backed guide to installing a solar SPD inside a PV combiner box - correct busbar position, short lead-length wiring, equipotential bonding, Type 1+2 selection and 1000V\/1500V rating for safer PV arrays.","txt":"<p style=\"margin: 0 0 18px 0; font-family: Arial,Helvetica,sans-serif; font-size: 16px; line-height: 1.8; color: #333333;\">By the Britec Electric engineering team \u2014 Britec Electric (Wenzhou, Zhejiang, China) has manufactured IEC\/EN 61643 surge protective devices since 2003, with products certified by T\u00dcV, CE and Intertek SEMKO and an ISO 9001 quality system. This guide explains, from a PV system designer\u2019s perspective, exactly where a solar SPD should be mounted inside a PV combiner box and why that position determines how much lightning and switching-surge energy actually gets diverted before it reaches the inverter.<\/p>\r\n\r\n<h2 style=\"font-family: Arial,Helvetica,sans-serif; font-size: 24px; color: #1a1a1a; margin: 28px 0 12px 0; border-bottom: 2px solid #009292; padding-bottom: 6px;\">Why the PV Combiner Box Is the Correct Location for a Solar SPD<\/h2>\r\n<p style=\"margin: 0 0 18px 0; font-family: Arial,Helvetica,sans-serif; font-size: 16px; line-height: 1.8; color: #333333;\">A PV combiner box sits between the PV string cabling and the inverter. It aggregates the output of several DC strings through fuses or circuit breakers onto a common DC busbar, then feeds the inverter. The array cabling is the longest, most exposed part of the system \u2014 metres of conductor run across rooftops and open ground, acting as an antenna for induced lightning overvoltage. If you only protect the inverter input, the surge has already travelled the full string length unchecked.<\/p>\r\n<p style=\"margin: 0 0 18px 0; font-family: Arial,Helvetica,sans-serif; font-size: 16px; line-height: 1.8; color: #333333;\">Placing a dedicated DC SPD at the combiner box gives the first and best clamping point: it intercepts the overvoltage right where the exposed array wiring enters the protected zone. For a deeper look at whether a PV system needs surge protection at all, see our guide on <a style=\"color: #009292; text-decoration: underline;\" href=\"https:\/\/www.britecelectric.com\/blog\/electrical-spd-for-solar-pv-systems-do-you-really-need-it\/\" target=\"_blank\" rel=\"noopener noreferrer\">whether you really need an SPD for solar PV systems<\/a>.<\/p>\r\n<p style=\"margin: 0 0 18px 0; font-family: Arial,Helvetica,sans-serif; font-size: 16px; line-height: 1.8; color: #333333;\">The goal is simple: divert the surge to earth as close as possible to the point where the string conductors enter the box, with the shortest possible SPD lead length.<\/p>\r\n\r\n<h2 style=\"font-family: Arial,Helvetica,sans-serif; font-size: 24px; color: #1a1a1a; margin: 28px 0 12px 0; border-bottom: 2px solid #009292; padding-bottom: 6px;\">Where Exactly to Mount the SPD Inside the Combiner Box<\/h2>\r\n<p style=\"margin: 0 0 18px 0; font-family: Arial,Helvetica,sans-serif; font-size: 16px; line-height: 1.8; color: #333333;\">The SPD must be connected in parallel across the DC bus, on the incoming (array) side of the combiner \u2014 not on the outgoing inverter side. Follow this physical order from the cable entry inward:<\/p>\r\n<p style=\"margin: 0 0 6px 0; font-family: Arial,Helvetica,sans-serif; font-size: 16px; line-height: 1.8; color: #333333;\">\u25cf Mount the SPD directly on the positive and negative DC busbar, between the string fuses\/breakers and the combiner output terminal.<\/p>\r\n<p style=\"margin: 0 0 6px 0; font-family: Arial,Helvetica,sans-serif; font-size: 16px; line-height: 1.8; color: #333333;\">\u25cf Position it as close as physically possible to the incoming string terminals \u2014 ideally within 0.5 m of lead length from the busbar to the SPD.<\/p>\r\n<p style=\"margin: 0 0 6px 0; font-family: Arial,Helvetica,sans-serif; font-size: 16px; line-height: 1.8; color: #333333;\">\u25cf Install it on the array side so every string is protected before its current reaches the common bus and the inverter feed.<\/p>\r\n<p style=\"margin: 0 0 6px 0; font-family: Arial,Helvetica,sans-serif; font-size: 16px; line-height: 1.8; color: #333333;\">\u25cf Keep the SPD away from the enclosure door and any moving parts; DIN-rail mount it on the same rail as the string breakers for a short, clean connection.<\/p>\r\n<p style=\"margin: 0 0 18px 0; font-family: Arial,Helvetica,sans-serif; font-size: 16px; line-height: 1.8; color: #333333;\">\u25cf For a multi-string box, one Type 1+2 SPD across the main + \/ \u2212 bus is normally sufficient; do not fit a separate SPD per string unless the design calls for it.<\/p>\r\n<p style=\"margin: 0 0 18px 0; font-family: Arial,Helvetica,sans-serif; font-size: 16px; line-height: 1.8; color: #333333;\">In practice the SPD is the last device the incoming surge meets before the busbar. That placement is what limits the let-through voltage (Up) seen by the inverter and the DC isolator downstream.<\/p>\r\n<p style=\"margin: 22px 0; font-family: Arial,Helvetica,sans-serif; font-size: 16px; line-height: 1.8; color: #ffffff; background: #009292; border-radius: 8px; padding: 20px 24px; text-align: center;\"><strong style=\"font-size: 18px; color: #ffffff;\">Specifying SPDs for your PV combiner boxes?<\/strong>\r\nBritec supplies IEC 61643-31 Type 1+2 DC SPDs in 1000 V and 1500 V classes, with DIN-rail modules and remote-signal options for panel builders.\r\n<a style=\"display: inline-block; margin-top: 12px; background: #ffffff; color: #009292; text-decoration: none; font-weight: bold; padding: 10px 22px; border-radius: 6px;\" href=\"https:\/\/www.britecelectric.com\/contact-us\/\" target=\"_blank\" rel=\"noopener noreferrer\">Request a combiner-box SPD quote<\/a><\/p>\r\n\r\n<h2 style=\"font-family: Arial,Helvetica,sans-serif; font-size: 24px; color: #1a1a1a; margin: 28px 0 12px 0; border-bottom: 2px solid #009292; padding-bottom: 6px;\">Wiring and Equipotential Bonding Rules<\/h2>\r\n<p style=\"margin: 0 0 18px 0; font-family: Arial,Helvetica,sans-serif; font-size: 16px; line-height: 1.8; color: #333333;\">Correct position is only half the story \u2014 the wiring determines whether the SPD actually performs. Inductance in the leads is the enemy: every extra centimetre of conductor lets the surge overshoot the rated protection level.<\/p>\r\n<p style=\"margin: 0 0 6px 0; font-family: Arial,Helvetica,sans-serif; font-size: 16px; line-height: 1.8; color: #333333;\">\u25cf Use the shortest possible connection from the SPD terminals to the DC busbar; keep both the live and the protective-earth leads short and equal in length.<\/p>\r\n<p style=\"margin: 0 0 6px 0; font-family: Arial,Helvetica,sans-serif; font-size: 16px; line-height: 1.8; color: #333333;\">\u25cf Bond the SPD\u2019s earthing terminal to the combiner box chassis and the site earth bar with a low-impedance, direct conductor \u2014 never share a long daisy-chained earth path.<\/p>\r\n<p style=\"margin: 0 0 6px 0; font-family: Arial,Helvetica,sans-serif; font-size: 16px; line-height: 1.8; color: #333333;\">\u25cf Keep the SPD earth lead separate from the DC power leads and route it straight to the enclosure earth point.<\/p>\r\n<p style=\"margin: 0 0 18px 0; font-family: Arial,Helvetica,sans-serif; font-size: 16px; line-height: 1.8; color: #333333;\">\u25cf Verify the enclosure itself is bonded to the PV system earthing electrode conductor so the diverted current has a low-resistance path to earth.<\/p>\r\n<p style=\"text-align: center; margin: 18px 0;\"><a href=\"https:\/\/www.britecelectric.com\/product\/brpv3-1500-12-5-t1t2-1500v-12-5ka-pv-surge-protection-device\/\" target=\"_blank\" rel=\"noopener noreferrer\"><img style=\"max-width: 320px; height: auto; border: 1px solid #e3e8ef; border-radius: 6px; padding: 6px; background: #ffffff;\" src=\"https:\/\/www.britecelectric.com\/wp-content\/uploads\/2026\/09\/BRPV3-1500-12.5.webp\" alt=\"BRPV3-1500-12.5 1500V T1+T2 PV surge arrester for solar SPD\" \/><\/a><\/p>\r\n\r\n<h2 style=\"font-family: Arial,Helvetica,sans-serif; font-size: 24px; color: #1a1a1a; margin: 28px 0 12px 0; border-bottom: 2px solid #009292; padding-bottom: 6px;\">Selecting the Right DC SPD Type and Voltage Rating<\/h2>\r\n<p style=\"margin: 0 0 18px 0; font-family: Arial,Helvetica,sans-serif; font-size: 16px; line-height: 1.8; color: #333333;\">A solar SPD inside a combiner box must comply with IEC\/EN 61643-31 (PV applications) and match the system\u2019s open-circuit voltage. Two decisions matter most: the Type and the voltage class.<\/p>\r\n<p style=\"margin: 0 0 18px 0; font-family: Arial,Helvetica,sans-serif; font-size: 16px; line-height: 1.8; color: #333333;\"><strong style=\"color: #1a1a1a;\">Type:<\/strong> For a combiner box exposed to both direct and indirect lightning, a Type 1+2 (T1+T2) device is the safest choice because it handles the partial lightning current (10\/350 \u00b5s) and the induced surge. A pure Type 2 is acceptable only where an upstream T1 already exists. If you are unsure which Type your site needs, our comparison of <a style=\"color: #009292; text-decoration: underline;\" href=\"https:\/\/www.britecelectric.com\/blog\/type-1-vs-1-2-vs-2-vs-3-dc-spd-which-to-choose\/\" target=\"_blank\" rel=\"noopener noreferrer\">Type 1, Type 1+2, Type 2 and Type 3 DC SPDs<\/a> breaks it down by application.<\/p>\r\n<p style=\"margin: 0 0 18px 0; font-family: Arial,Helvetica,sans-serif; font-size: 16px; line-height: 1.8; color: #333333;\"><strong style=\"color: #1a1a1a;\">Voltage rating:<\/strong> Match Ucpv to the array\u2019s maximum open-circuit voltage. For a 1000 V system the <a style=\"color: #009292; text-decoration: underline;\" href=\"https:\/\/www.britecelectric.com\/product\/brpv3-1000-type-2-surge-protection-device-for-pv-upto-1000v\/\" target=\"_blank\" rel=\"noopener noreferrer\">BRPV3-1000 Type 2 PV surge arrester<\/a> is the standard fit, while 1500 V arrays need a 1500 V-class device such as the <a style=\"color: #009292; text-decoration: underline;\" href=\"https:\/\/www.britecelectric.com\/product\/brpv3-1500-12-5-t1t2-1500v-12-5ka-pv-surge-protection-device\/\" target=\"_blank\" rel=\"noopener noreferrer\">BRPV3-1500-12.5 T1+T2 PV surge arrester<\/a>. The choice between the two voltage classes affects let-through and cost \u2014 see our post on <a style=\"color: #009292; text-decoration: underline;\" href=\"https:\/\/www.britecelectric.com\/blog\/1500v-vs-1000v-dc-spd-should-you-upgrade\/\" target=\"_blank\" rel=\"noopener noreferrer\">1000V vs 1500V DC SPD<\/a>. For sites in high lightning-density regions, a higher nominal current device like the <a style=\"color: #009292; text-decoration: underline;\" href=\"https:\/\/www.britecelectric.com\/product\/brpv3-1000-20-1000v-20ka-t12-pv-surge-arrester\/\" target=\"_blank\" rel=\"noopener noreferrer\">BRPV3-1000-20 Type 1+2 PV surge arrester (20 kA)<\/a> gives extra margin.<\/p>\r\n<p style=\"text-align: center; margin: 18px 0;\"><a href=\"https:\/\/www.britecelectric.com\/product\/brpv3-1000-20-1000v-20ka-t12-pv-surge-arrester\/\" target=\"_blank\" rel=\"noopener noreferrer\"><img style=\"max-width: 320px; height: auto; border: 1px solid #e3e8ef; border-radius: 6px; padding: 6px; background: #ffffff;\" src=\"https:\/\/www.britecelectric.com\/wp-content\/uploads\/2026\/09\/BRPV3-1000-20.webp\" alt=\"BRPV3-1000-20 1000V Type 1+2 PV surge arrester for solar SPD\" \/><\/a><\/p>\r\n<p style=\"margin: 22px 0; font-family: Arial,Helvetica,sans-serif; font-size: 16px; line-height: 1.8; color: #ffffff; background: #009292; border-radius: 8px; padding: 20px 24px; text-align: center;\"><strong style=\"font-size: 18px; color: #ffffff;\">Not sure which voltage class or Type fits your array?<\/strong>\r\nSend us your string open-circuit voltage, lightning zone and box layout \u2014 our engineers will size the right T1+T2 device.\r\n<a style=\"display: inline-block; margin-top: 12px; background: #ffffff; color: #009292; text-decoration: none; font-weight: bold; padding: 10px 22px; border-radius: 6px;\" href=\"https:\/\/www.britecelectric.com\/contact-us\/\" target=\"_blank\" rel=\"noopener noreferrer\">Talk to a Britec engineer<\/a><\/p>\r\n\r\n<h2 style=\"font-family: Arial,Helvetica,sans-serif; font-size: 24px; color: #1a1a1a; margin: 28px 0 12px 0; border-bottom: 2px solid #009292; padding-bottom: 6px;\">Pairing the SPD With a Dedicated Backup Protector (SCB)<\/h2>\r\n<p style=\"margin: 0 0 18px 0; font-family: Arial,Helvetica,sans-serif; font-size: 16px; line-height: 1.8; color: #333333;\">An SPD can become a short circuit at end of life or after a heavy surge, so the combiner box needs a backup protective device (Surge Protective Device Circuit Breaker, SCB) in series with the SPD. The SCB must be coordinated so it does not trip on normal SPD leakage current yet clears a fault quickly. Position the SCB on the incoming feeder to the SPD, before the SPD connection to the bus. Proper coordination is covered in our guide to <a style=\"color: #009292; text-decoration: underline;\" href=\"https:\/\/www.britecelectric.com\/blog\/dc-type-2-spd-coordination-with-dc-circuit-breakers\/\" target=\"_blank\" rel=\"noopener noreferrer\">DC Type 2 SPD coordination with DC circuit breakers<\/a>.<\/p>\r\n\r\n<h2 style=\"font-family: Arial,Helvetica,sans-serif; font-size: 24px; color: #1a1a1a; margin: 28px 0 12px 0; border-bottom: 2px solid #009292; padding-bottom: 6px;\">Common Installation Mistakes to Avoid<\/h2>\r\n<p style=\"margin: 0 0 6px 0; font-family: Arial,Helvetica,sans-serif; font-size: 16px; line-height: 1.8; color: #333333;\">\u25cf Installing the SPD only at the inverter and leaving the long array string unprotected.<\/p>\r\n<p style=\"margin: 0 0 6px 0; font-family: Arial,Helvetica,sans-serif; font-size: 16px; line-height: 1.8; color: #333333;\">\u25cf Running long, looped SPD leads \u2014 inductance then defeats the protection level.<\/p>\r\n<p style=\"margin: 0 0 6px 0; font-family: Arial,Helvetica,sans-serif; font-size: 16px; line-height: 1.8; color: #333333;\">\u25cf Using an AC-rated SPD instead of an IEC 61643-31 DC\/PV device.<\/p>\r\n<p style=\"margin: 0 0 6px 0; font-family: Arial,Helvetica,sans-serif; font-size: 16px; line-height: 1.8; color: #333333;\">\u25cf Picking a voltage class below the array open-circuit voltage (e.g. a 1000 V SPD on a 1500 V string).<\/p>\r\n<p style=\"margin: 0 0 6px 0; font-family: Arial,Helvetica,sans-serif; font-size: 16px; line-height: 1.8; color: #333333;\">\u25cf Forgetting the SCB or sharing the string breaker as the SPD backup.<\/p>\r\n<p style=\"margin: 0 0 18px 0; font-family: Arial,Helvetica,sans-serif; font-size: 16px; line-height: 1.8; color: #333333;\">\u25cf Leaving the SPD earth lead long or bonding it to a painted, high-resistance enclosure surface.<\/p>\r\n\r\n<h2 style=\"font-family: Arial,Helvetica,sans-serif; font-size: 24px; color: #1a1a1a; margin: 28px 0 12px 0; border-bottom: 2px solid #009292; padding-bottom: 6px;\">Quick Installation Position Checklist<\/h2>\r\n<table style=\"border-collapse: collapse; width: 100%; font-family: Arial,Helvetica,sans-serif; font-size: 15px; margin: 10px 0 18px 0; color: #333333;\">\r\n<thead>\r\n<tr style=\"background: #009292; color: #ffffff;\">\r\n<th style=\"border: 1px solid #e3e8ef; padding: 10px 12px; text-align: left;\">Check item<\/th>\r\n<th style=\"border: 1px solid #e3e8ef; padding: 10px 12px; text-align: left;\">Pass criteria<\/th>\r\n<\/tr>\r\n<\/thead>\r\n<tbody>\r\n<tr style=\"background: #f4fbfb;\">\r\n<td style=\"border: 1px solid #e3e8ef; padding: 10px 12px;\">Mounting point<\/td>\r\n<td style=\"border: 1px solid #e3e8ef; padding: 10px 12px;\">On + \/ \u2212 DC busbar, array side of output<\/td>\r\n<\/tr>\r\n<tr>\r\n<td style=\"border: 1px solid #e3e8ef; padding: 10px 12px;\">Lead length<\/td>\r\n<td style=\"border: 1px solid #e3e8ef; padding: 10px 12px;\">\u2264 0.5 m from busbar to SPD<\/td>\r\n<\/tr>\r\n<tr style=\"background: #f4fbfb;\">\r\n<td style=\"border: 1px solid #e3e8ef; padding: 10px 12px;\">Earth bond<\/td>\r\n<td style=\"border: 1px solid #e3e8ef; padding: 10px 12px;\">Direct, low-impedance to enclosure earth bar<\/td>\r\n<\/tr>\r\n<tr>\r\n<td style=\"border: 1px solid #e3e8ef; padding: 10px 12px;\">Type &amp; voltage<\/td>\r\n<td style=\"border: 1px solid #e3e8ef; padding: 10px 12px;\">T1+T2, Ucpv \u2265 array Voc<\/td>\r\n<\/tr>\r\n<tr style=\"background: #f4fbfb;\">\r\n<td style=\"border: 1px solid #e3e8ef; padding: 10px 12px;\">Backup<\/td>\r\n<td style=\"border: 1px solid #e3e8ef; padding: 10px 12px;\">Coordinated SCB in series with SPD<\/td>\r\n<\/tr>\r\n<\/tbody>\r\n<\/table>\r\n<h2 style=\"font-family: Arial,Helvetica,sans-serif; font-size: 24px; color: #1a1a1a; margin: 28px 0 12px 0; border-bottom: 2px solid #009292; padding-bottom: 6px;\">Frequently Asked Questions<\/h2>\r\n<p style=\"margin: 16px 0 4px 0; font-family: Arial,Helvetica,sans-serif; font-size: 17px; font-weight: bold; color: #1a1a1a;\">1. Can I install the solar SPD at the inverter instead of the combiner box?<\/p>\r\n<p style=\"margin: 0 0 18px 0; font-family: Arial,Helvetica,sans-serif; font-size: 16px; line-height: 1.8; color: #333333;\">You can, but it is not ideal. Mounting at the combiner box clamps the surge at the point where the long, exposed array wiring enters the system, giving the shortest protected run. An inverter-only SPD leaves the entire string length unprotected. Best practice is an SPD at the combiner box, with a second coordinated stage at the inverter if the design requires it.<\/p>\r\n<p style=\"margin: 16px 0 4px 0; font-family: Arial,Helvetica,sans-serif; font-size: 17px; font-weight: bold; color: #1a1a1a;\">2. Should the SPD go on the input or output side of the combiner box?<\/p>\r\n<p style=\"margin: 0 0 18px 0; font-family: Arial,Helvetica,sans-serif; font-size: 16px; line-height: 1.8; color: #333333;\">Always on the incoming (array \/ string) side, connected across the DC busbar before the output terminal that feeds the inverter. This way every string is protected before its energy reaches the common bus and the inverter feed.<\/p>\r\n<p style=\"margin: 16px 0 4px 0; font-family: Arial,Helvetica,sans-serif; font-size: 17px; font-weight: bold; color: #1a1a1a;\">3. How long can the SPD leads be?<\/p>\r\n<p style=\"margin: 0 0 18px 0; font-family: Arial,Helvetica,sans-serif; font-size: 16px; line-height: 1.8; color: #333333;\">Keep the total lead length from the DC busbar to the SPD at or below 0.5 m, with equal-length live and earth conductors. Longer leads add inductance that raises the let-through voltage and undermines the rated protection level.<\/p>\r\n<p style=\"margin: 16px 0 4px 0; font-family: Arial,Helvetica,sans-serif; font-size: 17px; font-weight: bold; color: #1a1a1a;\">4. What Type of SPD do I need in a PV combiner box?<\/p>\r\n<p style=\"margin: 0 0 18px 0; font-family: Arial,Helvetica,sans-serif; font-size: 16px; line-height: 1.8; color: #333333;\">For most combiner boxes a Type 1+2 (T1+T2) device per IEC\/EN 61643-31 is recommended because it handles both direct lightning partial current and induced surges. A Type 2 alone is acceptable only when a Type 1 device is already installed upstream.<\/p>\r\n<p style=\"margin: 16px 0 4px 0; font-family: Arial,Helvetica,sans-serif; font-size: 17px; font-weight: bold; color: #1a1a1a;\">5. Does the SPD voltage rating have to match the array voltage?<\/p>\r\n<p style=\"margin: 0 0 18px 0; font-family: Arial,Helvetica,sans-serif; font-size: 16px; line-height: 1.8; color: #333333;\">Yes. The SPD\u2019s maximum continuous operating voltage (Ucpv) must equal or exceed the array\u2019s maximum open-circuit voltage \u2014 1000 V systems use a 1000 V-class device, 1500 V strings need a 1500 V-class device. Underrating causes premature failure.<\/p>\r\n<p style=\"margin: 16px 0 4px 0; font-family: Arial,Helvetica,sans-serif; font-size: 17px; font-weight: bold; color: #1a1a1a;\">6. Is a backup breaker required for the combiner-box SPD?<\/p>\r\n<p style=\"margin: 0 0 18px 0; font-family: Arial,Helvetica,sans-serif; font-size: 16px; line-height: 1.8; color: #333333;\">Yes. A coordinated Surge Protective Device Circuit Breaker (SCB) in series with the SPD clears a fault if the SPD fails short, without tripping on normal leakage. Do not simply share the string breaker as the SPD backup.<\/p>\r\n<p style=\"margin: 22px 0; font-family: Arial,Helvetica,sans-serif; font-size: 16px; line-height: 1.8; color: #ffffff; background: #009292; border-radius: 8px; padding: 20px 24px; text-align: center;\"><strong style=\"font-size: 18px; color: #ffffff;\">Build a safer PV combiner box with Britec<\/strong>\r\nGet datasheets, wiring diagrams and sample units for your next solar project.\r\n<a style=\"display: inline-block; margin-top: 12px; background: #ffffff; color: #009292; text-decoration: none; font-weight: bold; padding: 10px 22px; border-radius: 6px;\" href=\"https:\/\/www.britecelectric.com\/contact-us\/\" target=\"_blank\" rel=\"noopener noreferrer\">Contact Britec Electric<\/a><\/p>\r\n\r\n<h2 style=\"font-family: Arial,Helvetica,sans-serif; font-size: 24px; color: #1a1a1a; margin: 28px 0 12px 0; border-bottom: 2px solid #009292; padding-bottom: 6px;\">Related Resources<\/h2>\r\n<p style=\"margin: 0 0 6px 0; font-family: Arial,Helvetica,sans-serif; font-size: 16px; line-height: 1.8; color: #333333;\">\u25cf <a style=\"color: #009292; text-decoration: underline;\" href=\"https:\/\/www.britecelectric.com\/blog\/electrical-spd-for-solar-pv-systems-do-you-really-need-it\/\" target=\"_blank\" rel=\"noopener noreferrer\">Do You Really Need an SPD for Solar PV Systems?<\/a><\/p>\r\n<p style=\"margin: 0 0 6px 0; font-family: Arial,Helvetica,sans-serif; font-size: 16px; line-height: 1.8; color: #333333;\">\u25cf <a style=\"color: #009292; text-decoration: underline;\" href=\"https:\/\/www.britecelectric.com\/blog\/type-1-vs-1-2-vs-2-vs-3-dc-spd-which-to-choose\/\" target=\"_blank\" rel=\"noopener noreferrer\">Type 1 vs 1+2 vs 2 vs 3 DC SPD \u2014 Which to Choose<\/a><\/p>\r\n<p style=\"margin: 0 0 6px 0; font-family: Arial,Helvetica,sans-serif; font-size: 16px; line-height: 1.8; color: #333333;\">\u25cf <a style=\"color: #009292; text-decoration: underline;\" href=\"https:\/\/www.britecelectric.com\/blog\/1500v-vs-1000v-dc-spd-should-you-upgrade\/\" target=\"_blank\" rel=\"noopener noreferrer\">1000V vs 1500V DC SPD \u2014 Should You Upgrade?<\/a><\/p>\r\n<p style=\"margin: 0 0 6px 0; font-family: Arial,Helvetica,sans-serif; font-size: 16px; line-height: 1.8; color: #333333;\">\u25cf <a style=\"color: #009292; text-decoration: underline;\" href=\"https:\/\/www.britecelectric.com\/blog\/dc-type-2-spd-coordination-with-dc-circuit-breakers\/\" target=\"_blank\" rel=\"noopener noreferrer\">DC Type 2 SPD Coordination With DC Circuit Breakers<\/a><\/p>\r\n<p style=\"margin: 0 0 6px 0; font-family: Arial,Helvetica,sans-serif; font-size: 16px; line-height: 1.8; color: #333333;\">\u25cf <a style=\"color: #009292; text-decoration: underline;\" href=\"https:\/\/www.britecelectric.com\/blog\/surge-protection-for-photovoltaic-systems\/\" target=\"_blank\" rel=\"noopener noreferrer\">Surge Protection for Photovoltaic Systems<\/a><\/p>"},"_links":{"self":[{"href":"https:\/\/www.britecelectric.com\/tr\/wp-json\/wp\/v2\/blog\/2700","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/www.britecelectric.com\/tr\/wp-json\/wp\/v2\/blog"}],"about":[{"href":"https:\/\/www.britecelectric.com\/tr\/wp-json\/wp\/v2\/types\/blog"}],"wp:featuredmedia":[{"embeddable":true,"href":"https:\/\/www.britecelectric.com\/tr\/wp-json\/wp\/v2\/media\/2655"}],"wp:attachment":[{"href":"https:\/\/www.britecelectric.com\/tr\/wp-json\/wp\/v2\/media?parent=2700"}],"wp:term":[{"taxonomy":"blog_category","embeddable":true,"href":"https:\/\/www.britecelectric.com\/tr\/wp-json\/wp\/v2\/blog_category?post=2700"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}