{"id":844,"date":"2023-12-18T15:08:31","date_gmt":"2023-12-18T07:08:31","guid":{"rendered":"https:\/\/www.britecelectric.com\/?post_type=blog&#038;p=844"},"modified":"2024-09-05T16:32:04","modified_gmt":"2024-09-05T08:32:04","slug":"lightning-protection-of-low-voltage-power-distribution-system-in-buildings","status":"publish","type":"blog","link":"https:\/\/www.britecelectric.com\/id\/blog\/lightning-protection-of-low-voltage-power-distribution-system-in-buildings\/","title":{"rendered":"Proteksi petir pada sistem distribusi tenaga listrik tegangan rendah pada gedung-gedung"},"content":{"rendered":"Bencana petir terutama mencakup sambaran petir langsung, induksi elektrostatis petir, dan gelombang elektromagnetik petir.\r\n\r\n<strong>Sambaran petir langsung<\/strong>\r\n\r\nSambaran petir langsung mengacu pada fenomena fisik dimana awan petir dilepaskan langsung ke tanah. Jika tanah disambar petir secara langsung, maka akan timbul arus sesaat yang besar di lokasi sambaran petir. Jika arus petir tidak dapat dilepaskan pada waktunya, maka benda yang tersambar petir akan langsung menghasilkan panas yang banyak sehingga menyebabkan benda tersebut memuai, meleleh, terbakar, meledak dan kerusakan lainnya. Biasanya, bangunan harus mempertimbangkan bahayasambaran petir langsung.\r\n\r\n<strong>Induksi elektrostatis petir<\/strong>\r\n\r\nInduksi petir berarti ketika awan petir bermuatan muncul di langit, garis logam, benda logam, dll. di bawah awan petir mengambil muatan listrik yang berlawanan dengan awan petir melalui induksi elektrostatis. Ketika sambaran petir terjadi, muatan awan petir dengan cepat menghilang melalui sambaran petir. Muatan yang diinduksi pada saluran logam merambat sepanjang saluran, menyebabkan tegangan berlebih sementara pada port saluran perangkat. Jika muatan induksi mengenai benda logamtidak dapat hilang pada waktunya, akan terjadi fenomena pelepasan muatan luar yang akan membentuk percikan api.\r\n\r\n<strong>Pulsa elektromagnetik petir<\/strong>\r\n\r\nLightning electromagnetic pulse refers to the instantaneous formation of a lightning electromagnetic field in the area where the lightning strike occurs due to the extremely large peak value and speed of the lightning current. Under the action of the changing lightning electromagnetic field, metal lines in the area induce instantaneous lightning current. If the lightning current penetrates into the power supply line and communication line, transient overvoltage may occur on the device\u2019s line port.\r\n\r\nLightning protection of low-voltage power distribution system is to prevent the low-voltage power distribution system from introducing lightning current from lines outside the building.\r\n\r\n<strong>Langkah-langkah proteksi petir dasar<\/strong>\r\n\r\nUntuk sistem distribusi tenaga listrik tegangan rendah, model dan parameter arester yang umum digunakan adalah sebagai berikut:\r\n\r\n<strong>SPD daya tiga fase Kelas I (untuk sistem TN-S)<\/strong>\r\n\r\nModel: BR-25GR 4P\r\n\r\nMax. continuous operating voltage: 275V~\r\n\r\nLightning impulse current: 25kA (10\/350\u03bcs)\r\n\r\nNominal discharge current: 25kA (8\/20\u03bcs)\r\n\r\nMax. discharge current: 100kA (8\/20\u03bcs)\r\n\r\nMain function: installed in the main power distribution cabinet, as the first-level lightning protection of the power line.\r\n\r\n<strong>SPD daya tiga fase Kelas I (untuk sistem TN-C)<\/strong>\r\n\r\nModel: BR-25GR 3P\r\n\r\nMax. continuous operating voltage: 275V~\r\n\r\nLightning impulse current: 25kA (10\/350\u03bcs)\r\n\r\nNominal discharge current: 25kA (8\/20\u03bcs)\r\n\r\nMax. discharge current: 100kA (8\/20\u03bcs)\r\n\r\nMain function: installed in the main power distribution cabinet, as the first-level lightning protection of the power line.\r\n\r\n<strong>SPD daya tiga fase Kelas I (untuk sistem TT)<\/strong>\r\n\r\nModel: BR-25GR 3P+NPE\r\n\r\nMax. Continuous operating voltage: 275V~\r\n\r\nLightning impulse current: 25Ka\/50kA (10\/350\u03bcs)\r\n\r\nNominal discharge current: 25kA\/50kA (8\/20\u03bcs)\r\n\r\nMax. discharge current: 100kA (8\/20\u03bcs)\r\n\r\nMain function: installed in the main power distribution cabinet, as the first-level lightning protection of the power line.\r\n\r\n<strong>SPD daya tiga fase Kelas II (untuk sistem TN-S atau TN-C-S)<\/strong>\r\n\r\nModel: BR-40 4P\r\n\r\nMax. continuous operating voltage: 275V~\r\n\r\nNominal discharge current: 20kA (8\/20\u03bcs)\r\n\r\nMax. discharge current: 40kA (8\/20\u03bcs)\r\n\r\nMain function: installed in the sub-power distribution box, as the second-level lightning protection of the power line.\r\n\r\n<strong>SPD daya tiga fase Kelas II (untuk sistem TT)<\/strong>\r\n\r\nModel: BR-40 3P+NPE\r\n\r\nMax. continuous operating voltage: 275V~\r\n\r\nNominal discharge current: 20kA (8\/20\u03bcs)\r\n\r\nMax. discharge current: 40kA (8\/20\u03bcs)\r\n\r\nMain function: installed in the sub-power distribution box, as the second-level lightning protection of the power line.\r\n\r\n<strong>Proteksi petir pada sistem distribusi tenaga listrik tegangan rendah adalah sebagai berikut:<\/strong>\r\n\r\nThe main power distribution cabinet of the building is installed with a Class I power SPD as the first-level lightning protection of the power line.\r\n\r\nThe secondary power distribution cabinet (box) of the building is installed with a Class II power SPD as the second-level lightning protection of the power line.\r\n\r\nThe tertiary power distribution cabinet (box) of the building is installed with a Class II power SPD as the third-level lightning protection of the power line.\r\n\r\nFor important equipment ports, install Class III power SPD as terminal-level lightning protection for power lines.","protected":false},"featured_media":845,"parent":0,"menu_order":155,"template":"","meta":{"_acf_changed":false},"blog_category":[8],"class_list":["post-844","blog","type-blog","status-publish","has-post-thumbnail","hentry","blog_category-company-news"],"acf":{"des":"Lightning disasters mainly include direct lightning strikes, lightning electrostatic induction, and lightning electromagnetic pulses.","txt":"Lightning disasters mainly include direct lightning strikes, lightning electrostatic induction, and lightning electromagnetic pulses.\r\n\r\n<strong>Direct lightning strike<\/strong>\r\n\r\nDirect lightning strike refers to the physical phenomenon that the thundercloud discharges directly to the ground. If the ground is directly struck by lightning, a large instantaneous current will be generated at the location of the lightning strike. If the lightning current cannot be released in time, the object struck by the lightning will generate a lot of heat instantly, causing the object to expand, melt, burn, explode and other damage. Typically, buildings must consider the hazards of direct lightning strikes.\r\n\r\n<strong>Lightning electrostatic induction<\/strong>\r\n\r\nLightning induction means that when a charged thundercloud appears in the sky, metal lines, metal objects, etc. under the thundercloud to take on an electric charge opposite to that of a thundercloud by electrostatic induction. When a lightning strike occurs, the thundercloud charge quickly disappears through the lightning strike. The induced charge on the metal line propagates along the line, causing transient overvoltage at the line port of the device. If the induced charge on the metal object cannot disappear in time, there will be an external discharge phenomenon, which will form a spark.\r\n\r\n<strong>Lightning electromagnetic pulse<\/strong>\r\n\r\nLightning electromagnetic pulse refers to the instantaneous formation of a lightning electromagnetic field in the area where the lightning strike occurs due to the extremely large peak value and speed of the lightning current. Under the action of the changing lightning electromagnetic field, metal lines in the area induce instantaneous lightning current. If the lightning current penetrates into the power supply line and communication line, transient overvoltage may occur on the device\u2019s line port.\r\n\r\nLightning protection of low-voltage power distribution system is to prevent the low-voltage power distribution system from introducing lightning current from lines outside the building.\r\n\r\n<strong>Basic lightning protection measures<\/strong>\r\n\r\nFor low-voltage power distribution systems, the commonly used arrester models and parameters are as follows:\r\n\r\n<strong>Class I three-phase power SPD (for TN-S system)<\/strong>\r\n\r\nModel: BR-25GR 4P\r\n\r\nMax. continuous operating voltage: 275V~\r\n\r\nLightning impulse current: 25kA (10\/350\u03bcs)\r\n\r\nNominal discharge current: 25kA (8\/20\u03bcs)\r\n\r\nMax. discharge current: 100kA (8\/20\u03bcs)\r\n\r\nMain function: installed in the main power distribution cabinet, as the first-level lightning protection of the power line.\r\n\r\n<strong>Class I three-phase power SPD (for TN-C system)<\/strong>\r\n\r\nModel: BR-25GR 3P\r\n\r\nMax. continuous operating voltage: 275V~\r\n\r\nLightning impulse current: 25kA (10\/350\u03bcs)\r\n\r\nNominal discharge current: 25kA (8\/20\u03bcs)\r\n\r\nMax. discharge current: 100kA (8\/20\u03bcs)\r\n\r\nMain function: installed in the main power distribution cabinet, as the first-level lightning protection of the power line.\r\n\r\n<strong>Class I three-phase power SPD (for TT system)<\/strong>\r\n\r\nModel: BR-25GR 3P+NPE\r\n\r\nMax. Continuous operating voltage: 275V~\r\n\r\nLightning impulse current: 25Ka\/50kA (10\/350\u03bcs)\r\n\r\nNominal discharge current: 25kA\/50kA (8\/20\u03bcs)\r\n\r\nMax. discharge current: 100kA (8\/20\u03bcs)\r\n\r\nMain function: installed in the main power distribution cabinet, as the first-level lightning protection of the power line.\r\n\r\n<strong>Class II three-phase power SPD (for TN-S or TN-C-S systems)<\/strong>\r\n\r\nModel: BR-40 4P\r\n\r\nMax. continuous operating voltage: 275V~\r\n\r\nNominal discharge current: 20kA (8\/20\u03bcs)\r\n\r\nMax. discharge current: 40kA (8\/20\u03bcs)\r\n\r\nMain function: installed in the sub-power distribution box, as the second-level lightning protection of the power line.\r\n\r\n<strong>Class II three-phase power SPD (for TT system)<\/strong>\r\n\r\nModel: BR-40 3P+NPE\r\n\r\nMax. continuous operating voltage: 275V~\r\n\r\nNominal discharge current: 20kA (8\/20\u03bcs)\r\n\r\nMax. discharge current: 40kA (8\/20\u03bcs)\r\n\r\nMain function: installed in the sub-power distribution box, as the second-level lightning protection of the power line.\r\n\r\n<strong>The lightning protection of the low-voltage power distribution system is as follows:<\/strong>\r\n\r\nThe main power distribution cabinet of the building is installed with a Class I power SPD as the first-level lightning protection of the power line.\r\n\r\nThe secondary power distribution cabinet (box) of the building is installed with a Class II power SPD as the second-level lightning protection of the power line.\r\n\r\nThe tertiary power distribution cabinet (box) of the building is installed with a Class II power SPD as the third-level lightning protection of the power line.\r\n\r\nFor important equipment ports, install Class III power SPD as terminal-level lightning protection for power lines."},"_links":{"self":[{"href":"https:\/\/www.britecelectric.com\/id\/wp-json\/wp\/v2\/blog\/844","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/www.britecelectric.com\/id\/wp-json\/wp\/v2\/blog"}],"about":[{"href":"https:\/\/www.britecelectric.com\/id\/wp-json\/wp\/v2\/types\/blog"}],"wp:featuredmedia":[{"embeddable":true,"href":"https:\/\/www.britecelectric.com\/id\/wp-json\/wp\/v2\/media\/845"}],"wp:attachment":[{"href":"https:\/\/www.britecelectric.com\/id\/wp-json\/wp\/v2\/media?parent=844"}],"wp:term":[{"taxonomy":"blog_category","embeddable":true,"href":"https:\/\/www.britecelectric.com\/id\/wp-json\/wp\/v2\/blog_category?post=844"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}