{"id":791,"date":"2023-12-19T16:19:00","date_gmt":"2023-12-19T08:19:00","guid":{"rendered":"https:\/\/www.britecelectric.com\/?post_type=blog&#038;p=791"},"modified":"2024-09-05T16:35:57","modified_gmt":"2024-09-05T08:35:57","slug":"en-62305-protection-against-lightning","status":"publish","type":"blog","link":"https:\/\/www.britecelectric.com\/id\/blog\/en-62305-protection-against-lightning\/","title":{"rendered":"EN 62305 Perlindungan terhadap petir"},"content":{"rendered":"The EN 62305 standard series specifically cover the protection against lightning to structures, their contents, persons and livestock.\r\n\r\nEN 62305 accepts that we now live in the electronic age, making LEMP (Lightning Electromagnetic Impulse) protection for electronic and electrical systems an integral part of the standard through EN 62305-4. LEMP is the term given to the overall electromagnetic effects of lightning, including conducted surges (transient overvoltage and currents) and radiated electromagnetic field effects.\r\n\r\nEN 62305 \u2013 4 categorizes the source of damage, type of damage and the type of loss.\r\n\r\n<strong>Sumber kerusakan<\/strong>\r\n\r\nKerusakan yang dapat ditimbulkan oleh petir dibedakan menjadi:\r\n<ul>\r\n \t<li>Kerusakan pada struktur (termasuk semua saluran listrik masuk dan saluran terkubur yang terhubung ke struktur)<\/li>\r\n \t<li>Kerusakan pada suatu layanan (layanan dalam hal ini adalah bagian dari jaringan telekomunikasi, data, pasokan listrik, air, gas, dan bahan bakar).<\/li>\r\n<\/ul>\r\n<img class=\"wp-image-17873 size-medium aligncenter\" src=\"https:\/\/www.britecelectric.com\/wp-content\/uploads\/2023\/12\/11-400x271.png\" alt=\"\" width=\"400\" height=\"271\" \/>\r\n\r\n<strong>Jenis kerusakan<\/strong>\r\n\r\nSetiap sumber kerusakan dapat mengakibatkan satu atau lebih dari tiga jenis kerusakan. Kemungkinan jenis kerusakan diidentifikasi sebagai berikut:\r\n<ul>\r\n \t<li>D1 Cedera pada orang atau ternak akibat tegangan langkah dan sentuhan<\/li>\r\n \t<li>D2 Kerusakan fisik (kebakaran, ledakan, kerusakan mekanis, pelepasan bahan kimia) akibat efek arus petir termasuk percikan api<\/li>\r\n \t<li>D3 Kegagalan sistem internal akibat Lightning Electromagnetic Impulse (LEMP).<\/li>\r\n<\/ul>\r\n<strong>Jenis kerugian<\/strong>\r\n\r\nBerikut jenis kerugian yang mungkin timbul akibat kerusakan akibat sambaran petir:\r\n<ul>\r\n \t<li>L1 Hilangnya nyawa manusia<\/li>\r\n \t<li>L2 Hilangnya pelayanan kepada masyarakat<\/li>\r\n \t<li>L3 Hilangnya warisan budaya<\/li>\r\n \t<li>L4 Hilangnya nilai ekonomi<\/li>\r\n<\/ul>\r\nThe relationships of all of the above parameters:\r\n\r\nThe relationships of all of the above parameters:\r\n<table border=\"1\" cellspacing=\"0\">\r\n<tbody>\r\n<tr class=\"firstRow\">\r\n<td valign=\"top\" width=\"142\">Titik serangan<\/td>\r\n<td valign=\"top\" width=\"142\">Sumber\u00a0kerusakan<\/td>\r\n<td valign=\"top\" width=\"142\">Jenis\u00a0kerusakan<\/td>\r\n<td valign=\"top\" width=\"142\">Jenis\u00a0kerugian<\/td>\r\n<\/tr>\r\n<tr>\r\n<td valign=\"top\" width=\"142\">Struktur<\/td>\r\n<td valign=\"top\" width=\"142\">S1<\/td>\r\n<td valign=\"top\" width=\"142\">D1&nbsp;\r\n\r\nD2\r\n\r\nD3<\/td>\r\n<td valign=\"top\" width=\"142\">L1, L4**&nbsp;\r\n\r\nL1, L2, L3, L4\r\n\r\nL1*, L2, L4<\/td>\r\n<\/tr>\r\n<tr>\r\n<td valign=\"top\" width=\"142\">Dekat\u00a0Struktur<\/td>\r\n<td valign=\"top\" width=\"142\">S2<\/td>\r\n<td valign=\"top\" width=\"142\">D3<\/td>\r\n<td valign=\"top\" width=\"142\">L1*, L2, L4<\/td>\r\n<\/tr>\r\n<tr>\r\n<td valign=\"top\" width=\"142\">Layanan terhubung ke struktur<\/td>\r\n<td valign=\"top\" width=\"142\">S3<\/td>\r\n<td valign=\"top\" width=\"142\">D1&nbsp;\r\n\r\nD2\r\n\r\nD3<\/td>\r\n<td valign=\"top\" width=\"142\">L1,L4**&nbsp;\r\n\r\nL1, L2, L3, L4\r\n\r\nL1*, L2, L4<\/td>\r\n<\/tr>\r\n<tr>\r\n<td valign=\"top\" width=\"142\">Dekat layanan<\/td>\r\n<td valign=\"top\" width=\"142\">S4<\/td>\r\n<td valign=\"top\" width=\"142\">D3<\/td>\r\n<td valign=\"top\" width=\"142\">L1*, L2, L4<\/td>\r\n<\/tr>\r\n<\/tbody>\r\n<\/table>\r\n* Only for structures with risk of explosion and for hospitals or other structures where failures of internal systems immediately endangers human life.\r\n\r\n** Only for properties where animals may be lost.\r\n\r\nLEMP damage is so prevalent that it is identified as one of the specific types (D3) against which protection should be provided and can occur from ALL strike points to the structure or connected services \u2013 direct or indirect. This extended approach also takes into account the danger of fire or explosion associated with services connected to the structure, e.g. power, telecoms and other metallic lines.\r\n\r\nEN 62305 makes it clear that structural lightning protection must no longer be considered in isolation from transient overvoltage\/surge protection and given that lightning from all strikes points, direct or indirect, to the structure or connected services creates a risk from transients, SPDs are a vital means of protection whether structural lightning protection is present or not.\r\n\r\n<strong>Bentuk gelombang arus dan tegangan<\/strong>\r\n\r\nEN 62305 takes account of protection measures on metallic service lines (typically power, signal and telecom lines) using transient overvoltage or Surge Protection Devices (SPDs) against both direct lightning strikes as well as the more common indirect lightning strikes and switching transients. Standards such as the EN 61643 series define the characteristics of lightning currents and voltages to enable reliable and repeatable testing of SPDs (as well as lightning protection components). Although these waveforms may differ from actual transients, the standardized forms are based upon years of observation and measurement (and in some cases simulation). In general they provide a fair approximation of the real world transient.\r\n\r\nTransient waveforms have a fast rising edge and a longer tail. They are described through their peak value (or magnitude), rise time and their duration (or fall time). The duration is measured as the time taken for the test transient to decay to half its peak value.\r\n\r\nThe figures below illustrate the common current and voltage waveforms that are used to test SPDs for mains, signal and telecom lines.\r\n\r\n<img class=\"wp-image-17874 size-medium aligncenter\" src=\"https:\/\/www.britecelectric.com\/wp-content\/uploads\/2023\/12\/12-400x239.png\" sizes=\"(max-width: 400px) 100vw, 400px\" srcset=\"https:\/\/www.britecelectric.com\/wp-content\/uploads\/2023\/12\/12-400x239.png 400w, https:\/\/www.britecelectric.com\/wp-content\/uploads\/2023\/12\/12-768x459.png 768w, https:\/\/www.britecelectric.com\/wp-content\/uploads\/2023\/12\/12-600x358.png 600w, https:\/\/www.britecelectric.com\/wp-content\/uploads\/2023\/12\/12-150x90.png 150w, https:\/\/www.britecelectric.com\/wp-content\/uploads\/2023\/12\/12.png 1147w\" alt=\"\" width=\"400\" height=\"239\" \/>\r\n\r\n<strong>Serangan langsung<\/strong>\r\n\r\nPetir langsung dapat menyuntikkan sebagian arus petir dengan bentuk gelombang 10\/350\u03bcs ke dalam sistem di mana struktur dengan Sistem Proteksi Petir struktural menerima sambaran langsung (Sumber S1) atau di mana petir langsung menyambar saluran layanan udara (Sumber S3).\r\n\r\n<strong>Serangan tidak langsung<\/strong>\r\n\r\nRemote or indirect lightning flashes near the structure (Source S2) or near a connected service to the structure (Source S4) of up to 1km radius away (and hence far more common) are represented by the 8\/20\u03bcs waveform. Induced surges from direct lightning flashes and switching sources are also represented by this waveform. With a much shorter decay or fall time relative to the 10\/350\u03bcs waveform, the 8\/20\u03bcs waveform presents significantly less energy (for an equivalent peak current) but is still devastating enough to damage electrical and electronic equipment.\r\n\r\nEN 62305-1 recognizes that failure of internal systems (Damage Type D3) due to Lightning Electromagnetic Impulse (LEMP) is possible from all points of strike to the structure or service \u2013 direct or indirect (all Sources: S1, S2, S3 and S4).\r\n\r\n<strong>Tindakan Perlindungan Lonjakan (SPM)<\/strong>\r\n\r\nEN 62305-4 describes a number of measures to minimize the severity of transient overvoltage caused by lightning and electrical switching.\r\n\r\nKey and basic protection measures are:\r\n<ul>\r\n \t<li>Pembumian dan pengikatan<\/li>\r\n \t<li>Pelindung elektromagnetik dan perutean saluran<\/li>\r\n \t<li>Perangkat Pelindung Lonjakan Terkoordinasi<\/li>\r\n<\/ul>\r\nTindakan perlindungan tambahan lebih lanjut meliputi:\r\n<ul>\r\n \t<li>Perluasan ke LPS struktural<\/li>\r\n \t<li>Lokasi peralatan<\/li>\r\n \t<li>Penggunaan kabel serat optik (perlindungan dengan isolasi)<\/li>\r\n<\/ul>\r\nSPMs also have to operate within and withstand the environment in which they are located considering factors such as temperature, humidity, vibration, voltage and current.\r\n\r\nSelection of the most suitable SPM is made using the risk assessment in accordance with EN 62305-2 taking into account both technical and economic factors. For example, it may not be practical or cost effective to implement electromagnetic shielding measures in an existing structure so the use of coordinated SPDs may be more suitable. Ideally SPDs are best incorporated at the project design stage, although they can also be readily installed in existing installations.\r\n\r\nTo ensure continuous operation of critical systems even in the event of a direct strike, SPDs are essential and these must be suitably deployed, based on the source of surge and its intensity using the Lightning Protection Zones (LPZ) concept within EN 62305-4.\r\n\r\n<strong>Konsep Lightning Protection Zone (LPZ).<\/strong>\r\n\r\nPerlindungan terhadap LEMP didasarkan pada konsep Lightning Protection Zone (LPZ) yang membagi struktur yang dimaksud menjadi beberapa zona sesuai dengan tingkat ancaman yang ditimbulkan oleh LEMP. Ide umumnya adalah untuk mengidentifikasi atau membuat zona di dalam struktur di mana paparan terhadap sebagian atau seluruh efek petir lebih sedikit dan mengoordinasikannya dengan karakteristik kekebalan peralatan listrik atau elektronik yang dipasang di dalam zona tersebut. Zona yang berurutan adalahditandai dengan penurunan keparahan LEMP yang signifikan sebagai akibat dari bonding, shielding, atau penggunaan SPD.\r\n\r\n<strong>Zona luar:<\/strong>\r\n<ul>\r\n \t<li>LPZ 0A adalah area yang terkena sambaran petir langsung dan oleh karena itu mungkin harus membawa arus petir hingga penuh. Ini biasanya merupakan area atap suatu struktur tanpa proteksi petir struktural. Medan elektromagnetik penuh terjadi di sini.<\/li>\r\n \t<li>LPZ 0B adalah area yang tidak terkena sambaran petir langsung dan biasanya merupakan dinding samping suatu struktur atau atap dengan proteksi petir struktural. Namun medan elektromagnetik penuh masih terjadi di sini dan arus petir parsial atau terinduksi serta lonjakan peralihan dapat terjadi di sini.<\/li>\r\n<\/ul>\r\n<strong>Zona dalam:<\/strong>\r\n<ul>\r\n \t<li>LPZ 1 adalah area internal yang terkena arus petir parsial. Arus petir yang dihantarkan dan\/atau lonjakan peralihan berkurang dibandingkan dengan zona eksternal LPZ 0A, LPZ 0B seperti halnya medan elektromagnetik jika tindakan pelindung yang sesuai digunakan. Ini biasanya merupakan area di mana layanan memasuki struktur atau di mana switchboard daya utama berada.<\/li>\r\n \t<li>LPZ 2 adalah area internal yang terletak lebih jauh di dalam struktur di mana sisa arus impuls petir dan\/atau lonjakan arus switching berkurang dibandingkan dengan LPZ 1. Demikian pula, medan elektromagnetik akan semakin berkurang jika tindakan pelindung yang sesuai diterapkan. Ini biasanya berupa ruangan berpelindung atau, untuk sumber listrik di area dewan sub-distribusi.<\/li>\r\n<\/ul>","protected":false},"featured_media":792,"parent":0,"menu_order":180,"template":"","meta":{"_acf_changed":false},"blog_category":[8],"class_list":["post-791","blog","type-blog","status-publish","has-post-thumbnail","hentry","blog_category-company-news"],"acf":{"des":"The EN 62305 standard series specifically cover the protection against lightning to structures, their contents, persons and livestock.","txt":"The EN 62305 standard series specifically cover the protection against lightning to structures, their contents, persons and livestock.\r\n\r\nEN 62305 accepts that we now live in the electronic age, making LEMP (Lightning Electromagnetic Impulse) protection for electronic and electrical systems an integral part of the standard through EN 62305-4. LEMP is the term given to the overall electromagnetic effects of lightning, including conducted surges (transient overvoltage and currents) and radiated electromagnetic field effects.\r\n\r\nEN 62305 \u2013 4 categorizes the source of damage, type of damage and the type of loss.\r\n\r\n<strong>Sources of damage<\/strong>\r\n\r\nDamage that can be caused by lightning is sub-divided into:\r\n<ul>\r\n \t<li>Damage to a structure (including all incoming electrical overhead and buried lines connected to the structure)<\/li>\r\n \t<li>Damage to a service (service in this instance being part of telecommunication, data, electrical supply, water, gas and fuel distribution networks).<\/li>\r\n<\/ul>\r\n<img class=\"wp-image-17873 size-medium aligncenter\" src=\"https:\/\/www.britecelectric.com\/wp-content\/uploads\/2023\/12\/11-400x271.png\" alt=\"\" width=\"400\" height=\"271\" \/>\r\n\r\n<strong>Types of damage<\/strong>\r\n\r\nEach source of damage may result in one or more of three types of damage. The possible types of damage are identified as follows:\r\n<ul>\r\n \t<li>D1 Injury of persons or livestock due to step and touch voltages<\/li>\r\n \t<li>D2 Physical damage (fire, explosion, mechanical destruction, chemical release) due to lightning current effects including sparking<\/li>\r\n \t<li>D3 Failure of internal systems due to Lightning Electromagnetic Impulse (LEMP).<\/li>\r\n<\/ul>\r\n<strong>Types of loss<\/strong>\r\n\r\nThe following types of loss may result from damage due to lightning:\r\n<ul>\r\n \t<li>L1 Loss of human life<\/li>\r\n \t<li>L2 Loss of service to the public<\/li>\r\n \t<li>L3 Loss of cultural heritage<\/li>\r\n \t<li>L4 Loss of economic value<\/li>\r\n<\/ul>\r\nThe relationships of all of the above parameters:\r\n\r\nThe relationships of all of the above parameters:\r\n<table border=\"1\" cellspacing=\"0\">\r\n<tbody>\r\n<tr class=\"firstRow\">\r\n<td valign=\"top\" width=\"142\">Point of strike<\/td>\r\n<td valign=\"top\" width=\"142\">Source of\u00a0damage<\/td>\r\n<td valign=\"top\" width=\"142\">Type of\u00a0damage<\/td>\r\n<td valign=\"top\" width=\"142\">Type of\u00a0loss<\/td>\r\n<\/tr>\r\n<tr>\r\n<td valign=\"top\" width=\"142\">Structure<\/td>\r\n<td valign=\"top\" width=\"142\">S1<\/td>\r\n<td valign=\"top\" width=\"142\">D1&nbsp;\r\n\r\nD2\r\n\r\nD3<\/td>\r\n<td valign=\"top\" width=\"142\">L1, L4**&nbsp;\r\n\r\nL1, L2, L3, L4\r\n\r\nL1*, L2, L4<\/td>\r\n<\/tr>\r\n<tr>\r\n<td valign=\"top\" width=\"142\">Near a\u00a0Structure<\/td>\r\n<td valign=\"top\" width=\"142\">S2<\/td>\r\n<td valign=\"top\" width=\"142\">D3<\/td>\r\n<td valign=\"top\" width=\"142\">L1*, L2, L4<\/td>\r\n<\/tr>\r\n<tr>\r\n<td valign=\"top\" width=\"142\">Service connected\u00a0to the structure<\/td>\r\n<td valign=\"top\" width=\"142\">S3<\/td>\r\n<td valign=\"top\" width=\"142\">D1&nbsp;\r\n\r\nD2\r\n\r\nD3<\/td>\r\n<td valign=\"top\" width=\"142\">L1,L4**&nbsp;\r\n\r\nL1, L2, L3, L4\r\n\r\nL1*, L2, L4<\/td>\r\n<\/tr>\r\n<tr>\r\n<td valign=\"top\" width=\"142\">Near a service<\/td>\r\n<td valign=\"top\" width=\"142\">S4<\/td>\r\n<td valign=\"top\" width=\"142\">D3<\/td>\r\n<td valign=\"top\" width=\"142\">L1*, L2, L4<\/td>\r\n<\/tr>\r\n<\/tbody>\r\n<\/table>\r\n* Only for structures with risk of explosion and for hospitals or other structures where failures of internal systems immediately endangers human life.\r\n\r\n** Only for properties where animals may be lost.\r\n\r\nLEMP damage is so prevalent that it is identified as one of the specific types (D3) against which protection should be provided and can occur from ALL strike points to the structure or connected services \u2013 direct or indirect. This extended approach also takes into account the danger of fire or explosion associated with services connected to the structure, e.g. power, telecoms and other metallic lines.\r\n\r\nEN 62305 makes it clear that structural lightning protection must no longer be considered in isolation from transient overvoltage\/surge protection and given that lightning from all strikes points, direct or indirect, to the structure or connected services creates a risk from transients, SPDs are a vital means of protection whether structural lightning protection is present or not.\r\n\r\n<strong>Current and voltage waveforms<\/strong>\r\n\r\nEN 62305 takes account of protection measures on metallic service lines (typically power, signal and telecom lines) using transient overvoltage or Surge Protection Devices (SPDs) against both direct lightning strikes as well as the more common indirect lightning strikes and switching transients. Standards such as the EN 61643 series define the characteristics of lightning currents and voltages to enable reliable and repeatable testing of SPDs (as well as lightning protection components). Although these waveforms may differ from actual transients, the standardized forms are based upon years of observation and measurement (and in some cases simulation). In general they provide a fair approximation of the real world transient.\r\n\r\nTransient waveforms have a fast rising edge and a longer tail. They are described through their peak value (or magnitude), rise time and their duration (or fall time). The duration is measured as the time taken for the test transient to decay to half its peak value.\r\n\r\nThe figures below illustrate the common current and voltage waveforms that are used to test SPDs for mains, signal and telecom lines.\r\n\r\n<img class=\"wp-image-17874 size-medium aligncenter\" src=\"https:\/\/www.britecelectric.com\/wp-content\/uploads\/2023\/12\/12-400x239.png\" sizes=\"(max-width: 400px) 100vw, 400px\" srcset=\"https:\/\/www.britecelectric.com\/wp-content\/uploads\/2023\/12\/12-400x239.png 400w, https:\/\/www.britecelectric.com\/wp-content\/uploads\/2023\/12\/12-768x459.png 768w, https:\/\/www.britecelectric.com\/wp-content\/uploads\/2023\/12\/12-600x358.png 600w, https:\/\/www.britecelectric.com\/wp-content\/uploads\/2023\/12\/12-150x90.png 150w, https:\/\/www.britecelectric.com\/wp-content\/uploads\/2023\/12\/12.png 1147w\" alt=\"\" width=\"400\" height=\"239\" \/>\r\n\r\n<strong>Direct strikes<\/strong>\r\n\r\nDirect lightning can inject partial lightning currents of the 10\/350\u03bcs waveform into a system where a structure with a structural Lightning Protection System receives a direct strike (Source S1) or where lightning directly strikes an overhead service line (Source S3).\r\n\r\n<strong>Indirect strikes<\/strong>\r\n\r\nRemote or indirect lightning flashes near the structure (Source S2) or near a connected service to the structure (Source S4) of up to 1km radius away (and hence far more common) are represented by the 8\/20\u03bcs waveform. Induced surges from direct lightning flashes and switching sources are also represented by this waveform. With a much shorter decay or fall time relative to the 10\/350\u03bcs waveform, the 8\/20\u03bcs waveform presents significantly less energy (for an equivalent peak current) but is still devastating enough to damage electrical and electronic equipment.\r\n\r\nEN 62305-1 recognizes that failure of internal systems (Damage Type D3) due to Lightning Electromagnetic Impulse (LEMP) is possible from all points of strike to the structure or service \u2013 direct or indirect (all Sources: S1, S2, S3 and S4).\r\n\r\n<strong>Surge Protection Measures (SPM)<\/strong>\r\n\r\nEN 62305-4 describes a number of measures to minimize the severity of transient overvoltage caused by lightning and electrical switching.\r\n\r\nKey and basic protection measures are:\r\n<ul>\r\n \t<li>Earthing and bonding<\/li>\r\n \t<li>Electromagnetic shielding and line routing<\/li>\r\n \t<li>Coordinated Surge Protective Devices<\/li>\r\n<\/ul>\r\nFurther additional protection measures include:\r\n<ul>\r\n \t<li>Extensions to the structural LPS<\/li>\r\n \t<li>Equipment location<\/li>\r\n \t<li>Use of fiber optic cables (protection by isolation)<\/li>\r\n<\/ul>\r\nSPMs also have to operate within and withstand the environment in which they are located considering factors such as temperature, humidity, vibration, voltage and current.\r\n\r\nSelection of the most suitable SPM is made using the risk assessment in accordance with EN 62305-2 taking into account both technical and economic factors. For example, it may not be practical or cost effective to implement electromagnetic shielding measures in an existing structure so the use of coordinated SPDs may be more suitable. Ideally SPDs are best incorporated at the project design stage, although they can also be readily installed in existing installations.\r\n\r\nTo ensure continuous operation of critical systems even in the event of a direct strike, SPDs are essential and these must be suitably deployed, based on the source of surge and its intensity using the Lightning Protection Zones (LPZ) concept within EN 62305-4.\r\n\r\n<strong>The Lightning Protection Zone (LPZ) concept<\/strong>\r\n\r\nProtection against LEMP is based on a concept of the Lightning Protection Zone (LPZ) that divides the structure in question into a number of zones according to the level of threat posed by the LEMP. The general idea is to identify or create zones within the structure where there is less exposure to some or all of the effects of lightning and to coordinate these with the immunity characteristics of the electrical or electronic equipment installed within the zone. Successive zones are characterized by significant reductions in LEMP severity as a result of bonding, shielding or the use of SPDs.\r\n\r\n<strong>External zones:<\/strong>\r\n<ul>\r\n \t<li>LPZ 0A is the area subject to direct lightning strokes and therefore may have to carry up to the full lightning current. This is typically the roof area of a structure without structural lightning protection. The full electromagnetic field occurs here.<\/li>\r\n \t<li>LPZ 0B is the area not subject to direct lightning strokes and is typically the sidewalls of a structure or a roof with structural lightning protection. However the full electromagnetic field still occurs here and conducted partial or induced lightning currents and switching surges can occur here.<\/li>\r\n<\/ul>\r\n<strong>Internal zones:<\/strong>\r\n<ul>\r\n \t<li>LPZ 1 is the internal area that is subject to partial lightning currents. The conducted lightning currents and\/or switching surges are reduced compared with the external zones LPZ 0A, LPZ 0B as is the electromagnetic field if suitable shielding measures are employed. This is typically the area where services enter the structure or where the main power switchboard is located.<\/li>\r\n \t<li>LPZ 2 is an internal area that is further located inside the structure where the remnants of lightning impulse currents and\/or switching surges are reduced compared with LPZ 1. Similarly the electromagnetic field is further reduced if suitable shielding measures are employed. This is typically a screened room or, for mains power at the sub-distribution board area.<\/li>\r\n<\/ul>"},"_links":{"self":[{"href":"https:\/\/www.britecelectric.com\/id\/wp-json\/wp\/v2\/blog\/791","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/www.britecelectric.com\/id\/wp-json\/wp\/v2\/blog"}],"about":[{"href":"https:\/\/www.britecelectric.com\/id\/wp-json\/wp\/v2\/types\/blog"}],"wp:featuredmedia":[{"embeddable":true,"href":"https:\/\/www.britecelectric.com\/id\/wp-json\/wp\/v2\/media\/792"}],"wp:attachment":[{"href":"https:\/\/www.britecelectric.com\/id\/wp-json\/wp\/v2\/media?parent=791"}],"wp:term":[{"taxonomy":"blog_category","embeddable":true,"href":"https:\/\/www.britecelectric.com\/id\/wp-json\/wp\/v2\/blog_category?post=791"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}