{"id":758,"date":"2023-12-19T20:49:46","date_gmt":"2023-12-19T12:49:46","guid":{"rendered":"https:\/\/www.britecelectric.com\/?post_type=blog&#038;p=758"},"modified":"2024-09-05T16:35:18","modified_gmt":"2024-09-05T08:35:18","slug":"low-voltage-power-supply-systems","status":"publish","type":"blog","link":"https:\/\/www.britecelectric.com\/id\/blog\/low-voltage-power-supply-systems\/","title":{"rendered":"Sistem Catu Daya Tegangan Rendah"},"content":{"rendered":"<strong>terminologi IEC<\/strong>\r\n\r\nInternational standard IEC 60364 distinguishes three families of earthing arrangements, using the two-letter codes TN, TT, and IT.\r\n\r\nThe first letter indicates the connection between earth and the power-supply equipment (generator or transformer):\r\n\r\n\u201cT\u201d \u2014 Direct connection of a point with earth\r\n\r\n\u201cI\u201d \u2014 No point is connected with earth, except perhaps via high impedance.\r\n\r\nThe second letter indicates the connection between earth or network and the electrical device being supplied:\r\n\r\n\u201cT\u201d \u2014 Earth connection is by a local direct connection to earth, usually via a ground rod.\r\n\r\n\u201cN\u201d \u2014 the earth connection is supplied by the electricity supply network, either separately to the neutral conductor (TN-S), combined with the neutral conductor (TN-C), or both (TN-C-S). These are discussed below.\r\n\r\n<strong>Jenis jaringan TN<\/strong>\r\n\r\nIn a TN earthing system, one of the points in the generator or transformer is connected with earth, usually the star point in a three-phase system. The body of the electrical device is connected with earth via this earth connection at the transformer. This arrangement is a current standard for residential and industrial electric systems particularly in Europe.\r\n\r\nThe conductor that connects the exposed metallic parts of the consumer\u2019s electrical installation is called protective earth (PE; see also: Ground). The conductor that connects to the star point in a three-phase system, or that carries the return current in a single-phase system, is called neutral (N). Three variants of TN systems are distinguished:\r\n\r\n<strong>TN\u2212S<\/strong>\r\n\r\nPE dan N merupakan konduktor terpisah yang dihubungkan bersama hanya di dekat sumber listrik.\r\n\r\n<img class=\"alignnone size-full wp-image-760\" src=\"http:\/\/www.britecelectric.com\/wp-content\/uploads\/2024\/08\/Low-voltage-Power-Supply-Systems-2.png\" alt=\"\" width=\"520\" height=\"405\" \/>\r\n\r\n<strong>TN\u2212C<\/strong>\r\n\r\nKonduktor PEN gabungan memenuhi fungsi konduktor PE dan N. (Pada sistem 230\/400 V biasanya hanya digunakan untuk jaringan distribusi)\r\n\r\n<img class=\"alignnone size-full wp-image-761\" src=\"http:\/\/www.britecelectric.com\/wp-content\/uploads\/2024\/08\/Low-voltage-Power-Supply-Systems-3.png\" alt=\"\" width=\"445\" height=\"384\" \/>\r\n\r\n<strong>TN\u2212C\u2212S<\/strong>\r\n\r\nBagian dari sistem menggunakan konduktor PEN gabungan, yang pada titik tertentu dipecah menjadi jalur PE dan N yang terpisah. Konduktor PEN gabungan biasanya terjadi antara gardu induk dan titik masuk ke dalam gedung, dan bumi dan netral dipisahkan di kepala layanan. Di Inggris, sistem ini juga dikenal sebagai proteksi pembumian ganda (PME), karena praktik menghubungkan gabungan konduktor netral dan pembumian melalui rute terpendek yang dapat diterapkan ke batang pembumian lokal di sumbernya.dan pada interval tertentu di sepanjang jaringan distribusi ke setiap lokasi, untuk menyediakan pembumian sistem dan pembumian peralatan di setiap lokasi tersebut. Sistem serupa di Australia dan Selandia Baru ditetapkan sebagai multiple earthed neutral (MEN) dan, di Amerika Utara, sebagai multi-grounded neutral (MGN).\r\n\r\n<img class=\"alignnone size-full wp-image-762\" src=\"http:\/\/www.britecelectric.com\/wp-content\/uploads\/2024\/08\/Low-voltage-Power-Supply-Systems-4.png\" alt=\"\" width=\"656\" height=\"456\" \/>\r\n\r\n<strong>jaringan TT<\/strong>\r\n\r\nDalam sistem pembumian TT, sambungan pembumian pelindung untuk konsumen disediakan oleh elektroda pembumian lokal, dan ada elektroda lain yang dipasang secara terpisah di generator. Tidak ada \u2018kabel bumi\u2019 di antara keduanya. Impedansi loop kesalahan lebih tinggi, dan kecuali impedansi elektroda sangat rendah, instalasi TT harus selalu memiliki RCD (GFCI) sebagai isolator pertamanya.\r\n\r\n<img class=\"alignnone size-full wp-image-763\" src=\"http:\/\/www.britecelectric.com\/wp-content\/uploads\/2024\/08\/Low-voltage-Power-Supply-Systems-5.png\" alt=\"\" width=\"524\" height=\"418\" \/>\r\n\r\n<strong>jaringan TI<\/strong>\r\n\r\nDalam jaringan IT, sistem distribusi listrik tidak memiliki sambungan ke bumi sama sekali, atau hanya memiliki sambungan impedansi tinggi.\r\n\r\n<img class=\"alignnone size-full wp-image-764\" src=\"http:\/\/www.britecelectric.com\/wp-content\/uploads\/2024\/08\/Low-voltage-Power-Supply-Systems-6.png\" alt=\"\" width=\"502\" height=\"425\" \/>","protected":false},"featured_media":780,"parent":0,"menu_order":183,"template":"","meta":{"_acf_changed":false},"blog_category":[8],"class_list":["post-758","blog","type-blog","status-publish","has-post-thumbnail","hentry","blog_category-company-news"],"acf":{"des":"International standard IEC 60364 distinguishes three families of earthing arrangements, using the two-letter codes TN, TT, and IT.","txt":"<strong>IEC terminology<\/strong>\r\n\r\nInternational standard IEC 60364 distinguishes three families of earthing arrangements, using the two-letter codes TN, TT, and IT.\r\n\r\nThe first letter indicates the connection between earth and the power-supply equipment (generator or transformer):\r\n\r\n\u201cT\u201d \u2014 Direct connection of a point with earth\r\n\r\n\u201cI\u201d \u2014 No point is connected with earth, except perhaps via high impedance.\r\n\r\nThe second letter indicates the connection between earth or network and the electrical device being supplied:\r\n\r\n\u201cT\u201d \u2014 Earth connection is by a local direct connection to earth, usually via a ground rod.\r\n\r\n\u201cN\u201d \u2014 the earth connection is supplied by the electricity supply network, either separately to the neutral conductor (TN-S), combined with the neutral conductor (TN-C), or both (TN-C-S). These are discussed below.\r\n\r\n<strong>Types of TN networks<\/strong>\r\n\r\nIn a TN earthing system, one of the points in the generator or transformer is connected with earth, usually the star point in a three-phase system. The body of the electrical device is connected with earth via this earth connection at the transformer. This arrangement is a current standard for residential and industrial electric systems particularly in Europe.\r\n\r\nThe conductor that connects the exposed metallic parts of the consumer\u2019s electrical installation is called protective earth (PE; see also: Ground). The conductor that connects to the star point in a three-phase system, or that carries the return current in a single-phase system, is called neutral (N). Three variants of TN systems are distinguished:\r\n\r\n<strong>TN\u2212S<\/strong>\r\n\r\nPE and N are separate conductors that are connected together only near the power source.\r\n\r\n<img class=\"alignnone size-full wp-image-760\" src=\"http:\/\/www.britecelectric.com\/wp-content\/uploads\/2024\/08\/Low-voltage-Power-Supply-Systems-2.png\" alt=\"\" width=\"520\" height=\"405\" \/>\r\n\r\n<strong>TN\u2212C<\/strong>\r\n\r\nA combined PEN conductor fulfills the functions of both a PE and an N conductor. (On 230\/400 V systems normally only used for distribution networks)\r\n\r\n<img class=\"alignnone size-full wp-image-761\" src=\"http:\/\/www.britecelectric.com\/wp-content\/uploads\/2024\/08\/Low-voltage-Power-Supply-Systems-3.png\" alt=\"\" width=\"445\" height=\"384\" \/>\r\n\r\n<strong>TN\u2212C\u2212S<\/strong>\r\n\r\nPart of the system uses a combined PEN conductor, which is at some point split up into separate PE and N lines. The combined PEN conductor typically occurs between the substation and the entry point into the building, and earth and neutral are separated in the service head. In the UK, this system is also known as protective multiple earthing (PME), because of the practice of connecting the combined neutral-and-earth conductor via the shortest practicable route to local earth rods at the source and at intervals along the distribution networks to each premises, to provide both system earthing and equipment earthing at each of these locations. Similar systems in Australia and New Zealand are designated as multiple earthed neutral (MEN) and, in North America, as multi-grounded neutral (MGN).\r\n\r\n<img class=\"alignnone size-full wp-image-762\" src=\"http:\/\/www.britecelectric.com\/wp-content\/uploads\/2024\/08\/Low-voltage-Power-Supply-Systems-4.png\" alt=\"\" width=\"656\" height=\"456\" \/>\r\n\r\n<strong>TT network<\/strong>\r\n\r\nIn a TT earthing system, the protective earth connection for the consumer is provided by a local earth electrode, and there is another independently installed at the generator. There is no \u2018earth wire\u2019 between the two. The fault loop impedance is higher, and unless the electrode impedance is very low indeed, a TT installation should always have an RCD (GFCI) as its first isolator.\r\n\r\n<img class=\"alignnone size-full wp-image-763\" src=\"http:\/\/www.britecelectric.com\/wp-content\/uploads\/2024\/08\/Low-voltage-Power-Supply-Systems-5.png\" alt=\"\" width=\"524\" height=\"418\" \/>\r\n\r\n<strong>IT network<\/strong>\r\n\r\nIn an IT network, the electrical distribution system has no connection to earth at all, or it has only a high-impedance connection.\r\n\r\n<img class=\"alignnone size-full wp-image-764\" src=\"http:\/\/www.britecelectric.com\/wp-content\/uploads\/2024\/08\/Low-voltage-Power-Supply-Systems-6.png\" alt=\"\" width=\"502\" height=\"425\" \/>"},"_links":{"self":[{"href":"https:\/\/www.britecelectric.com\/id\/wp-json\/wp\/v2\/blog\/758","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/www.britecelectric.com\/id\/wp-json\/wp\/v2\/blog"}],"about":[{"href":"https:\/\/www.britecelectric.com\/id\/wp-json\/wp\/v2\/types\/blog"}],"wp:featuredmedia":[{"embeddable":true,"href":"https:\/\/www.britecelectric.com\/id\/wp-json\/wp\/v2\/media\/780"}],"wp:attachment":[{"href":"https:\/\/www.britecelectric.com\/id\/wp-json\/wp\/v2\/media?parent=758"}],"wp:term":[{"taxonomy":"blog_category","embeddable":true,"href":"https:\/\/www.britecelectric.com\/id\/wp-json\/wp\/v2\/blog_category?post=758"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}