{"id":844,"date":"2023-12-18T15:08:31","date_gmt":"2023-12-18T07:08:31","guid":{"rendered":"https:\/\/www.britecelectric.com\/?post_type=blog&#038;p=844"},"modified":"2024-09-05T16:32:04","modified_gmt":"2024-09-05T08:32:04","slug":"lightning-protection-of-low-voltage-power-distribution-system-in-buildings","status":"publish","type":"blog","link":"https:\/\/www.britecelectric.com\/fr\/blog\/lightning-protection-of-low-voltage-power-distribution-system-in-buildings\/","title":{"rendered":"Protection contre la foudre des syst\u00e8mes de distribution d'\u00e9nergie basse tension dans les b\u00e2timents"},"content":{"rendered":"Les catastrophes dues \u00e0 la foudre comprennent principalement les coups de foudre directs, l'induction \u00e9lectrostatique de la foudre et les impulsions \u00e9lectromagn\u00e9tiques de la foudre.\r\n\r\n<strong>Coup de foudre direct<\/strong>\r\n\r\nLa foudre directe fait r\u00e9f\u00e9rence au ph\u00e9nom\u00e8ne physique selon lequel le nuage d\u2019orage se d\u00e9charge directement sur le sol. Si le sol est directement frapp\u00e9 par la foudre, un courant instantan\u00e9 important sera g\u00e9n\u00e9r\u00e9 \u00e0 l\u2019endroit de la foudre. Si le courant de foudre ne peut pas \u00eatre lib\u00e9r\u00e9 \u00e0 temps, l'objet frapp\u00e9 par la foudre g\u00e9n\u00e9rera instantan\u00e9ment beaucoup de chaleur, provoquant sa dilatation, sa fonte, sa br\u00fblure, son explosion et d'autres dommages. En r\u00e8gle g\u00e9n\u00e9rale, les b\u00e2timents doivent tenir compte des dangers li\u00e9s auxcoups de foudre directs.\r\n\r\n<strong>Induction \u00e9lectrostatique de la foudre<\/strong>\r\n\r\nL'induction de la foudre signifie que lorsqu'un nuage d'orage charg\u00e9 appara\u00eet dans le ciel, des lignes m\u00e9talliques, des objets m\u00e9talliques, etc. sous le nuage d'orage prennent une charge \u00e9lectrique oppos\u00e9e \u00e0 celle d'un nuage d'orage par induction \u00e9lectrostatique. Lorsqu'un \u00e9clair se produit, la charge du nuage d'orage dispara\u00eet rapidement \u00e0 cause de l'\u00e9clair. La charge induite sur la ligne m\u00e9tallique se propage le long de la ligne, provoquant une surtension transitoire au niveau du port ligne de l'appareil. Si la charge induite sur l'objet m\u00e9talliquene peut pas dispara\u00eetre avec le temps, il y aura un ph\u00e9nom\u00e8ne de d\u00e9charge externe, qui formera une \u00e9tincelle.\r\n\r\n<strong>Impulsion \u00e9lectromagn\u00e9tique de foudre<\/strong>\r\n\r\nLightning electromagnetic pulse refers to the instantaneous formation of a lightning electromagnetic field in the area where the lightning strike occurs due to the extremely large peak value and speed of the lightning current. Under the action of the changing lightning electromagnetic field, metal lines in the area induce instantaneous lightning current. If the lightning current penetrates into the power supply line and communication line, transient overvoltage may occur on the device\u2019s line port.\r\n\r\nLightning protection of low-voltage power distribution system is to prevent the low-voltage power distribution system from introducing lightning current from lines outside the building.\r\n\r\n<strong>Mesures de base de protection contre la foudre<\/strong>\r\n\r\nPour les syst\u00e8mes de distribution d'\u00e9nergie basse tension, les mod\u00e8les et param\u00e8tres de parafoudre couramment utilis\u00e9s sont les suivants\u00a0:\r\n\r\n<strong>SPD d'alimentation triphas\u00e9 de classe I (pour syst\u00e8me TN-S)<\/strong>\r\n\r\nModel: BR-25GR 4P\r\n\r\nMax. continuous operating voltage: 275V~\r\n\r\nLightning impulse current: 25kA (10\/350\u03bcs)\r\n\r\nNominal discharge current: 25kA (8\/20\u03bcs)\r\n\r\nMax. discharge current: 100kA (8\/20\u03bcs)\r\n\r\nMain function: installed in the main power distribution cabinet, as the first-level lightning protection of the power line.\r\n\r\n<strong>SPD d'alimentation triphas\u00e9 de classe I (pour syst\u00e8me TN-C)<\/strong>\r\n\r\nModel: BR-25GR 3P\r\n\r\nMax. continuous operating voltage: 275V~\r\n\r\nLightning impulse current: 25kA (10\/350\u03bcs)\r\n\r\nNominal discharge current: 25kA (8\/20\u03bcs)\r\n\r\nMax. discharge current: 100kA (8\/20\u03bcs)\r\n\r\nMain function: installed in the main power distribution cabinet, as the first-level lightning protection of the power line.\r\n\r\n<strong>SPD de puissance triphas\u00e9 de classe I (pour syst\u00e8me TT)<\/strong>\r\n\r\nModel: BR-25GR 3P+NPE\r\n\r\nMax. Continuous operating voltage: 275V~\r\n\r\nLightning impulse current: 25Ka\/50kA (10\/350\u03bcs)\r\n\r\nNominal discharge current: 25kA\/50kA (8\/20\u03bcs)\r\n\r\nMax. discharge current: 100kA (8\/20\u03bcs)\r\n\r\nMain function: installed in the main power distribution cabinet, as the first-level lightning protection of the power line.\r\n\r\n<strong>SPD de puissance triphas\u00e9 de classe II (pour les syst\u00e8mes TN-S ou TN-C-S)<\/strong>\r\n\r\nModel: BR-40 4P\r\n\r\nMax. continuous operating voltage: 275V~\r\n\r\nNominal discharge current: 20kA (8\/20\u03bcs)\r\n\r\nMax. discharge current: 40kA (8\/20\u03bcs)\r\n\r\nMain function: installed in the sub-power distribution box, as the second-level lightning protection of the power line.\r\n\r\n<strong>SPD de puissance triphas\u00e9 de classe II (pour le syst\u00e8me TT)<\/strong>\r\n\r\nModel: BR-40 3P+NPE\r\n\r\nMax. continuous operating voltage: 275V~\r\n\r\nNominal discharge current: 20kA (8\/20\u03bcs)\r\n\r\nMax. discharge current: 40kA (8\/20\u03bcs)\r\n\r\nMain function: installed in the sub-power distribution box, as the second-level lightning protection of the power line.\r\n\r\n<strong>La protection contre la foudre du syst\u00e8me de distribution d'\u00e9nergie basse tension est la suivante\u00a0:<\/strong>\r\n\r\nThe main power distribution cabinet of the building is installed with a Class I power SPD as the first-level lightning protection of the power line.\r\n\r\nThe secondary power distribution cabinet (box) of the building is installed with a Class II power SPD as the second-level lightning protection of the power line.\r\n\r\nThe tertiary power distribution cabinet (box) of the building is installed with a Class II power SPD as the third-level lightning protection of the power line.\r\n\r\nFor important equipment ports, install Class III power SPD as terminal-level lightning protection for power lines.","protected":false},"featured_media":845,"parent":0,"menu_order":155,"template":"","meta":{"_acf_changed":false},"blog_category":[8],"class_list":["post-844","blog","type-blog","status-publish","has-post-thumbnail","hentry","blog_category-company-news"],"acf":{"des":"Lightning disasters mainly include direct lightning strikes, lightning electrostatic induction, and lightning electromagnetic pulses.","txt":"Lightning disasters mainly include direct lightning strikes, lightning electrostatic induction, and lightning electromagnetic pulses.\r\n\r\n<strong>Direct lightning strike<\/strong>\r\n\r\nDirect lightning strike refers to the physical phenomenon that the thundercloud discharges directly to the ground. If the ground is directly struck by lightning, a large instantaneous current will be generated at the location of the lightning strike. If the lightning current cannot be released in time, the object struck by the lightning will generate a lot of heat instantly, causing the object to expand, melt, burn, explode and other damage. Typically, buildings must consider the hazards of direct lightning strikes.\r\n\r\n<strong>Lightning electrostatic induction<\/strong>\r\n\r\nLightning induction means that when a charged thundercloud appears in the sky, metal lines, metal objects, etc. under the thundercloud to take on an electric charge opposite to that of a thundercloud by electrostatic induction. When a lightning strike occurs, the thundercloud charge quickly disappears through the lightning strike. The induced charge on the metal line propagates along the line, causing transient overvoltage at the line port of the device. If the induced charge on the metal object cannot disappear in time, there will be an external discharge phenomenon, which will form a spark.\r\n\r\n<strong>Lightning electromagnetic pulse<\/strong>\r\n\r\nLightning electromagnetic pulse refers to the instantaneous formation of a lightning electromagnetic field in the area where the lightning strike occurs due to the extremely large peak value and speed of the lightning current. Under the action of the changing lightning electromagnetic field, metal lines in the area induce instantaneous lightning current. If the lightning current penetrates into the power supply line and communication line, transient overvoltage may occur on the device\u2019s line port.\r\n\r\nLightning protection of low-voltage power distribution system is to prevent the low-voltage power distribution system from introducing lightning current from lines outside the building.\r\n\r\n<strong>Basic lightning protection measures<\/strong>\r\n\r\nFor low-voltage power distribution systems, the commonly used arrester models and parameters are as follows:\r\n\r\n<strong>Class I three-phase power SPD (for TN-S system)<\/strong>\r\n\r\nModel: BR-25GR 4P\r\n\r\nMax. continuous operating voltage: 275V~\r\n\r\nLightning impulse current: 25kA (10\/350\u03bcs)\r\n\r\nNominal discharge current: 25kA (8\/20\u03bcs)\r\n\r\nMax. discharge current: 100kA (8\/20\u03bcs)\r\n\r\nMain function: installed in the main power distribution cabinet, as the first-level lightning protection of the power line.\r\n\r\n<strong>Class I three-phase power SPD (for TN-C system)<\/strong>\r\n\r\nModel: BR-25GR 3P\r\n\r\nMax. continuous operating voltage: 275V~\r\n\r\nLightning impulse current: 25kA (10\/350\u03bcs)\r\n\r\nNominal discharge current: 25kA (8\/20\u03bcs)\r\n\r\nMax. discharge current: 100kA (8\/20\u03bcs)\r\n\r\nMain function: installed in the main power distribution cabinet, as the first-level lightning protection of the power line.\r\n\r\n<strong>Class I three-phase power SPD (for TT system)<\/strong>\r\n\r\nModel: BR-25GR 3P+NPE\r\n\r\nMax. Continuous operating voltage: 275V~\r\n\r\nLightning impulse current: 25Ka\/50kA (10\/350\u03bcs)\r\n\r\nNominal discharge current: 25kA\/50kA (8\/20\u03bcs)\r\n\r\nMax. discharge current: 100kA (8\/20\u03bcs)\r\n\r\nMain function: installed in the main power distribution cabinet, as the first-level lightning protection of the power line.\r\n\r\n<strong>Class II three-phase power SPD (for TN-S or TN-C-S systems)<\/strong>\r\n\r\nModel: BR-40 4P\r\n\r\nMax. continuous operating voltage: 275V~\r\n\r\nNominal discharge current: 20kA (8\/20\u03bcs)\r\n\r\nMax. discharge current: 40kA (8\/20\u03bcs)\r\n\r\nMain function: installed in the sub-power distribution box, as the second-level lightning protection of the power line.\r\n\r\n<strong>Class II three-phase power SPD (for TT system)<\/strong>\r\n\r\nModel: BR-40 3P+NPE\r\n\r\nMax. continuous operating voltage: 275V~\r\n\r\nNominal discharge current: 20kA (8\/20\u03bcs)\r\n\r\nMax. discharge current: 40kA (8\/20\u03bcs)\r\n\r\nMain function: installed in the sub-power distribution box, as the second-level lightning protection of the power line.\r\n\r\n<strong>The lightning protection of the low-voltage power distribution system is as follows:<\/strong>\r\n\r\nThe main power distribution cabinet of the building is installed with a Class I power SPD as the first-level lightning protection of the power line.\r\n\r\nThe secondary power distribution cabinet (box) of the building is installed with a Class II power SPD as the second-level lightning protection of the power line.\r\n\r\nThe tertiary power distribution cabinet (box) of the building is installed with a Class II power SPD as the third-level lightning protection of the power line.\r\n\r\nFor important equipment ports, install Class III power SPD as terminal-level lightning protection for power lines."},"_links":{"self":[{"href":"https:\/\/www.britecelectric.com\/fr\/wp-json\/wp\/v2\/blog\/844","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/www.britecelectric.com\/fr\/wp-json\/wp\/v2\/blog"}],"about":[{"href":"https:\/\/www.britecelectric.com\/fr\/wp-json\/wp\/v2\/types\/blog"}],"wp:featuredmedia":[{"embeddable":true,"href":"https:\/\/www.britecelectric.com\/fr\/wp-json\/wp\/v2\/media\/845"}],"wp:attachment":[{"href":"https:\/\/www.britecelectric.com\/fr\/wp-json\/wp\/v2\/media?parent=844"}],"wp:term":[{"taxonomy":"blog_category","embeddable":true,"href":"https:\/\/www.britecelectric.com\/fr\/wp-json\/wp\/v2\/blog_category?post=844"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}