Χαρακτηριστικά προϊόντος:
| Προσδιορισμός | BR-80 150 3P | BR-80 275 3P | BR-80 320 3P | BR-80 385 3P | ||
| SPD classification according to EN61643-11 | Τύπος 2 | Τύπος 2 | Τύπος 2 | Τύπος 2 | ||
| SPD classification according to IEC61643-11 | Class II | Class II | Class II | Class II | ||
| Max. continuous operating a.c. voltage | Uc | 150V | 275V | 320V | 385V | |
| Ονομαστικό ρεύμα εκφόρτισης (8/20μs) | Σε | 40 kA | 40 kA | 40 kA | 40 kA | |
| Μέγ. ρεύμα εκφόρτισης (8/20μs) | Imax | 80kA | 80kA | 80kA | 80kA | |
| Επίπεδο προστασίας τάσης | Επάνω | ≤1.0kV | ≤1.7kV | ≤2.0kV | ≤2.3kV | |
| Voltage protection level 5kA | Επάνω | ≤0.6kV | ≤1.0kV | ≤1.1kV | ≤1.2kV | |
| Max. backup fuse | 160A gG | 160A gG | 160A gG | 160A gG | ||
| Short-circuit withstand capacity | Isccr | 25 kA | 25 kA | 25 kA | 25 kA | |
| Temporary overvoltage TOV-withstand | UT | 180V/5sec. | 335V/5sec. | 400V/5sec. | 500V/5sec. | |
| Temporary overvoltage TOV-safe failure | UT | 230V/120min. | 440V/120min. | 520V/120min. | 650V/120min. | |
| Χρόνος απόκρισης | tA | ≤25ns | ≤25ns | ≤25ns | ≤25ns | |
| Εύρος θερμοκρασίας λειτουργίας | Tu | -40℃-80℃ | -40℃-80℃ | -40℃-80℃ | -40℃-80℃ | |
| Operating state/fault indication | green/red | green/red | green/red | green/red | ||
| Εμβαδόν διατομής (ελάχ.) | 4mm² | 4mm² | 4mm² | 4mm² | ||
| Εμβαδόν διατομής (Μέγ.) | 35 mm² | 35 mm² | 35 mm² | 35 mm² | ||
| Για τοποθέτηση σε | Ράγα Din 35mm | |||||
| Υλικό περιβλήματος | Thermoplastic UL94-V0 | |||||
| Βαθμός προστασίας | IP20 | IP20 | IP20 | IP20 | ||
| Order Code | B18268 | B18270 | B18272 | B18274 | ||
| Order Code (With remote signaling) | B18269 | B18271 | B18273 | B18275 | ||
Χαρακτηριστικά:
Visual status display
Labeled connections
Type 2 (class II/C) for main boards, distribution boards and consumer units.
Available with and without remote signalling contacts.
1 pole up to 4 poles protected.
BR-80 consists of a high performance varistor block with thermal disconnection device. The plug-in module/base design facilitates replacement of a failed module in situ without the need to remove system wiring.
Solutions to meet IEC 61643-1 and EN 61643-11
Εφαρμογή:
Distribution switch board located downstream from a Type 1 Lightning Current Arrester.
Protecting them from direct and indirect lightning impulse and other transient overvoltage.
Protects low-voltage systems against overvoltage triggered by lightning strikes or grid switching operations.
Ideal for industrial applications.
At the origin of the electrical installation in the main switchboard, in areas where electromagnetic fields caused by lightning currents are dominant (excluding a direct strike).
Suitable for TN-C systems.
Preventing the spread of medium overvoltage (Up) in the electrical installation and protecting equipment that is connected to it.
Περισσότερες πληροφορίες ή προσωπική διαβούλευση; Τα προϊόντα και η τεχνογνωσία μας υπάρχουν για να δώσουν λύσεις.