Συσκευή προστασίας από υπερτάσεις BR-7M 1+1 7kA Τύπου 1+2 / B+C για TT και TNS

Λάβετε μια προσφορά
Περιγραφή

Χαρακτηριστικά προϊόντος:

Προσδιορισμός BR-7M 150 1+1 ΜΡ-7Μ 275 1+1 BR-7M 320 1+1
SPD classification according to EN61643-11 Type 1 + Type 2 Type 1 + Type 2 Type 1 + Type 2
SPD classification according to IEC61643-11 Class I + Class II Class I + Class II Class I + Class II
Max. continuous operating a.c. voltage Uc(L-N/N-PE) 150V/255V(50/60Hz) 275V/255V(50/60Hz) 320V/255V(50/60Hz)
Lightning impulse current (10/350μs) Iimp(L-N/N-PE) 7kA/12.5kA 7kA/12.5kA 7kA/12.5kA
Ονομαστικό ρεύμα εκφόρτισης (8/20μs) In(L-N/N-PE) 20kA/50kA 20kA/50kA 20kA/50kA
Μέγ. ρεύμα εκφόρτισης (8/20μs) Imax(L-N/N-PE) 50kA/100kA 50kA/100kA 50kA/100kA
Specific energy W/R(L-N/N-PE) 12.25kJ/Ω, 39kJ/Ω 12.25kJ/Ω, 39kJ/Ω 12.25kJ/Ω, 39kJ/Ω
Επίπεδο προστασίας τάσης Up(L-N/N-PE) ≤0.8kV/≤1.5kV ≤1.3kV/≤1.5kV ≤1.5kV/≤1.5kV
Short-circuit current rating a.c. Isccr 25kA rms 25kA rms 25kA rms
Max. backup fuse 125A gG 125A gG 125A gG
Temporary overvoltage TOV-withstand UT(L-N) 180V/5sec. 335V/5sec. 400V/5sec.
Temporary overvoltage TOV-safe failure UT(L-N) 230V/120min. 440V/120min. 520V/120min.
Temporary overvoltage TOV-withstand UT(N-PE) 1200V/200ms 1200V/200ms 1200V/200ms
Χρόνος απόκρισης tA(L-N/N-PE) ≤25ns/≤100ns ≤25ns/≤100ns ≤25ns/≤100ns
Εύρος θερμοκρασίας λειτουργίας Tu -40℃-80℃ -40℃-80℃ -40℃-80℃
Operating state/fault indication green/red green/red green/red
Εμβαδόν διατομής (ελάχ.) 4mm² 4mm² 4mm²
Εμβαδόν διατομής (Μέγ.) 35 mm² 35 mm² 35 mm²
Για τοποθέτηση σε Ράγα Din 35mm
Υλικό περιβλήματος Θερμοπλαστικό UL94-V0
Βαθμός προστασίας IP20 IP20 IP20
Order Code B17330 B17332 B17334
Order Code (With remote signaling) B17331 B17333 B17335

Χαρακτηριστικά:

Surge arrester for low-voltage power supply system protection against surges.

SPD is suitable for AC 50/60HZ, TT power supply systems.

Protective device adopts 35mm Din rail type mounting.

Designed according to IEC61643-11 and GB18802.1 standards.

As the protector normal works that the pilot lamp is green.

Εφαρμογή:

Widely suitable for TT system, for protecting the buildings.

Εγκατάσταση:

Wiring according to the mark of surge protector according to the wiring diagram.

When installed according to the installation diagram shows the connection, where l (L1, L2, L3) for the line, n is neutral, PE ground wire, do not mistake. After the installation is complete, check that the protection unit is plugging in place, close the automatic circuit breaker (fuse) switch, check the working status is normal.

Protector in use during the fault display window should periodically verify and view state when red fault display window or remote Terminal outputs alarm signals, the protector fails, should be repaired or replaced in a timely manner.

 

ΕΙΜΑΣΤΕ ΕΔΩ ΓΙΑ ΝΑ ΣΑΣ ΥΠΟΣΤΗΡΙΞΟΥΜΕ!

Περισσότερες πληροφορίες ή προσωπική διαβούλευση; Τα προϊόντα και η τεχνογνωσία μας υπάρχουν για να δώσουν λύσεις.

ΣΧΕΤΙΚΑ ΠΡΟΪΟΝΤΑ
ΣΧΕΤΙΚΑ ΝΕΑ
ΜΠΟΡΕΙ ΕΠΙΣΗΣ ΝΑ ΘΕΛΕΤΕ ΝΑ ΔΕΙΤΕ
ΑΠΟΚΤΗΣΤΕ ΤΗΝ ΠΡΟΣΤΑΣΙΑ ΑΠΟ ΤΥΠΟΥΣ
ΛΥΣΗ ΣΗΜΕΡΑ!
εικόνισμα
εικόνισμα
Seraphinite AcceleratorOptimized by Seraphinite Accelerator
Turns on site high speed to be attractive for people and search engines.