BR-50GR 3+1 Type 1 50kA Surge Arrester for TT and TNS

Λάβετε μια προσφορά
Περιγραφή

Χαρακτηριστικά προϊόντος:

Προσδιορισμός BR-50GR 150 3+1 BR-50GR 275 3+1 BR-50GR 350 3+1
SPD classification according to EN61643-11 Type 1 + Type 2 Type 1 + Type 2 Type 1 + Type 2
SPD classification according to IEC61643-11 Class I + Class II Class I + Class II Class I + Class II
Nominal operating voltage Ηνωμένα Έθνη 120V/240V(50/60Hz) 230V/400V(50/60Hz) 250V/440V(50/60Hz)
Max. continuous operating a.c. voltage Uc (L-N/N-PE) 150V/255V(50/60Hz) 275V/255V(50/60Hz) 350V/255V(50/60Hz)
Lightning impulse current (10/350μs) Iimp (L-N/N-PE) 50kA/100kA 50kA/100kA 50kA/100kA
Ονομαστικό ρεύμα εκφόρτισης (8/20μs) In (L-N/N-PE) 50kA/100kA 50kA/100kA 50kA/100kA
Μέγ. ρεύμα εκφόρτισης (8/20μs) Imax (L-N/N-PE) 160kA/200kA 160kA/200kA 160kA/200kA
Quantity of electric charge (L-N, N-PE) Q 25As, 50As 25As, 50As 25As, 50As
Specific energy (L-N, N-PE) W/R 625kJ/Ω, 2500kJ/Ω 625kJ/Ω, 2500kJ/Ω 625kJ/Ω, 2500kJ/Ω
Επίπεδο προστασίας τάσης Up (L-N/N-PE) ≤1.5kV/≤1.5kV ≤1.5kV/≤1.5kV ≤1.5kV/≤1.5kV
Short-circuit current rating a.c. Isccr (L-N/N-PE) 25kA rms/100A rms 25kA rms/100A rms 25kA rms/100A rms
Max. backup fuse 350A gG 350A gG 350A gG
Temporary overvoltage TOV-withstand UT (L-N) 230V/120min. 440V/120min. 580V/120min.
Temporary overvoltage TOV-withstand UT (N-PE) 1200V/200ms 1200V/200ms 1200V/200ms
Χρόνος απόκρισης tA ≤100ns ≤100ns ≤100ns
Εύρος θερμοκρασίας λειτουργίας Tu -40℃-80℃ -40℃-80℃ -40℃-80℃
Operating state/fault indication green/red green/red green/red
Εμβαδόν διατομής (ελάχ.) 4mm² 4mm² 4mm²
Εμβαδόν διατομής (Μέγ.) 35 mm² 35 mm² 35 mm²
Για τοποθέτηση σε Ράγα Din 35mm
Υλικό περιβλήματος Θερμοπλαστικό UL94-V0
Βαθμός προστασίας IP20 IP20 IP20
Order Code B17166 B18167 B17192
Order Code (With remote signaling) B17167 B18168 B17193

Χαρακτηριστικά:

Endurable, sustains multiple strikes.

LED status indication.

Protection class: Type 1+2, Class I +Class II.

BR-50GR 3P+N is suitable for TT and TN-S system.

Εφαρμογή:

● Suitable for TT and TN-S system.

● Used in industrial systems and buildings with external lightning protection of Classes I to IV.

● For the protection of low voltage distribution systems against direct lightning strike into the overhead power supply line or external lightning protection system.

● Can be used in standard distributor housing.

● Used to protect all kinds of electrical equipment in the power system from lightning over-voltage, operation over-voltage, power frequency transient over-voltage impact damage to an electrical appliance.

 

ΕΙΜΑΣΤΕ ΕΔΩ ΓΙΑ ΝΑ ΣΑΣ ΥΠΟΣΤΗΡΙΞΟΥΜΕ!

Περισσότερες πληροφορίες ή προσωπική διαβούλευση; Τα προϊόντα και η τεχνογνωσία μας υπάρχουν για να δώσουν λύσεις.

ΣΧΕΤΙΚΑ ΠΡΟΪΟΝΤΑ
ΣΧΕΤΙΚΑ ΝΕΑ
ΜΠΟΡΕΙ ΕΠΙΣΗΣ ΝΑ ΘΕΛΕΤΕ ΝΑ ΔΕΙΤΕ
ΑΠΟΚΤΗΣΤΕ ΤΗΝ ΠΡΟΣΤΑΣΙΑ ΑΠΟ ΤΥΠΟΥΣ
ΛΥΣΗ ΣΗΜΕΡΑ!
εικόνισμα
εικόνισμα
Seraphinite AcceleratorOptimized by Seraphinite Accelerator
Turns on site high speed to be attractive for people and search engines.