Χαρακτηριστικά προϊόντος:
| Προσδιορισμός | BR-40VG 150 1P | BR-40VG 275 1P | BR-40VG 320 1P | BR-40VG 385 1P | BR-40VG 440 1P | |
| SPD classification according to EN61643-11 | Τύπος 2 | Τύπος 2 | Τύπος 2 | Τύπος 2 | Τύπος 2 | |
| SPD classification according to IEC61643-11 | Class II | Class II | Class II | Class II | Class II | |
| Max. continuous operating a.c. voltage | Uc | 150V | 275V | 320V | 385V | 440V |
| Ονομαστικό ρεύμα εκφόρτισης (8/20μs) | Σε | 20 kA | 20 kA | 20 kA | 20 kA | 20 kA |
| Μέγ. ρεύμα εκφόρτισης (8/20μs) | Imax | 40 kA | 40 kA | 40 kA | 40 kA | 40 kA |
| Επίπεδο προστασίας τάσης | Επάνω | ≤1.3kV | ≤1.3kV | ≤1.5kV | ≤1.8kV | ≤2.0kV |
| Max. backup fuse | 100A gG | 100A gG | 100A gG | 100A gG | 100A gG | |
| Short-circuit withstand capacity | Isccr | 25 kA | 25 kA | 25 kA | 25 kA | 25 kA |
| Temporary overvoltage TOV-withstand | UT | 180V/5sec. | 335V/5sec. | 400V/5sec. | 500V/5sec. | 580V/5sec. |
| Temporary overvoltage TOV-safe failure | UT | 230V/120min. | 440V/120min. | 520V/120min. | 650V/120min. | 765V/120min. |
| Χρόνος απόκρισης | tA | ≤100ns | ≤100ns | ≤100ns | ≤100ns | ≤100ns |
| Εύρος θερμοκρασίας λειτουργίας | Tu | -40℃-80℃ | -40℃-80℃ | -40℃-80℃ | -40℃-80℃ | -40℃-80℃ |
| Operating state/fault indication | green/red | green/red | green/red | green/red | green/red | |
| Εμβαδόν διατομής (ελάχ.) | 4mm² | 4mm² | 4mm² | 4mm² | 4mm² | |
| Εμβαδόν διατομής (Μέγ.) | 35 mm² | 35 mm² | 35 mm² | 35 mm² | 35 mm² | |
| Για τοποθέτηση σε | Ράγα Din 35mm | |||||
| Υλικό περιβλήματος | Thermoplastic UL94-V0 | |||||
| Βαθμός προστασίας | IP20 | IP20 | IP20 | IP20 | IP20 | |
| Order Code | B17500 | B17512 | B17524 | B17536 | B17548 | |
| Order Code (With remote signaling) | B17501 | B17513 | B17525 | B17537 | B17549 | |
Χαρακτηριστικά:
Class II / Type 2 lightning protective device.
In: 20kA.
For using in the lightning protection zones concept at boundary 1-2.
Module design, convenient installation
Low residual voltage and quick response.
Time of response ˂ 100ns
With remote signaling contact for control device.
Protecting low-voltage consumers’ installations against indirect lightning discharges.
Fault indication via red mark in the inspection window.
Power Source : Electric
Plug-in module/base design facilitate replacement of a failed module without the need to remove system wiring etc.
Εφαρμογή:
Protection of an electrical installation and all electrical and electronic devices connected this installation against destructive overvoltage surges.
Surge arresters cover the protection of home appliances, commercial building equipment, and industrial equipment.
The devices are especially designed to provide complete and effective protection against surges, protecting equipment and property connected to the low voltage network.
Περισσότερες πληροφορίες ή προσωπική διαβούλευση; Τα προϊόντα και η τεχνογνωσία μας υπάρχουν για να δώσουν λύσεις.