BR-12.5M 3P 12.5kA Type 1+2 Surge Protective Device For TN-C

Λάβετε μια προσφορά
Περιγραφή

Χαρακτηριστικά προϊόντος:

Προσδιορισμός BR-12,5M 150 3P BR-12,5M 275 3P BR-12,5M 320 3P
SPD classification according to EN61643-11 Type 1 + Type 2 Type 1 + Type 2 Type 1 + Type 2
SPD classification according to IEC61643-11 Class I + Class II Class I + Class II Class I + Class II
Max. continuous operating a.c. voltage Uc 150V(50/60Hz) 275V(50/60Hz) 320V(50/60Hz)
Lightning impulse current (10/350μs) Iimp 12,5 kA 12,5 kA 12,5 kA
Ονομαστικό ρεύμα εκφόρτισης (8/20μs) Σε 25 kA 25 kA 25 kA
Μέγ. ρεύμα εκφόρτισης (8/20μs) Imax 60kA 60kA 60kA
Specific energy W/R 39kJ/Ω 39kJ/Ω 39kJ/Ω
Επίπεδο προστασίας τάσης Επάνω ≤0.8kV ≤1.3kV ≤1.5kV
Short-circuit current rating a.c. Isccr 25kA rms 25kA rms 25kA rms
Max. backup fuse 125A gG 125A gG 125A gG
Temporary overvoltage TOV-withstand UT(L-N) 180V/5sec. 335V/5sec. 400V/5sec.
Temporary overvoltage TOV-safe failure UT(L-N) 230V/120min. 440V/120min. 520V/120min.
Χρόνος απόκρισης tA ≤25ns ≤25ns ≤25ns
Εύρος θερμοκρασίας λειτουργίας Tu -40℃-80℃ -40℃-80℃ -40℃-80℃
Operating state/fault indication green/red green/red green/red
Εμβαδόν διατομής (ελάχ.) 4mm² 4mm² 4mm²
Εμβαδόν διατομής (Μέγ.) 35 mm² 35 mm² 35 mm²
Για τοποθέτηση σε Ράγα Din 35mm
Υλικό περιβλήματος Θερμοπλαστικό UL94-V0
Βαθμός προστασίας IP20 IP20 IP20
Order Code B18311 B18313 B18315
Order Code (With remote signaling) B18312 B18314 B18316

Χαρακτηριστικά:

Britec hold patent for the design.

It adopts 35mm standard rail.

Time of response 25ns.

The plug-in module / base design facilitate replacement of a failed module without the need to remove system wiring etc.

There is a failure release mounted on the module of surge protective device.

It consists of a high performance varistor with thermal disconnection tripping device.

When the SPD fails in breakdown for over-heat and over-current, the failure release will help electric device separate from the power system and give the indication signal, green means normal, red means abnormal.

Εφαρμογή:

Used to guard sensitive equipment from voltage spike.

It is applied to low-voltage distribution system, which is connected in parallel between power supply and system equipment to protect the damage caused by instantaneous overvoltage caused by external (lightning

strike, electromagnetic radiation interference, etc.) or internal (system closing effect, induction and start and stop of capacitive load, etc.).

Εγκατάσταση:

Installed in low-voltage distributions at the boundary of LPZ 0–LPZ 1 zones and higher to prevent overvoltage effects induced during a lightning strike and to prevent switching overvoltage.

Install in the main distribution cabinet/box of the low-voltage cabinet and the incoming line cabinet.

Recommended for main distribution boards.

During installation, please connect according to the installation schematic diagram, where L1, L2 and L3 are phase lines, N is the zero line and PE is the ground line.

Grounding should conform to the requirements of the specification of lightning protection.

 

ΕΙΜΑΣΤΕ ΕΔΩ ΓΙΑ ΝΑ ΣΑΣ ΥΠΟΣΤΗΡΙΞΟΥΜΕ!

Περισσότερες πληροφορίες ή προσωπική διαβούλευση; Τα προϊόντα και η τεχνογνωσία μας υπάρχουν για να δώσουν λύσεις.

ΣΧΕΤΙΚΑ ΠΡΟΪΟΝΤΑ
ΣΧΕΤΙΚΑ ΝΕΑ
ΜΠΟΡΕΙ ΕΠΙΣΗΣ ΝΑ ΘΕΛΕΤΕ ΝΑ ΔΕΙΤΕ
ΑΠΟΚΤΗΣΤΕ ΤΗΝ ΠΡΟΣΤΑΣΙΑ ΑΠΟ ΤΥΠΟΥΣ
ΛΥΣΗ ΣΗΜΕΡΑ!
εικόνισμα
εικόνισμα
Seraphinite AcceleratorOptimized by Seraphinite Accelerator
Turns on site high speed to be attractive for people and search engines.